background image

English

12

WHEN ELECTRIC WIRING WORK IS NOT FINISHED

CAUTION

Electrical wiring work should be done by a certified electrician.

If someone who does not have the proper qualifications performs the work, perform the following after 
test run is complete.

Remove the control box lid. Connect the single phase power supply (SINGLE PHASE 50/60Hz 
220-240V/220V) to connections No.1 and No.2 on the terminal block for wiring the units. Do not con-
nect to No.3 of the terminal block for wiring the units. (The drain pump will not operate.) Connect the 
ground wire firmly. When carrying out wiring work around the control box, make sure none of the con-
nectors come undone. Be sure to attach the control box before turning on the power.

After confirming drainage 

(Fig. 16, Fig. 17)

, turn off the power and remove the power supply.

Attach the control box lid as before.

8. ELECTRIC WIRING WORK

All field supplied parts and materials and electric works must conform to local codes.

Use copper wire only.

For electric wiring work, refer also to “13. WIRING DIAGRAM” 

For remote controller wiring details, refer to the installation manual attached to the remote controller.

All wiring must be performed by an authorized electrician.

A circuit breaker capable of shutting down power supply to the entire system must be installed.

Refer to the installation manual attached to the outdoor unit and BP unit for the size of power supply electric 
wire connected to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.

Be sure to ground the air conditioner

Do not connect the ground wire to gas pipes, plumbing pipes, lightning rods, or telephone ground wires.

Gas pipes: might cause explosions or fire if gas leaks.

Plumbing: no grounding effect if hard vinyl piping is used. 

Telephone ground wires or lightning rods: might cause abnormally high electric potential in the ground
during lighting storms.

• Specifications for field wire

The remote controller cord should be procured locally. Refer to the Table 2 when preparing one.

Table 2

NOTE

1.

Shows only in case of protected pipes. Use H07RN-F in case of no protection.

2.

For Asian market : Vinyl cord with sheath or cable (Insulated thickness : 1mm or more)
For Australian regular : Shield wire (Insulated thickness : 1mm or more)

Wire

Size (mm

2

)

Length

Wiring the units

H05VV - U4G (NOTE 1)

2.5

-

Remote controller cord

(NOTE 2) (2 wires)

0.75 - 1.25

Max. 500 m

1 2 3

Control box

Terminal block for wiring

Single phase power supply

Fig. 17

01_EN_3P156215-4C.fm  Page 12  Saturday, May 14, 2005  9:17 AM

Summary of Contents for FBQ60BV1

Page 1: ...FBQ60BV1 FBQ60BVL FBQ71BV1 FBQ71BVL SPLIT SYSTEM Air Conditioners INSTALLATION MANUAL READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE 00_C...

Page 2: ...caution may result in injury or damage to the equipment WARNING Ask your dealer or qualified personnel to carry out installation work Do not try to install the air conditioner yourself Improper instal...

Page 3: ...aves a distance of 1 meter may not be sufficient enough to eliminate the noise Remote controller wireless kit transmitting distance can result shorter than expected in rooms with elec tronic fluoresce...

Page 4: ...de Where volatile flammable gas like thinner or gasoline is used Where machines can generate electromagnetic waves Control system may malfunction Where the air contains high levels of salt such as tha...

Page 5: ...35 cm or more Installation not required Items to be checked If not properly done what is likely to occur Check Are the indoor unit and outdoor unit fixed firmly The unit may drop vibrate or make noise...

Page 6: ...e gas leakage Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual for the outdoor unit CAUTION Keep indoor unit outdoor unit power sup...

Page 7: ...ure by changing the initial setting from the remote controller Refer to the section entitled 10 FIELD SETTING Indoor unit Suspension bolt 4 1000 Indoor unit 1050 Suspension bolt pitch Pipe 630 145 Sus...

Page 8: ...Fig 3 2 Check the unit is horizontally level Refer to Fig 4 CAUTION The indoor unit is equipped with a built in drain pump and float switch Verify that it is level by using a level or a water filled...

Page 9: ...either pinch the end or cover it with tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while wor...

Page 10: ...copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine base...

Page 11: ...rain pipe from sagging space hanging wires every 1 to 1 5 m CAUTION Water pooling in the drainage piping can cause the drain to clog Use the attached drain hose 3 and Metal clamp 1 Insert the drain ho...

Page 12: ...n the water inlet lid add approximately 1000 cc of water gradually and check drainage flow Refer to Fig 16 NOTE Use the drain outlet for maintenance to drain water from the drain pan WHEN ELECTRIC WIR...

Page 13: ...performed by an authorized electrician A circuit breaker capable of shutting down power supply to the entire system must be installed Refer to the installation manual attached to the outdoor unit and...

Page 14: ...g the units Doing so may cause malfunction Remote controller cord Control box Control box lid WIRING DIAGRAM Fig 18 CAUTION After wiring adhere the attached small sealing pad 13 around the wires as sh...

Page 15: ...Observe the notes when wiring to the terminal block for wiring the units Use a round crimp style terminal with insulation sleeve for connection to the terminal block for wiring the units In case it ca...

Page 16: ...be used connect a shielded portion with the grounding terminal for remote controller inside the control box Also connect the ground for the remote control to a grounded metal part 3 For group control...

Page 17: ...able 4 4 When implementing group control When using as a pair unit or as a parent unit for simultaneous operation multi you may simultaneous start stop group control up to 16 unit with the remote cont...

Page 18: ...y and decoration panel 12 TEST OPERATION Refer to the section of FOR THE FOLLOWING ITEMS TAKE SPECIAL CARE DURING CON STRUCTION AND CHECK AFTER INSTALLATION IS FINISHED After finishing the constructio...

Page 19: ...recognized NOTE 2 NOTE 1 In case wired remote controller Press the INSPECTION TEST OPERATION button on remote con troller starts flashing and changes the inspection mode 2 Keep down the ON OFF button...

Page 20: ...function outdoor unit H9 Outdoor air thermistor faulty outdoor unit J3 Discharge pipe thermistor faulty outdoor unit J5 Suction pipe thermistor faulty outdoor unit J6 Heat exchanger thermistor faulty...

Page 21: ...the fan mounted on the outdoor unit may start operation independent of the remote controller operation U5 Transmission error indoor unit remote controller Transmission is improper between the indoor...

Page 22: ...DAPTOR FOR SKY AIR SERIES CONTROL BOX TO BP UNIT INDOOR UNIT WIRED REMOTE CONTROLLER OPTIONAL PARTS NOTE 7 NOTE 7 CONNECTER DISCRIMINATION COLOUR FOR COMPONENTS CONNECTER COLOUR FOR COMPONENTS CONNECT...

Page 23: ...0506 HT 3P156215 4C EM04A076B 00_CV_3P156215 4C fm Page 2 Saturday May 14 2005 10 52 AM...

Reviews: