PRECAUTION
Connection of wiring units, ground wire and remote controller cord. (Refer to Fig. 18 and 19)
• Wiring the units and ground for the wire
Remove the control box lid and pull out the control box.
(Refer to Fig. 18)
Next, pull the wires inside through the rubber bush A and connect them to their respective terminals on the
terminal block for wiring the units (4P) inside. Also, connect the ground wire to the ground terminal. In doing
this, pull the wiring through the rubber bush A and fix it in place with the clamp.
• Remote controller cord
Connect the cord to the terminal block for remote controller (2P) (no polarity). In doing this, pull the wiring
through the rubber bush B and fix it in place with the clamp.
A
Rubber bush B
Rubber bush A
*Wiring the units
*Do not clamp remote
controller cords together with
wires connecting the units.
Doing so may cause
malfunction.
*Remote controller cord
Control box
Control box lid
WIRING DIAGRAM
Fig. 18
CAUTION
• After wiring, adhere the attached
small sealing pad (13) around the
wires as shown below.
(Be sure to adhere it to avoid
water from outside unit.)
Rubber bush
Note) No gap are allowed.
(Between rubber bush
and sealing material.)
Note) In case of two wires or more,
adhere sealing material to
each wire separately.
Inside unit
Outside unit
Wire
[ How to adhere it ]
Small sealing pad (13)
(Adhere it around the wire)
Motor lead wire
Control box
Terminal block for
wiring the units
Terminal block for remote controller
Indoor PC board
Shield part
C-cup
washer
Ground the shield
part of shield wire.
If using shield wire.
Refer to NOTE of
“9. WIRING EXAMPLE”
Grounding terminal for
the remote controller
Grounding
terminal
Arrow view A
Fig. 19
1 2 3
P1 P2
Remote
controller
cord
Clamp material
Wiring the
units
Ground
wire
(10) Clamp (attached)
Clamp material
(10) Clamp (attached)