Daikin F Operation Manual Download Page 32

11 

Trail  Operation And Testing 

1. Trial operation and testing

•  Check that the inter-unit wire is correctly connected. 
•  Trial operation should be carried out in COOL operation. 

1·1 Measure the supply voltage and make sure that It Is within the specified range. 

1-2  Select the lowest programmable temperature.

1-3 Carry out the trial operation following the Instructions In the operation manual to ensure that all functions and parts, 

such as the movement of the flaps, are working properly. 

• To protect the air conditioner,  restart  operation is disabled  for 3 minutes alter the system has been turned off.

1-4 After trial operation Is complete, set the temperature to a normal leval (26

°

C to 28

°

C in COOL  operation, 20

°

c to 24

°

In HEAToperation). 

•  When operating the air conditioner in COOL operation in winter, or HEAT operation in summer, set it ID the trial operation mode using the following method. 

1)  Press "MODE" button and select the cooling or heating mode. 

2)  Press "ON/OFF" button ID turn on the sys1em. 

3)  Press both of "TEMP" button and "MODE" button at the same time. 

4)  Press "TEMP" button, select •r·, and press "MODE" button for conlmiation. 

■ Trial operation will stop automatically after about 30 minutes. To stop the operation press "ON/OFF" button. 

• The air conditioner draws a smal amount of power in its standby mode. II the system is notto be used for some time alter installation, srut off the circuit breaker to 

eliminate unnecessary power consumption. 

• If the circuit breaker trips to shut  off the power to the air conditioner, the system wil restore the original operation mode when the circuit breaker is 

turned  on again. 

2. Items to Check

Test  Items 

Symptom 

Check 

Indoor and outdoor units are installed securely. 

Fall,  vibration,  noise 

No  refrigerant  gas  leaks. 

Incomplete  cooling function 

Refrigerant gas and  liquid pipes and  indoor drain  hose 

Water leakage 

extension  are  thermally  insulated. 
Draining  line  is  properly installed. 

Water leakage 

System is proper1y  earthed. 

Electrical leakage 

Only specified wires are  used for all  wiring,  and all 

I

No operation or  bum damage 

wires  are  connected correctly. 
Indoor or outdoor unit's air intake or exhaust has clear path of  air. 

Incomplete  coolinQ  function 

Stop valves are  opened. 

Incomplete cooling function 

Indoor unit properly receives remote controller commands.  No operation 

Pump Down Operation 

� WARNING--------------

• Make sure that air or any matter other than refrigerant (R32) does not get into the refrigeration cycle.

• When performing a pump down, turn off the compressor before detaching the refrigerant pipes.  {If the refrigerant pipes are detached when 

the compressor Is operating and the stop valves are open, air will be drawn In leading to abnormally high pressure In the 

refrigeration cycle. This may result in rupturing and bodily injury.)

In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 

1)  Remove the valve cap from the liquid stop valve and gas stop valve. 

2)  Begin forced cooling operation. 
3)  Alter 5 to  10 minutes, close the liquid stop valve with a hexagonal wrench. 
4)  After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation. 
5)  Attach the valve cap once procedures are complete. 

Liquid stop valve 

�Hexagonal 

wrench 

lose 

Gas stop 

valve 

-

ve cap 

Forced cooling operation 

Service port -

■  Using the indoor unit ON/OFF switch

Press and hold the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.) 

• Forced cooling operation will stop automatically alter about 15 minutes.

To stop the operation, press the indoor unit ON/OFF switch. 

Disclaimer: Appearance of indoor & outdoor unit may differ 

between different models. 

Summary of Contents for F

Page 1: ...MTKM60UV16U FTKT35UV16W FTKT50UV16V FTKT60UV16U FTKN35UV16W FTKN50UV16V A D F G MTKL35UV16W A D F G MTKL50UV16V A D F G MTKL50UV16U A D F GTKL60UV16U F GTKL71UV16T A F G MTKM50UV16VA F GTKC48UV16W F G...

Page 2: ...ity and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that produce naked flames i...

Page 3: ...receiver Receives signals from the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed beep Operation stop long beep...

Page 4: ...EEP DISPLAY button 15 DEW CLEAN button NOTE Notes on remote controller S NO 1 2 3 4 5 6 7 9 10 11 12 13 Never expose the remote controller to direct sunlight fJ 1 1 DAIICl fl D 2 REMOTE NO ARC484832 A...

Page 5: ...er Do not get it wet The maximum transmission distance is about 7m To attach the accessory filters Set the accessory filters under the tabs of the filter frame on the indoor streamer unit When attachi...

Page 6: ...ter and the decomposition power of the streamer discharge combine to reduce unpleasant odours and viruses cleaning the air in the room COANDA To start operation 1 Press C i i7 STREAMER When long press...

Page 7: ...LOCK disables all the buttons except when ECONO and POWERFULL button press togetherfor about 5 seconds To set the CHILD LOCK Press t ECONO and togetherfor about 5 seconds wie will be displayed on the...

Page 8: ...ction t ______ 1 Press swiNv and 7 1 and e are displayed on the LCD The flap and louvres move in turn To cancel 3 D airflow press either swiNGJ or ffiwiNG again The flap or louvres will stop moving To...

Page 9: ...B causes the settings to be cancelled and disappears from the LCD ECONO operation functions in COOL and DRY operation POWER CHILL and ECONO operation cannot be used at the same time is displayed on th...

Page 10: ...stop time default 2HR are displayed on the LCD i ol The TIMER lamp lights Display TEMP orange E 2 Press v while C is blinking Each pressing of the button changes tempera ture shift value by 1 C You ca...

Page 11: ...on Set temperature does not display when the unit is in DRY operation or FAN operation Inverter output and set temperature may not display depending on the operation mode that is active The display tu...

Page 12: ...F l hours 35 minutes Cooling operation To cancel DEW CLEAN operation Turn OFF the machine from Remote Controller Wi Fi Control NOTE Note on LED 7 Segment Brightness Control Ld indicates for the bright...

Page 13: ...nt panel shaft on the other side in the same manner After disengaging both front panel shafts pull the front panel toward yourself and remove it 3 Clean the front panel Wipe it with a soft damp cloth...

Page 14: ...ith a vacuum cleaner If the dust does not come off easily wash them with neutral detergent thinned with lukewarm water then let them dry in the shade Be sure to remove the accessory filter optional pa...

Page 15: ...ting procedures Item Titanium apatite deodorizing air purifying filter 1 set Ag ion filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set Micro filter PM2 5 for streamer unit 1 set Micro f...

Page 16: ...onditioner may stop operating after sudden large voltage fluctuations It automatically resumes operation in about 3 minutes Voltage range protection 130V 285V Voltage range protection 130V 265V for F...

Page 17: ...been tripped or the fuse blown operate Is there a power failure OPERATION lamp is off Are batteries set in the remote controller Is the timer setting correct The room does not cool down Is the airflow...

Page 18: ...air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood stop operation and turn off the circ...

Page 19: ...N MOTOR FAULT ES OVERCURRENT INPUT F3 HIGH TEMPERATURE DISCHARGE PIPE CONTROL F6 HIGH PRESSURE CONTROL IN COOLING F8 1 OPERATION HALT DUE TO COMPRESSOR INTERNAL TEMPERATURE ABNORMALITY OUTDOOR HO SENS...

Page 20: ......

Page 21: ...V16U F G MTKM60UV16U FTKT35UV16W FTKT50UV16V FTKT60UV16U FTKN35UV16W FTKN50UV16V A D F G MTKL35UV16W A D F G MTKL50UV16V A D F G MTKL50UV16U A D F GTKL60UV16U F GTKL71UV16T AJF GIMTKM50UV16VA F GTKC48...

Page 22: ...rant gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas le...

Page 23: ...may cause interferencewith the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby The outdoor unit should be positioned in a place where 1 th...

Page 24: ...lllq ral fir rufrlgerant pipe exaiedi 10min length Gas pipe Diameter mm Liquid pipe Diame1ar mm in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur de...

Page 25: ...l the front grille and firmly engage the upper hooks 3 locations 2 Install 3 screws of the front grille 3 Install the air filter and then mount the front panel Opening the service lid The service lid...

Page 26: ...298 X 821 X 235 298 X 885 X 229 298 X 906 X 235 Unit size available on name plate A B C 800 116 5 116 5 821 128 126 5 885 116 5 116 5 906 127 127 5 Table No 4 Applicable Unit Size Type H X W X D I 31...

Page 27: ...on the edge ofthe indoor unit 9 Securethe indoor unit to the A mounting plate with the E indoorunit fixingscrews M4 x12L 10 Caulk the gap between the pipe andthe frontgrille with putty 11 After comple...

Page 28: ...otincluded wi th the unit TableNo 6 WARNING Use a stabiliser if required by the voltage supply condition Do not use tapped wires extension cords or starburst connections as they may cause overheating...

Page 29: ...g W f 3l Heat insulationpipe cover SI This illustration shows the case of the left rear piping Drain hose Sectional view wire J rwrap more than ha heat insu ation tape Heat Insulation pipe cover Insul...

Page 30: ...ening torque tightening torque tightening torque 0 D 9 5mm 32 7 39 9N m 21 6 27 4N m 333 407 kgf cm 220 280 kgf cm Gas side 0 D 12 7mm 49 5 60 3N m 505 615 kgf cm 48 1 59 7N m 10 8 14 N m 0 D 15 9mm 6...

Page 31: ...e all soapy water off 7 Disconnect charginghosefrom gasstop valve s service port thenfullyopenliquidandgasstop valves Do not attempt to tum valve rod beyond its stop 8 Tighten valve caps and service p...

Page 32: ...noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated Draining line is properly installed W...

Page 33: ...0020 Meaning of E waste under E Waste Management Rules 2022 E waste Rules Waste electrical and electronic equipment whole or in part of reject from their manufacturing and repair process which are int...

Reviews: