7
Indoor Unit
Wiring
1) Strip wire ends (15mm).
2) Match wire colours with terminal numbers on indoor and outdoor
unit's terminal blocks and firmly screw wires to the corresponding
terminals with the screw.
3) Connect the earth wires to the corresponding terminals.
Attach the earth wire so that it is not connected to the fan motor connector.
4) Pull wires to make sure that they are securely latched up, then retain wires
with wire retainer.
5) Shape the wires so that the service lid fits securely, then close service lid.
Finny fix the wires with
the terminal screws.
lnter-uiit wire (a)
Outdoor unit
Power supply wire(b)
Indoor
unit
Circuit breaker
Earth leakage
(c)
circuit breaker
Power supply (d)
Firmly fix the wires with
the terminal sa-e.vs.
Earth
Capacity Class (kW)
2.5-3.7
I
above 3.7 and upto 7.1
Inter Unit wire (a)
4-core, 1.0 mm
2
or more
I
4-core, 1.5 mm
2
or more
Power supply wire (b)
3-<:ore, 1.5 mm
2
or more
Wire Standard
IS:694 or country specific standard.
Circuit breaker size (c )
15A or more
I
20A or more
Power supply (d)
501-tz 230V-or Country specific
Note: Use 4-core 1.5 mm2 wire if wire is not included wi th the unit.
TableNo.6
� WARNING--------------------------
• Use a stabiliser if required by the voltage supply condition.
• Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
Drain Piping
1) Connect the drain hose, as described right.
2) Remove the air filters and pour some water into the drain pan to check the water
flows smoothly.
3) When drain hose requires extension, obtain an extension hose commercially available.
Be sure to thermally insulate the indoor section of the extension hose.
The drain hose shookl
be inclined downwmd,
No trap is pennitted .
...,
L
_;
not put the end
--w--
the hose in water,
Heat lns�atlon tube
(fiekl supply)
4) When connecting a rigid polyvinyl chloride pipe (nominal diameter
13mm) directly to the drain hose attached to the indoor unit as with
embedded piping work, use any commercially available drain
socket (nominal diameter 13mm) as a joint.
-tj �
JJID)JJ)))If � <_l __ l .... <_I_)
Drain hose supplied
with the Indoor untt
Commercially
availabte drain
socket (nominal
diameter 13mm)
Commercially
available rigk:I
polyvinyl chloride
pipe (nominal
dismatar 13mm)