Daikin F Operation Manual Download Page 31

Outdoor Unit 

Purging Air And Checking Gas Leakage 

� WARNING----------------------

• Do not mix any substance other than the specified refrigerant (R32) into the  refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• To prevent air pollution, a vacuum pump should be used for air purging wherever possible.

• If using additional refrigerant, perform air  purging from the refrigerant pipes and

indoor unit using a vacuum pump, then  charge additional refrigerant.

• Use a hexagonal wrench to operate the  stop valve rod.

• All refrigerant pipe joints should be tightened with a torque wrench at the 

specified tightening torque. 

1) Connect projection side (on which pin is pressed) of charging hose (which comes from gauge 

manifold) to gas stop valve's service port. 

Compound 

Pressure meter 

pressure gauge  / 

Gauge 

manifold 

Low-

Charging 

hoses 

Liquid 

stop 

valve 

Vacuum pump 

Service port 

Gas 

stop 

valve 

2)  Fully open gauge manifold's low-pressure valve (Lo) and completely close its high-pressure  valve (Hi). 

(High-pressure valve subsequently requires no operation.) 

3) Do vacuum pumping and make sure that the compound pressure gauge reads -0.1MPa (-76cmHg) *1. 

4) Close gauge manifold's low-pressure valve (Lo) and stop vacuum pump. 

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does  not swing back.) *2. 

5)  Remove valve cap from liquid stop value and gas stop valve. 

6) Tum the liquid stop valve's rod 90 degrees counterclockwise with a hexagonal wrench to open valve. Close it after 5 seconds, and check for gas leakage. 

Using soapy water, check for gas leakage from indoor unit's flare and outdoor unit's flare and valve rods. 
After the check is complete, wipe all soapy water off. 

7) Disconnect charging hose from gas stop valve's service port, then fully open liquid and gas stop valves.  (Do not attempt to tum valve rod beyond its stop.) 

8) 'Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques. 

*1. Pipe length vs. vacuum pump run time

Pipe length  Up to 15m 

More than 15m

Run time 

Not less than 10 min.  Not less than 15 min. 

•2.  If the compound pressure gauge pointer swings back,

refrigerant may have water content or a loose pipe Joint 

may exists.  Check all pipe joints and retighten nuts as 

needed, then repeat steps2) through4). 

Wiring 

• For inter-unit wires connections, see ( INDOOR UNIT) 

WIRING).

Tenninsl 

block 

• When connecting the connection wires to the terminal block using a single core wire, be sure to perform rurtlng. 

Wire 

retainer 

•  Regarding the interconnecting 

and power cables. 

� WARNING ---

Never use short cables for 

connecting end of conductor to 

each other. 

Drain Work 

Problems with the work may cause heat and fres. 

-

£1 

t

� 

� 

QGood 

XWrong 

Stripping wire at tennlnel block 

• Precaution to be taken for power supply wiring. 

• When using stranded wires, make sure to use a round aimp--sty{e tem1inal for connection to 

the power supply tenninel block.  Place the rwnd  aimp-&tyle tenninels on the wires up to 
the oovered part and oecure in place. 

1) Use the@draln socket for drainage. 

2) When attaching the@draln socket to the bottom frame, make sure the connect the drain hose to the drain socket first. 

3) If the drain port is covered by a mounting base or floor surface, place additional loot bases of at lease! 30mm in height under the outdoor untt's feet. 

4) In cold areas, do not use a drain hose with outdoor unit. (Drain water may freeze. impainng heating performance.) 

Strip wire end to this point. 

QGood 

XWrong 

Roundaimp­

&tyle terminal 

Stranded wire 

m-

°'"'"

""' 

..,.. 

....,mtnune 

8Drull0dlel 

HoM(8Vllllablt�ly.7 .... 

lnnerdlL 16mm) 

10 

Summary of Contents for F

Page 1: ...MTKM60UV16U FTKT35UV16W FTKT50UV16V FTKT60UV16U FTKN35UV16W FTKN50UV16V A D F G MTKL35UV16W A D F G MTKL50UV16V A D F G MTKL50UV16U A D F GTKL60UV16U F GTKL71UV16T A F G MTKM50UV16VA F GTKC48UV16W F G...

Page 2: ...ity and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that produce naked flames i...

Page 3: ...receiver Receives signals from the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed beep Operation stop long beep...

Page 4: ...EEP DISPLAY button 15 DEW CLEAN button NOTE Notes on remote controller S NO 1 2 3 4 5 6 7 9 10 11 12 13 Never expose the remote controller to direct sunlight fJ 1 1 DAIICl fl D 2 REMOTE NO ARC484832 A...

Page 5: ...er Do not get it wet The maximum transmission distance is about 7m To attach the accessory filters Set the accessory filters under the tabs of the filter frame on the indoor streamer unit When attachi...

Page 6: ...ter and the decomposition power of the streamer discharge combine to reduce unpleasant odours and viruses cleaning the air in the room COANDA To start operation 1 Press C i i7 STREAMER When long press...

Page 7: ...LOCK disables all the buttons except when ECONO and POWERFULL button press togetherfor about 5 seconds To set the CHILD LOCK Press t ECONO and togetherfor about 5 seconds wie will be displayed on the...

Page 8: ...ction t ______ 1 Press swiNv and 7 1 and e are displayed on the LCD The flap and louvres move in turn To cancel 3 D airflow press either swiNGJ or ffiwiNG again The flap or louvres will stop moving To...

Page 9: ...B causes the settings to be cancelled and disappears from the LCD ECONO operation functions in COOL and DRY operation POWER CHILL and ECONO operation cannot be used at the same time is displayed on th...

Page 10: ...stop time default 2HR are displayed on the LCD i ol The TIMER lamp lights Display TEMP orange E 2 Press v while C is blinking Each pressing of the button changes tempera ture shift value by 1 C You ca...

Page 11: ...on Set temperature does not display when the unit is in DRY operation or FAN operation Inverter output and set temperature may not display depending on the operation mode that is active The display tu...

Page 12: ...F l hours 35 minutes Cooling operation To cancel DEW CLEAN operation Turn OFF the machine from Remote Controller Wi Fi Control NOTE Note on LED 7 Segment Brightness Control Ld indicates for the bright...

Page 13: ...nt panel shaft on the other side in the same manner After disengaging both front panel shafts pull the front panel toward yourself and remove it 3 Clean the front panel Wipe it with a soft damp cloth...

Page 14: ...ith a vacuum cleaner If the dust does not come off easily wash them with neutral detergent thinned with lukewarm water then let them dry in the shade Be sure to remove the accessory filter optional pa...

Page 15: ...ting procedures Item Titanium apatite deodorizing air purifying filter 1 set Ag ion filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set Micro filter PM2 5 for streamer unit 1 set Micro f...

Page 16: ...onditioner may stop operating after sudden large voltage fluctuations It automatically resumes operation in about 3 minutes Voltage range protection 130V 285V Voltage range protection 130V 265V for F...

Page 17: ...been tripped or the fuse blown operate Is there a power failure OPERATION lamp is off Are batteries set in the remote controller Is the timer setting correct The room does not cool down Is the airflow...

Page 18: ...air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood stop operation and turn off the circ...

Page 19: ...N MOTOR FAULT ES OVERCURRENT INPUT F3 HIGH TEMPERATURE DISCHARGE PIPE CONTROL F6 HIGH PRESSURE CONTROL IN COOLING F8 1 OPERATION HALT DUE TO COMPRESSOR INTERNAL TEMPERATURE ABNORMALITY OUTDOOR HO SENS...

Page 20: ......

Page 21: ...V16U F G MTKM60UV16U FTKT35UV16W FTKT50UV16V FTKT60UV16U FTKN35UV16W FTKN50UV16V A D F G MTKL35UV16W A D F G MTKL50UV16V A D F G MTKL50UV16U A D F GTKL60UV16U F GTKL71UV16T AJF GIMTKM50UV16VA F GTKC48...

Page 22: ...rant gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas le...

Page 23: ...may cause interferencewith the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby The outdoor unit should be positioned in a place where 1 th...

Page 24: ...lllq ral fir rufrlgerant pipe exaiedi 10min length Gas pipe Diameter mm Liquid pipe Diame1ar mm in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur de...

Page 25: ...l the front grille and firmly engage the upper hooks 3 locations 2 Install 3 screws of the front grille 3 Install the air filter and then mount the front panel Opening the service lid The service lid...

Page 26: ...298 X 821 X 235 298 X 885 X 229 298 X 906 X 235 Unit size available on name plate A B C 800 116 5 116 5 821 128 126 5 885 116 5 116 5 906 127 127 5 Table No 4 Applicable Unit Size Type H X W X D I 31...

Page 27: ...on the edge ofthe indoor unit 9 Securethe indoor unit to the A mounting plate with the E indoorunit fixingscrews M4 x12L 10 Caulk the gap between the pipe andthe frontgrille with putty 11 After comple...

Page 28: ...otincluded wi th the unit TableNo 6 WARNING Use a stabiliser if required by the voltage supply condition Do not use tapped wires extension cords or starburst connections as they may cause overheating...

Page 29: ...g W f 3l Heat insulationpipe cover SI This illustration shows the case of the left rear piping Drain hose Sectional view wire J rwrap more than ha heat insu ation tape Heat Insulation pipe cover Insul...

Page 30: ...ening torque tightening torque tightening torque 0 D 9 5mm 32 7 39 9N m 21 6 27 4N m 333 407 kgf cm 220 280 kgf cm Gas side 0 D 12 7mm 49 5 60 3N m 505 615 kgf cm 48 1 59 7N m 10 8 14 N m 0 D 15 9mm 6...

Page 31: ...e all soapy water off 7 Disconnect charginghosefrom gasstop valve s service port thenfullyopenliquidandgasstop valves Do not attempt to tum valve rod beyond its stop 8 Tighten valve caps and service p...

Page 32: ...noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated Draining line is properly installed W...

Page 33: ...0020 Meaning of E waste under E Waste Management Rules 2022 E waste Rules Waste electrical and electronic equipment whole or in part of reject from their manufacturing and repair process which are int...

Reviews: