![Daikin EWYQ080DAYN Operation Manual Download Page 3](http://html1.mh-extra.com/html/daikin/ewyq080dayn/ewyq080dayn_operation-manual_4153268003.webp)
EWYQ080~250DAYN
Packaged air-cooled water chillers
4PW35558-1B
Operation manual
2
Electrical specifications
(1)
General EWYQ
230
250
Dimensions HxWxD
(mm)
2311x2000x4833
Weight
• machine weight
(kg)
3200
3300
• operation weight
(kg)
3239
3342
Connections
• chilled water inlet and outlet
3"
3"
• evaporator drain
1/2" G
1/2" G
Internal water volume
(l)
39
42
Expansion vessel
(only for OPSP, OPTP and OPHP)
• volume
(l)
50
50
• pre-pressure
(bar)
1.5
1.5
Safety valve
water circuit
(bar)
3.0
3.0
Pump
(only for OPSP)
• type
Vertical in-line pump
• model (standard)
TP 65-260/2
TP 65-260/2
Compressor
Type
semi-hermetic scroll compressor
Qty x model
2x SJ240-4 +
2x SJ300-4
4x SJ300-4
Speed
(rpm)
2900
2900
Oil type
FVC68D
FVC68D
Oil charge volume
(l)
2x 6.2 + 2x 6.2
4x 6.2
Condenser
Nominal air flow
(m
3
/min)
1600
1600
No. of motors x output
(W)
8x 600
8x 600
Evaporator
Model
DV58HP
DV58HP
EWYQ
080
100
130
150
Power supply
YN
• Phase
3~
• Frequency
(Hz)
50
• Voltage
(V)
400
• Voltage tolerance
(%)
±10
Unit
• Nominal running current
(A)
60
72
88
113
• Maximum running current (A)
96
120
160
177
• Recommended fuses
according to IEC 269-2
(A)
3x 125 gL
3x 160 gL
3x 200 gL
3x 200 gL
Compressor
• Circuit 1
Circuit 2
(hp)
(hp)
15 + 15
—
20 + 20
—
13 + 13
13 + 13
15 + 15
15 + 15
• Phase
3~
• Frequency
(Hz)
50
• Voltage
(V)
400
• Maximum running current
Circuit 1
Circuit 2
(A)
(A)
39 + 39
—
51 + 51
—
35 + 35
35 + 35
39 + 39
39 + 39
Control and fan motor
• Phase
1~
• Frequency
(Hz)
50
• Voltage
(V)
230 V
• Maximum running current (A)
4x 1.5
4x 1.5
4x 1.6
4x 2.3
Pump
• Power
(kW)
2.2
2.2
3
3
• Maximum running current (A)
4.5
4.5
6.3
6.3
Heater tape
(OP10)
• Supply voltage
(V)
230 V ±10%
• Power
(standard)
(OPSP)
(OPBT)
1x 300 W
2x 300 W
2x 300 W + 150 W
• Optional field heater
maximum 1 kW
• Recommended fuses
(A)
2x 10
EWYQ
180
210
230
250
Power supply
YN
• Phase
3~
• Frequency
(Hz)
50
• Voltage
(V)
400
• Voltage tolerance
(%)
±10
Unit
• Nominal running current
(A)
131
144
162
181
• Maximum running current (A)
209
233
262
290
• Recommended fuses
according to IEC 269-2
(A)
3x 250 gL
3x 250 gL
3x 300 gL
3x 355 gL
Compressor
• Circuit 1
Circuit 2
(hp)
(hp)
20 + 15
20 + 15
20 + 20
20 + 20
25 + 20
25 + 20
25 + 25
25 + 25
• Phase
3~
• Frequency
(Hz)
50
• Voltage
(V)
400
• Maximum running current
Circuit 1
Circuit 2
(A)
(A)
51 + 39
51 + 39
51 + 51
51 + 51
65 + 51
65 + 51
65 + 65
65 + 65
Control and fan motor
• Phase
1~
• Frequency
(Hz)
50
• Voltage
(V)
230 V
• Maximum running current (A)
6x 2.3
6x 2.3
8x 1.6
8x 1.6
Pump
• Power
(kW)
4
4
4
4
• Maximum running current (A)
8.0
8.0
8.0
8.0
Heater tape
(OP10)
• Supply voltage
(V)
230 V ±10%
• Power
(standard)
(OPSP)
(OPBT)
1x 300 W
2x 300 W
2x 300 W + 150 W
• Optional field heater
maximum 1 kW
• Recommended fuses
(A)
2x 10
Summary of Contents for EWYQ080DAYN
Page 30: ...4PW35558 1B Copyright Daikin...