![Daikin EWYQ080DAYN Operation Manual Download Page 12](http://html1.mh-extra.com/html/daikin/ewyq080dayn/ewyq080dayn_operation-manual_4153268012.webp)
Operation manual
11
EWYQ080~250DAYN
Packaged air-cooled water chillers
4PW35558-1B
Adjusting the temperature setpoint
The unit provides definition and selection of four independent
temperature setpoints. Two setpoints are reserved for inlet control,
the other two are reserved for outlet control.
■
COOL. INLSP1
: cooling inlet water temperature, setpoint 1,
■
COOL. INLSP2
: cooling inlet water temperature, setpoint 2.
■
COOL. OUTSP1
: cooling outlet water temperature, setpoint 1,
■
COOL. OUTSP2
: cooling outlet water temperature, setpoint 2.
■
HEAT. INLSP1
: heating inlet water temperature, setpoint 1,
■
HEAT. INLSP2
: heating inlet water temperature, setpoint 2.
■
HEAT. OUTSP1
: heating outlet water temperature, setpoint 1,
■
HEAT. OUTSP2
: heating outlet water temperature, setpoint 2.
The selection between setpoint 1 and 2 is done by a remote dual
setpoint switch (to be installed by the customer). The actual active
setpoint can be consulted in the readout menu.
If the manual control mode is selected (refer to
"Usersettings menu
Å
" on page 12
), none of the above-mentioned setpoints will be
active.
To adjust a setpoint, proceed as follows:
1
Enter the setpoints menu. Refer to the chapter
"How to enter a
menu" on page 8
.
If the user password is disabled for setpoint modifications (refer
to
"Usersettings menu
Å
" on page 12
), the controller will
immediately enter the setpoints menu.
If the user password is enabled for setpoint modifications, enter
the correct code using the
fi
and
Ì
keys (refer to
"User
password menu
Æ
" on page 15
). Press
‡
to confirm the
password and to enter the setpoints menu.
2
Select the setpoint to be adjusted using the
‡
key.
A setpoint is selected when the cursor is blinking behind the
setpoint's name.
The "
>
" sign indicates the actual active temperature setpoint.
3
Press the
fi
and
Ì
keys to adjust the temperature setting.
The default, limit and step values for the cooling temperature
setpoints are:
4
Press
‡
to save the adjusted temperature setpoint.
When the setting has been confirmed, the cursor switches to the
next setpoint.
5
To adjust other setpoints, repeat from step 2.
Resetting the unit
The units are equipped with three kinds of safety devices: unit
safeties, circuit safeties and network safeties.
When a unit or circuit safety occurs, the compressor is shut down.
The safeties menu will indicate which safety is activated. The
UNIT
STATUS
screen of the readout menu will indicate
OFF - SAFETY
ACTIVE
. The red LED inside the
π
key lights up and the buzzer
inside the controller is activated.
When a network safety occurs in a DICN configuration, the slaves not
detected by the network will function as stand alone units.
■
If a slave unit can not be found by the network, the red light
inside the
π
key of the master lights up and the buzzer inside
the control is activated.
■
If the master can not be found by the network, the red light
inside the
π
key of all the slaves light up and the buzzer inside
their controls are activated. All units will work as stand alone
units.
If the unit has been shut down due to a power failure, it will carry out
an autoreset and restart automatically when the electrical power is
restored.
To reset the unit, proceed as follows:
1
Press the
π
key to acknowledge the alarm.
The buzzer is deactivated.
The controller automatically switches to the corresponding
screen of the safeties menu: unit safety or circuit safety or
network safety.
2
Find the cause of shutdown and correct.
Refer to
"Listing activated safeties and checking the unit status"
on page 18
and
"Troubleshooting" on page 20
.
When a safety can be reset, the LED under the
π
key starts
blinking.
3
Press the
π
key to reset the safeties that are no longer active.
If required, enter the
USER PASSWORD
or the
SERVICE
PASSWORD
. (Refer to the installation manual "Setting the
password for safety reset".)
Once all safety devices are deactivated and reset, the LED
under the
π
key goes out. If one of the safeties is still active, the
LED under the
π
key goes on again. In this case, return to
step 2.
4
It will only be necessary to switch the
œ
key on again if a unit
safety occurs.
NOTE
The customer is also allowed to define a setpoint in
function of an analogue input.
NOTE
Refer to "Customization in the service menu" chapter
"Setting of the changeable inputs and outputs" in the
installation manual
COOLING INLET SETP
COOLING OUTLET SETP
default value
12¢
7¢
limit values
(*)
(*)
For glycol treated units with OPZH installed, the lower limit of the cooling
temperature setpoint can be adapted by changing the minimum operating
temperature in the service menu (refer to the installation manual).
7
➞
23¢
5
➞
20¢
step value
0$1¢
0$1¢
HEATING INLET SETP
HEATING OUTLET SETP
default value
40¢
45¢
limit values
(*)
20
➞
45¢
25
➞
50¢
step value
0$1¢
0$1¢
NOTE
When a setpoint on a unit in a DICN system is set, this
setpoint will be transferred to all other units.
NOTE
Also consult
"Defining the floating setpoint settings" on
page 16
.
If the user shuts down the power supply in order to repair a
safety, the safety will automatically be reset after power-up.
NOTE
The history information, i.e. the number of times a unit
safety or a circuit safety occurred and the unit status at
the moment of shutdown, can be checked by means of
the history menu.
Summary of Contents for EWYQ080DAYN
Page 30: ...4PW35558 1B Copyright Daikin...