D-EIMWC003D01-17EN-AR - 17/80
Chilled water control sensor
The water cooled EWWD VZ unit is equipped with a microprocessor. Be careful when working around the unit to
avoid damaging cables and sensors. Check cables before starting the unit. Prevent rubbing of the cables on the
frame or other components. Make sure the cables are securely locked. If the temperature sensor is removed for
maintenance, do not eliminate the conductive paste in the well and replace the sensor correctly. After replacing
the sensor, tighten the lock nut to prevent accidental slipping.
Safety Valve
Each exchanger (evaporator and condenser) is provided with a safety valve installed on an exchange valve that
allows maintenance and periodic checks, without losing a significant amount of refrigerant. Do not leave the
safety valve in the intermediate position.
WARNING
To prevent damage due to R134a gas inhalation, do not release the refrigerant in the air or other indoor places.
The safety valves must be connected externally in accordance with the regulations in the place of installation.
The installer is responsible for connecting the safety valve to the purge pipe and pipe dimensioning. In this
regard, refer to the harmonized standard EN13136 to dimension the drain pipes to be connected to the safety
valves
Open the isolation and/or shut off valves
Before powering the machine and thus starting the compressors, open all valves that were closed at the factory
for shipping.
The valves to be opened are:
1. Valve (optional) installed on the compressor line
2. Oil return pipe shutoff valves (jet pump). These valves are positioned below the evaporator sleeve in the
vicinity of the jet pump.
3. Liquid line valve installed under the condenser.
4. Oil valves installed on the line that feeds the compressor lubrication system. This line comes from the
bottom of the oil separator located inside the condenser.
5. Valve (optional) installed on the compressor pump line.
Electrical connections
The unit must be connected with in the proper section copper cables relative to the plate absorption values and
in accordance with applicable electrical regulations.
Daikin Applied Europe S.p.A. cannot be held liable for improper electrical connections.
Warning
The connections to the terminals must be made with copper terminals and cables.
The electrical connection must be made by qualified personnel.
There is a risk of electric shock
The electrical panel must be connected keeping the correct phase sequence.
Phase imbalance
In a three-phase system, excessive imbalance between the phases is the cause of motor overheating. The
maximum allowed voltage imbalance is 2%, calculated as follows:
imbalance %=
(Vx-Vm) x 100
=
Vm
Vx = phase with greatest imbalance
Summary of Contents for EWWD VZ Series
Page 3: ...D EIMWC003D01 17EN AR 3 80 Description of the labels applied to the unit Single circuit unit...
Page 26: ...D EIMWC003D01 17EN AR 26 80 Fig 6 Typical single circuit cooling circuit...
Page 41: ...EIMWC003D01 17EN AR 41 80 EWWD VZ 055 0055 05 HFC R134a D EIMWC003D01 17EN AR...
Page 43: ...D EIMWC003D01 17EN AR 43 80...
Page 45: ...D EIMWC003D01 17EN AR 45 80 0 6 0 7 3 1 4 1 0 05...
Page 47: ...EIMWC003D01 17EN AR 47 80 0 00 Daikin Applied Europe S p A Daikin Applied Europe S p A...
Page 48: ...EIMWC003D01 17EN AR 48 80 0...
Page 50: ...EIMWC003D01 17EN AR 50 80 Daikin 00 Victaulic 3 4 0 0...
Page 51: ...EIMWC003D01 17EN AR 51 80 5 05 Daikin Applied Europe...
Page 52: ...EIMWC003D01 17EN AR 52 80 EWWD VZ 3 05 00 05 00 60 00 4 05...
Page 53: ...EIMWC003D01 17EN AR 53 80 TWLE TWLE 0 0 51 3 000 4 000 51...
Page 55: ...EIMWC003D01 17EN AR 55 80 4 0 6 6 Daikin Applied Europe SpA 3 4 05 05 5 05 3 0 0 0 0...
Page 56: ...EIMWC003D01 17EN AR 56 80 05 4 0 0 3 4 0 0 0 3 0 4...
Page 58: ...EIMWC003D01 17EN AR 58 80 05 EWWD VZ 035 Q0 Daikin Applied Europe 0 35 EWWD VZ...
Page 59: ...EIMWC003D01 17EN AR 59 80 Daikin Daikin Daikin VVR...
Page 60: ...EIMWC003D01 17EN AR 60 80 supercap EWWD VZ 145 04 4155 15 VVR VVR 3...
Page 61: ...EIMWC003D01 17EN AR 61 80 055 0 0 Daikin Mobil EAL Artic 220H Daikin EWWD VZ Venturi 3 4...
Page 62: ...EIMWC003D01 17EN AR 62 80 0 PID niaiaD TLLnD WE TLLn WE HP...
Page 63: ...EIMWC003D01 17EN AR 63 80 IGBT EN 60204 1 5 PED d e f...
Page 65: ...EIMWC003D01 17EN AR 65 80 6...
Page 68: ...EIMWC003D01 17EN AR 68 80 4 0 6 05 3 4 1 1 05 00 0 5 5 00 03 04...
Page 69: ...EIMWC003D01 17EN AR 69 80 Daikin Applied Europe Spa 055 6 7 1 1 05...
Page 70: ...EIMWC003D01 17EN AR 70 80 Daikin Applied Europe Daikin Daikin...
Page 72: ...EIMWC003D01 17EN AR 72 80 6 O X X X X X X X 7 X X 1 X O X niaiaD...
Page 73: ...EIMWC003D01 17EN AR 73 80 00 Daikin...
Page 74: ...D EIMWC003D01 17EN AR 74 80 4102 86 CE DCP...
Page 75: ...EIMWC003D01 17EN AR 75 80 R134a GWP 0 0435 0 GWP...
Page 76: ...EIMWC003D01 17EN AR 76 80 0 0 0 3 0 0 3 x 0555 a b c d e f g h m n GWP p 2 x 0555...
Page 77: ...EIMWC003D01 17EN AR 77 80...
Page 78: ...EIMWC003D01 17EN AR 78 80 05...