28
CG-SVX04C-E4
Maintenance
Maintenance Instructions
The following maintenance
instructions are part of maintenance
operations required for this
equipment. A qualified technician is
needed for regular maintenance as
part of a regular maintenance contract.
Carry out all operations as required
by schedule. This will ensure long
unit service life and reduce the
possibility of serious and costly
breakdown.
Keep service records up to date,
showing monthly information on
unit operations. These records can
be of great help to maintenance
personnel diagnostics.
Similarly, if machine operator keeps
a log of changes in unit operating
conditions, problems can be
identified and solutions found before
more serious problems arise.
Inspection visit after the first 500
hours of operation from unit start up
- Carry out oil analysis
- Carry out leak test.
- Inspect contacts and tighten
terminals.
- Record operating pressures,
temperatures, amperages and
voltage.
- Check operation of
machines/compare conditions of
operation against original
commissioning data.
- Fill out inspection visit log sheet
and review with the operator
- Check and clean the strainer
Monthly preventive visit
- Carry out leak test.
- Oil test of acidity
- Check Ethylene glycol % in the
chilled water circuit if glycol
presence is required
- Inspect contacts and tighten
terminals.
- Record operating pressures,
temperatures, amperages and
voltage.
- Check operation of
machines/compare conditions of
operation against original
commissioning data.
- Fill out visit log sheet and review
with the operator.
- Check and clean the strainer.
Annual preventive visit
- Check water flows and interlocks.
- Check expansion tank pressure.
- Check glycol % in the chilled water
circuit if glycol presence is
required
- Check operational set points and
performance.
- Calibrate controls and pressure
transducer.
- Check operation of all safety
devices.
- Inspect contacts and tighten
terminals.
- Megger the motor compressor
windings.
- Record operating pressures,
temperatures, amperages and
voltage.
- Carry out leak test.
- Check configuration of unit control
module.
- Carry out oil analysis
- Change the oil as required based
upon results of the oil analysis
- Check operation of
machines/compare conditions of
operation against original
commissioning data.
- Fill out the annual start up visit log
sheet and review with the operator.
- Check and clean the strainer.
Caution:
- Please refer to specific Daikin
documentation on oil, available
from your nearest Daikin office.
Oils recommended by Daikin have
been exhaustively tested in Daikin
laboratories to the specific
requirement of Daikin chiller and
hence the user's requirements.
Any use of oils not meeting
specifications recommended by
Daikin is the responsibility of the
user only, who thereby is liable to
warranty loss.
- Oil analysis and oil test acidity
must be carried out by a qualified
technician. Poor interpretation of
results may cause unit operating
problems. Also, oil analysis must
follow the correct procedures, to
avoid accidental injury to
maintenance personnel.
- If the condensers are dirty, clean
them with a soft brush and water.
If the coils are too dirty, consult a
cleaning professional. Never use
high pressure water to clean
condenser coils.
- Contact Daikin Service for
information on maintenance
contracts.
Warning:
- Switch off unit main power supply
before to any intervention. Failure
to follow this safety instruction can
lead to accident death of the
maintenance personnel and may
also destroy equipment.
- Never use steam or hot water
above 60°C to clean condenser
coils. The resulting increasing
pressure could cause refrigerant
lost through the safety valve.
Pump maintenance
Pumps motor bearings and
mechanical seals have a designed
life expectancy of 20000-25000 hours
of operation. For critical applications
it might be necessary to change the
components as a preventive
measure.
Summary of Contents for EWAP/EWYP 060-260
Page 212: ...1 2 3 Daikin EWAP EWYP 212 CG SVX04C EL...
Page 213: ...CG SVX04C EL 213 Daikin 3 7 Daikin...
Page 214: ...214 CG SVX04C EL Daikin...
Page 215: ...CG SVX04C EL 215 212 216 225 225 225 225 228 230 230 230 232 E 232 237 237 237 238 239 240...
Page 225: ...Daikin 5 I MAX 4 060 6 075 260 8 1 2 CG SVX04C EL 225...
Page 230: ...230 CG SVX04C EL Daikin Daikin AISI 316 1 4401 Daikin Daikin J 1 2 1 2 C 8 1 2 3 1 C 2 C LP...
Page 237: ...CG SVX04C EL 237 TRACER CH532 CH532 CH532 CH532 off Daikin CH532 off Daikin megger 8 HP LP...
Page 238: ...238 CG SVX04C EL 500 megger Daikin Daikin Daikin Daikin Daikin Daikin Daikin 60 C 20000 25000...
Page 239: ...CG SVX04C EL 239 Daikin...
Page 240: ...240 CG SVX04C EL Daikin A H B H H...
Page 241: ...CG SVX04C EL 241 E H K Daikin...
Page 332: ...1 2 3 Daikin EWAP EWYP 332 CG SVX04C RU...
Page 333: ...CG SVX04C RU 333 Daikin 3 7 Daikin...
Page 334: ...334 CG SVX04C RU...
Page 335: ...CG SVX04C RU 335 332 336 345 345 345 345 348 350 350 350 352 352 357 357 357 358 359 360...
Page 345: ...Daikin 5 I MAX 4 060 6 075 260 8 1 1 2 2 CG SVX04C RU 345...
Page 350: ...350 CG SVX04C RU Daikin Daikin AISI 316 1 4401 Daikin Daikin 1 2 1 2 C 8 8 1 2 3 1 2 C...
Page 352: ...352 CG SVX04C RU 500 2 TRACER 532 500 500 CH532 15 Daikin 2 9 11 50 Daikin 11 1 11 1 1 2...
Page 357: ...CG SVX04C RU 357 TRACER CH532 CH532 CH532 CH532 Clock Daikin CH532 Daikin 8 HP LP...
Page 358: ...358 CG SVX04C RU 5 50 00 0 Daikin Daikin Daikin Daikin Daikin 60 C 20000 25000...
Page 359: ...CG SVX04C RU 359 Daikin...
Page 360: ...360 CG SVX04C RU Daikin A A B B C C a b a b a b...
Page 361: ...CG SVX04C RU 361 D D E E F F G G H H I I J J K K a b a b Daikin a b a b...