background image

9 Commissioning

Installation manual

35

EWAA004~008D2 + EWYA004~008D2
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688014-1A – 2022.05

9

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during commissioning and
hand-over to the user.

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

NOTICE

The unit contains an automatic air purge valve. Make sure
it  is  open.  All  automatic  air  purge  valves  in  the  system  (in
the unit, and in the field piping – if any) must remain open
after commissioning.

INFORMATION

Protective  functions  –  "Installer-on-site  mode"

.  The

software  is  equipped  with  protective  functions,  such  as
room antifrost. The unit automatically runs these functions
when necessary.

During  installation  or  service  this  behaviour  is  undesired.
Therefore, the protective functions can be disabled:

At  first  power-on:

  The  protective  functions  are

disabled  by  default.  After  12  hours  they  will  be
automatically enabled.

Afterwards:

  An  installer  can  manually  disable  the

protective  functions  by  setting  [9.G]: 

Disable

protections

=

Yes

.  After  his  work  is  done,  he  can

enable  the  protective  functions  by  setting  [9.G]:

Disable protections

=

No

.

9.1

Checklist before commissioning

1

After the installation of the unit, check the items listed below.

2

Close the unit.

3

Power up the unit.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

outdoor unit

 is properly mounted.

The  switchbox  is  rotated  back  and  correctly  engaged  in
the switchbox holder.

Field wiring

Be  sure  that  the  field  wiring  has  been  carried  out
according  to  the  instructions  described  in  the  chapter

"6  Electrical  installation"

  [

4

  15],  according  to  the  wiring

diagrams and according to the applicable legislation.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the outdoor unit.

Only for models with integrated backup heater (F1B: field
supply), or if the external backup heater kit (F1B: factory-
mounted in the backup heater kit) is installed:

Backup heater circuit breaker

 F1B is turned ON.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There are no 

water leaks

 inside the outdoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

automatic air purge valve

 is open.

The 

pressure  relief  valve

  purges  water  when  opened.

Clean water MUST come out.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions. See "To check the water volume and flow rate"
in 

"5.1 Preparing water piping"

 [

4

 12].

9.2

Checklist during commissioning

The 

minimum  flow  rate

  is  guaranteed  in  all  conditions.

See  "To  check  the  water  volume  and  flow  rate"  in

"5.1 Preparing water piping"

 [

4

 12].

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

9.2.1

To check the minimum flow rate

1

Check the hydraulic configuration to find out which
space heating loops can be closed by mechanical,
electronic, or other valves.

2

Close all space heating loops that can be closed.

3

Start the pump test run (see 

"9.2.4 To perform an

actuator test run"

 [

4

 36]).

4

Read out the flow rate

(a)

 and modify the bypass valve

setting to reach the minimum required flow rate + 2 l/
min.

(a)

During pump test run, the unit can operate below the minimum
required flow rate.

If operation is…

Then the minimum required

flow rate is…

Cooling

10 l/min

Heating

6 l/min

BUH operation

12 l/min

Heating defrost

12 l/min

9.2.2

To perform an air purge

Conditions: 

Make  sure  all  operation  is  disabled.  Go  to  [C]:

Operation

 and turn off 

Space heating/cooling

 operation.

Summary of Contents for EWAA004D2V3P

Page 1: ...ers and packaged air to water heat pumps English Installation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAA004D2V3P EWAA006D2V3P EWAA008D2V3P EWYA004D2V3P EWYA006...

Page 2: ...6 17 18 19 v platn m zn n kako je izmijenjeno amandmanima s m dos t saik rendelkez seit z p niejszymi zmianami cu amendamentele respective kakor je bilo spremenjeno 20 21 22 23 24 25 koos muudatustega...

Page 3: ...mp tila TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistu...

Page 4: ...gulations 2016 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 as set out in A and...

Page 5: ...mum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate K L M TSmin TSmax PS N P 46 30 68 R32 46 bar C...

Page 6: ...figuration wizard Language 28 8 2 2 Configuration wizard Time and date 28 8 2 3 Configuration wizard System 28 8 2 4 Configuration wizard Backup heater 30 8 2 5 Configuration wizard Main zone 30 8 2 6...

Page 7: ...open flames an operating gas appliance or an operating electric heater WARNING Make sure installation servicing maintenance and repair comply with instructions from Daikin and with applicable legisla...

Page 8: ...dampers j Cable tie k Bolts nuts washers and spring washers 2 After opening the unit see 4 3 1 To open the outdoor unit 411 remove the accessory inside the unit m m Shutoff valve 4 Unit installation 4...

Page 9: ...sary install a snow cover or shed and a pedestal 4 2 Mounting the outdoor unit 4 2 1 To provide the installation structure This topic shows different installation structures For all use 4 sets of M8 o...

Page 10: ...r can be evacuated properly INFORMATION If necessary you can use a drain pan field supply to prevent drain water from dripping NOTICE If the drain holes of the outdoor unit are blocked up provide spac...

Page 11: ...witch box During the installation you will need access to the inside of the outdoor unit To have easier front access rotate the switch box out of the unit as follows Prerequisite The front plate has b...

Page 12: ...ting defrost operation and the external backup heater kit is Connected 15 l NOT connected and The return flow temperature is 15 C 20 l The return flow temperature is 15 C 50 l NOTICE Never use less wa...

Page 13: ...the water circuit To fill the water circuit use a field supply filling kit Make sure you comply with the applicable legislation NOTICE The unit contains an automatic air purge valve Make sure it is op...

Page 14: ...ainst freezing the glycol will prevent the liquid inside the piping from freezing NOTICE The required concentration might differ depending on the type of glycol ALWAYS compare the requirements from th...

Page 15: ...ain power supply 416 User interface See 6 3 3 To connect the user interface 418 Shut off valve See 6 3 4 To connect the shut off valve 419 Electricity meters See 6 3 5 To connect the electricity meter...

Page 16: ...the outdoor unit 1 Open the service cover See 4 3 1 To open the outdoor unit 411 If necessary rotate the switch box See 4 3 2 To rotate the switch box 411 2 Insert the cables at the back of the unit...

Page 17: ...power supply 1 Connect the preferential kWh rate power supply N N L N N N PE N Q1DI N L M 1 X N N N N N N M 1 X N M 1 X N N N N N N N N 1N N 1N 50 Hz 220 240 V AC N N X1M N L N 1N 180 2 If necessary...

Page 18: ...erface cable to the outdoor unit Fix the cable with cable ties to the cable tie mountings X1B a X5M 11 X5M 12 X5M 16 X5M 15 1 2 3 4 P1P2 PSU a User interface Required for operation Delivered with the...

Page 19: ...as follows 1 Remove the WLAN cartridge and USB memory stick if any 2 Push the rear plate on each of the 4 spots where the snap fits are located 6 3 4 To connect the shut off valve INFORMATION Shut of...

Page 20: ...utput 1 Open the service cover See 4 3 1 To open the outdoor unit 411 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires...

Page 21: ...alent 1 Open the service cover See 4 3 1 To open the outdoor unit 411 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below A4P X2 A4P...

Page 22: ...his topic describes 2 possible ways to connect the outdoor unit to a Smart Grid In case of low voltage Smart Grid contacts In case of high voltage Smart Grid contacts This requires the installation of...

Page 23: ...oltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 K1A Relay for Smart Grid contact 1 K2A Relay for Smart Grid contact 2 a b Coil sides of relays c d Contact sides of relays e Jumper fact...

Page 24: ...egislation Depending on the configuration wiring on X14M and settings in 9 3 Backup heater the backup heater capacity can vary Make sure that the power supply is in accordance with the backup heater c...

Page 25: ...3 52 9 52 9 K2M 5 52 9 52 9 K2M 3 K2M 5 52 9 52 9 52 9 52 9 K1M 5 K2M 1 132 3 Example measure resistance between K1M 1 and K5M 13 K1M K2M K2M 1 3 5 13 2 4 6 14 K5M 1 3 5 13 2 4 6 14 1 3 5 13 2 4 6 14...

Page 26: ...temperature B Dry bulb temperature Relative humidity 40 Relative humidity 60 Relative humidity 80 Example Given are an ambient temperature of 25 C and a relative humidity of 40 If the leaving water e...

Page 27: ...Configuration wizard When you turn ON the user interface for the first time via the unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the syste...

Page 28: ...show a popup screen and request to restart the system When confirmed the system will restart and recent changes will be applied 8 2 Configuration wizard After first power ON of the system the user in...

Page 29: ...ne a a Main LWT zone Code Description 4 4 7 02 1 Dual zone Two leaving water temperature zones The main leaving water temperature zone consists of the higher load heat emitters and a mixing station to...

Page 30: ...qual to 2 6 03 6 04 Capacity step 1 Code Description 9 3 4 6 03 The capacity of the first step of the backup heater at nominal voltage Additional capacity step 2 Code Description 9 3 5 6 04 The capaci...

Page 31: ...3 7 2 0D 0 Underfloor heating 1 Fancoil unit 2 Radiator Control The control type is displayed here but cannot be adjusted It is determined by the control type of the main zone For more info about the...

Page 32: ...eratures too cold raise the slope so that leaving water temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the tempera...

Page 33: ...f a zone You feel Fine tune with slope and offset At regular outdoor temperatures At cold outdoor temperatures Slope Offset OK Cold OK Hot Cold OK Cold Cold Cold Hot Hot OK Hot Cold Hot Hot To fine tu...

Page 34: ...s 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater BBR16 activation BBR16 power limit 9 Installer settings Configuration wizard Backup...

Page 35: ...he wiring diagrams and according to the applicable legislation The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed acco...

Page 36: ...ctuator test run starts It stops automatically when ready 30 min To stop the test run manually 1 In the menu go to Stop test run 2 Select OK to confirm Possible actuator test runs Backup heater 1 test...

Page 37: ...e printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to...

Page 38: ...efrigerant pressure sensor S1PH High pressure switch a1 Water IN screw connection male 1 a2 Water OUT screw connection male 1 Thermistors hydro module b Drain valve water circuit R1T Outlet water heat...

Page 39: ...lectronic expansion valve Y1S Solenoid valve 4 way valve Z C Noise filter ferrite core Z F Noise filter NOTES 1 When operating do not short circuit protection device s S1PH and Q1L 2 Colours BLK black...

Page 40: ...e input 2 S4S Smart Grid feed in S6S S9S Digital power limitation inputs S10S S11S Low voltage Smart Grid contact SS1 A4P Selector switch TR1 Power supply transformer X4M Terminal strip booster heater...

Page 41: ...act 16 V DC detection voltage supplied by PCB Smartgrid contacts Smart Grid contacts Smartgrid PV power pulse meter Smart Grid photovoltaic power pulse meter SWB Switch box 7 External On OFF thermosta...

Page 42: ...nal 2 core 2 core 2 core 2 core 3 core R2T External sensor oor or ambient Only for KRTETS WLAN cartridge Optional part for EWA EWYA signal 2 core 3m included A14P P1 P2 user interface Only for remote...

Page 43: ......

Page 44: ...4P688014 1A 2022 05 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: