8 Configuration

Installation manual

28

EWAA004~008D2 + EWYA004~008D2

Packaged air-cooled water chillers

and packaged air to water heat pumps

4P688014-1A – 2022.05

5678

Installer

Advanced user pin code

The 

Advanced user

 pin code is 

1234

. Additional menu items for the

user are now visible.

1234

Advanced user

User pin code

The 

User

 pin code is 

0000

.

0000

User

To access the installer settings

1

Set the user permission level to 

Installer

.

2

Go to [9]: 

Installer settings

.

To modify an overview setting

Example: 

Modify [1‑01] from 15 to 20.

Most  settings  can  be  configured  via  the  menu  structure.  If  for  any
reason it is required to change a setting using the overview settings,
then the overview settings can be accessed as follows:

1

Set the user permission level to 

Installer

. See 

"To

change the user permission level"

 [

4

 27].

2

Go to [9.I]: 

Installer settings

 > 

Overview

field settings

.

3

Turn the left dial to select the first part of the setting
and confirm by pressing the dial.

00
01
02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

0

1

2
3

4

Turn the left dial to select the second part of the
setting

00
01

15

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

5

Turn the right dial to modify the value from 15 to 20.

00
01

20

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

6

Press the left dial to confirm the new setting.

7

Press the center button to go back to the home
screen.

INFORMATION

When  you  change  the  overview  settings  and  you  go  back
to  the  home  screen,  the  user  interface  will  show  a  popup
screen and request to restart the system.

When  confirmed,  the  system  will  restart  and  recent
changes will be applied.

8.2

Configuration wizard

After  first  power  ON  of  the  system,  the  user  interface  starts  a
configuration wizard. Use this wizard to set the most important initial
settings  for  the  unit  to  run  properly.  If  required,  you  can  afterwards
configure  more  settings.  You  can  change  all  these  settings  via  the
menu structure.

8.2.1

Configuration wizard: Language

#

Code

Description

[7.1]

N/A

Language

8.2.2

Configuration wizard: Time and date

#

Code

Description

[7.2]

N/A

Set the local time and date

INFORMATION

By  default,  daylight  savings  time  is  enabled  and  clock
format  is  set  to  24  hours.  These  settings  can  be  changed
during  initial  configuration  or  via  the  menu  structure  [7.2]:

User settings

 > 

Time/date

.

8.2.3

Configuration wizard: System

Backup heater type

#

Code

Description

[9.3.1]

[E‑03]

▪ 0: 

No heater

▪ 1: 

External heater

Emergency

When  the  heat  pump  fails  to  operate,  the  optional  external  backup
heater kit can serve as an emergency heater. It then takes over the
heat load either automatically or by manual interaction.

▪ When 

Emergency

 is set to 

Automatic

 (or 

auto  SH  normal/DHW

off

)

(1)

  and  a  heat  pump  failure  occurs,  the  backup  heater

automatically takes over the heat load.

▪ When 

Emergency

  is  set  to 

Manual

  and  a  heat  pump  failure

occurs, the space heating stops.

To  manually  recover  it  via  the  user  interface,  go  to  the

Malfunctioning

  main  menu  screen  and  confirm  whether  the

backup heater can take over the heat load or not.

(1)

auto SH normal/DHW off

 has the same effect as 

Automatic

, but should NOT be used because there is no domestic hot water.

Summary of Contents for EWAA004D2V3P

Page 1: ...ers and packaged air to water heat pumps English Installation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAA004D2V3P EWAA006D2V3P EWAA008D2V3P EWYA004D2V3P EWYA006...

Page 2: ...6 17 18 19 v platn m zn n kako je izmijenjeno amandmanima s m dos t saik rendelkez seit z p niejszymi zmianami cu amendamentele respective kakor je bilo spremenjeno 20 21 22 23 24 25 koos muudatustega...

Page 3: ...mp tila TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistu...

Page 4: ...gulations 2016 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 as set out in A and...

Page 5: ...mum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate K L M TSmin TSmax PS N P 46 30 68 R32 46 bar C...

Page 6: ...figuration wizard Language 28 8 2 2 Configuration wizard Time and date 28 8 2 3 Configuration wizard System 28 8 2 4 Configuration wizard Backup heater 30 8 2 5 Configuration wizard Main zone 30 8 2 6...

Page 7: ...open flames an operating gas appliance or an operating electric heater WARNING Make sure installation servicing maintenance and repair comply with instructions from Daikin and with applicable legisla...

Page 8: ...dampers j Cable tie k Bolts nuts washers and spring washers 2 After opening the unit see 4 3 1 To open the outdoor unit 411 remove the accessory inside the unit m m Shutoff valve 4 Unit installation 4...

Page 9: ...sary install a snow cover or shed and a pedestal 4 2 Mounting the outdoor unit 4 2 1 To provide the installation structure This topic shows different installation structures For all use 4 sets of M8 o...

Page 10: ...r can be evacuated properly INFORMATION If necessary you can use a drain pan field supply to prevent drain water from dripping NOTICE If the drain holes of the outdoor unit are blocked up provide spac...

Page 11: ...witch box During the installation you will need access to the inside of the outdoor unit To have easier front access rotate the switch box out of the unit as follows Prerequisite The front plate has b...

Page 12: ...ting defrost operation and the external backup heater kit is Connected 15 l NOT connected and The return flow temperature is 15 C 20 l The return flow temperature is 15 C 50 l NOTICE Never use less wa...

Page 13: ...the water circuit To fill the water circuit use a field supply filling kit Make sure you comply with the applicable legislation NOTICE The unit contains an automatic air purge valve Make sure it is op...

Page 14: ...ainst freezing the glycol will prevent the liquid inside the piping from freezing NOTICE The required concentration might differ depending on the type of glycol ALWAYS compare the requirements from th...

Page 15: ...ain power supply 416 User interface See 6 3 3 To connect the user interface 418 Shut off valve See 6 3 4 To connect the shut off valve 419 Electricity meters See 6 3 5 To connect the electricity meter...

Page 16: ...the outdoor unit 1 Open the service cover See 4 3 1 To open the outdoor unit 411 If necessary rotate the switch box See 4 3 2 To rotate the switch box 411 2 Insert the cables at the back of the unit...

Page 17: ...power supply 1 Connect the preferential kWh rate power supply N N L N N N PE N Q1DI N L M 1 X N N N N N N M 1 X N M 1 X N N N N N N N N 1N N 1N 50 Hz 220 240 V AC N N X1M N L N 1N 180 2 If necessary...

Page 18: ...erface cable to the outdoor unit Fix the cable with cable ties to the cable tie mountings X1B a X5M 11 X5M 12 X5M 16 X5M 15 1 2 3 4 P1P2 PSU a User interface Required for operation Delivered with the...

Page 19: ...as follows 1 Remove the WLAN cartridge and USB memory stick if any 2 Push the rear plate on each of the 4 spots where the snap fits are located 6 3 4 To connect the shut off valve INFORMATION Shut of...

Page 20: ...utput 1 Open the service cover See 4 3 1 To open the outdoor unit 411 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires...

Page 21: ...alent 1 Open the service cover See 4 3 1 To open the outdoor unit 411 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below A4P X2 A4P...

Page 22: ...his topic describes 2 possible ways to connect the outdoor unit to a Smart Grid In case of low voltage Smart Grid contacts In case of high voltage Smart Grid contacts This requires the installation of...

Page 23: ...oltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 K1A Relay for Smart Grid contact 1 K2A Relay for Smart Grid contact 2 a b Coil sides of relays c d Contact sides of relays e Jumper fact...

Page 24: ...egislation Depending on the configuration wiring on X14M and settings in 9 3 Backup heater the backup heater capacity can vary Make sure that the power supply is in accordance with the backup heater c...

Page 25: ...3 52 9 52 9 K2M 5 52 9 52 9 K2M 3 K2M 5 52 9 52 9 52 9 52 9 K1M 5 K2M 1 132 3 Example measure resistance between K1M 1 and K5M 13 K1M K2M K2M 1 3 5 13 2 4 6 14 K5M 1 3 5 13 2 4 6 14 1 3 5 13 2 4 6 14...

Page 26: ...temperature B Dry bulb temperature Relative humidity 40 Relative humidity 60 Relative humidity 80 Example Given are an ambient temperature of 25 C and a relative humidity of 40 If the leaving water e...

Page 27: ...Configuration wizard When you turn ON the user interface for the first time via the unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the syste...

Page 28: ...show a popup screen and request to restart the system When confirmed the system will restart and recent changes will be applied 8 2 Configuration wizard After first power ON of the system the user in...

Page 29: ...ne a a Main LWT zone Code Description 4 4 7 02 1 Dual zone Two leaving water temperature zones The main leaving water temperature zone consists of the higher load heat emitters and a mixing station to...

Page 30: ...qual to 2 6 03 6 04 Capacity step 1 Code Description 9 3 4 6 03 The capacity of the first step of the backup heater at nominal voltage Additional capacity step 2 Code Description 9 3 5 6 04 The capaci...

Page 31: ...3 7 2 0D 0 Underfloor heating 1 Fancoil unit 2 Radiator Control The control type is displayed here but cannot be adjusted It is determined by the control type of the main zone For more info about the...

Page 32: ...eratures too cold raise the slope so that leaving water temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the tempera...

Page 33: ...f a zone You feel Fine tune with slope and offset At regular outdoor temperatures At cold outdoor temperatures Slope Offset OK Cold OK Hot Cold OK Cold Cold Cold Hot Hot OK Hot Cold Hot Hot To fine tu...

Page 34: ...s 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater BBR16 activation BBR16 power limit 9 Installer settings Configuration wizard Backup...

Page 35: ...he wiring diagrams and according to the applicable legislation The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed acco...

Page 36: ...ctuator test run starts It stops automatically when ready 30 min To stop the test run manually 1 In the menu go to Stop test run 2 Select OK to confirm Possible actuator test runs Backup heater 1 test...

Page 37: ...e printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to...

Page 38: ...efrigerant pressure sensor S1PH High pressure switch a1 Water IN screw connection male 1 a2 Water OUT screw connection male 1 Thermistors hydro module b Drain valve water circuit R1T Outlet water heat...

Page 39: ...lectronic expansion valve Y1S Solenoid valve 4 way valve Z C Noise filter ferrite core Z F Noise filter NOTES 1 When operating do not short circuit protection device s S1PH and Q1L 2 Colours BLK black...

Page 40: ...e input 2 S4S Smart Grid feed in S6S S9S Digital power limitation inputs S10S S11S Low voltage Smart Grid contact SS1 A4P Selector switch TR1 Power supply transformer X4M Terminal strip booster heater...

Page 41: ...act 16 V DC detection voltage supplied by PCB Smartgrid contacts Smart Grid contacts Smartgrid PV power pulse meter Smart Grid photovoltaic power pulse meter SWB Switch box 7 External On OFF thermosta...

Page 42: ...nal 2 core 2 core 2 core 2 core 3 core R2T External sensor oor or ambient Only for KRTETS WLAN cartridge Optional part for EWA EWYA signal 2 core 3m included A14P P1 P2 user interface Only for remote...

Page 43: ......

Page 44: ...4P688014 1A 2022 05 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: