5 Piping installation

Installation manual

9

ETVH/23E
Daikin Altherma 3 H HT F
4P644728-1B – 2022.03

5.2

Connecting water piping

5.2.1

To connect the water piping

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  field
piping  and  make  sure  the  piping  is  aligned  properly.
Deformation of the piping can cause malfunctioning of the
unit.

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.

1

Connect  the  O-rings  and  shut-off  valves  to  the  outdoor  unit
water connection pipes of the indoor unit.

2

Connect the outdoor unit field piping to the shut-off valves.

3

Connect  the  O-rings  and  shut-off  valves  to  the  space  heating/
cooling water pipes of the indoor unit.

4

Connect the space heating/cooling field piping of both zones to
the shut-off valves.

5

Connect  the  domestic  hot  water  in  and  out  pipes  to  the  indoor
unit.

b1

b2

a1

a2

c2

c1

a1

Space heating/cooling – Water IN (screw connection, 1")

a2

Space heating/cooling – Water OUT (screw connection,
1")

b1

DHW – Cold water IN (screw connection, 3/4")

b2

DHW – Hot water OUT (screw connection, 3/4")

c1

Water IN from outdoor unit (screw connection, 1")

c2

Water OUT to outdoor unit (screw connection, 1")

NOTICE

It  is  recommended  to  install  shut-off  valves  to  domestic
cold  water  in  and  domestic  hot  water  out  connections.
These shut-off valves are field supplied.

NOTICE

Overpressure bypass valve

 (delivered as accessory). We

recommend to install the overpressure bypass valve in the
space heating water circuit.

▪ Mind  the  minimum  water  volume  when  choosing  the

installation  location  of  the  overpressure  bypass  valve
(at  the  indoor  unit,  or  at  the  collector).  See 

"5.1.1  To

check the water volume and flow rate"

 [

4

 8].

▪ Mind  the  minimum  flow  rate  when  adjusting  the

overpressure  bypass  valve  setting.  See 

"5.1.1  To

check  the  water  volume  and  flow  rate"

  [

4

  8]  and

"8.2.1 To check the minimum flow rate"

 [

4

 30].

NOTICE

Install air purge valves at all local high points.

NOTICE

A  pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  (=1  MPa)  must  be  installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.

5.2.2

To connect the recirculation piping

Prerequisite: 

Only required if you need recirculation in your system.

1

Remove  the  top  panel  from  the  unit,  see 

"4.2.1  To  open  the

indoor unit"

 [

4

 5].

2

Cut out the rubber grommet on top of the unit, and remove the
stop. The recirculation connector is placed below the hole.

3

Route the recirculation piping through the grommet and connect
it to the recirculation connector.

4

Reattach the top panel.

5.2.3

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

NOTICE

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

All  automatic  air  purge  valves  MUST  remain  open  after
commissioning.

Summary of Contents for ETVX16E9W7

Page 1: ...therma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18E 6V ETVH16S23E 6V ETVH16S18E 9W ETVH16S23E 9W ETVX16S18E 6V ETVX16S23E 6V ETVX16S18E 9W ETVX16S23E 9W A B C Z 1 2 3 9 htt...

Page 2: ...m rnicemi nebo p edpisy za p edpokladu e tyto v robky jsou pou v ny v souladu s na imi pokyny u skladu sa sljede om direktivom ma ili odredbom a uz uvjet da se proizvodi koriste sukladno na im uputama...

Page 3: ...te 22 7 2 3 Configuration wizard System 22 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 24 7 2 6 Configuration wizard Additional zone 25 7 2 7 Configuration wizard...

Page 4: ...the instructions from this manual See 5 Piping installation 48 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is...

Page 5: ...isible 4 Unit installation 4 1 Preparing the installation site 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following am...

Page 6: ...lowing cases 4 2 2 To lower the switch box on the indoor unit 46 4 3 2 To connect the drain hose to the drain 47 When you need access to the high voltage switch box 2 T25 5 If you need access to the h...

Page 7: ...hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximum...

Page 8: ...er volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When circulati...

Page 9: ...e field supplied NOTICE Overpressure bypass valve delivered as accessory We recommend to install the overpressure bypass valve in the space heating water circuit Mind the minimum water volume when cho...

Page 10: ...n is then lower than assumed As a result the hydraulic components might freeze up after all Take preventive actions to ensure a minimal exposure of the glycol to air Types of glycol The types of glyco...

Page 11: ...TICE The distance between the high voltage and low voltage cables should be at least 50 mm 6 1 About electrical compliance Only for the backup heater of the indoor unit See 6 3 2 To connect the backup...

Page 12: ...1 6 Room sensor offset Item Description WLAN module See Installation manual of the WLAN module Addendum book for optional equipment Installer reference guide Use the cable delivered with the WLAN modu...

Page 13: ...9 S1S N L 5 6 1N 50 Hz 230 V AC 6 3 A 1 2 3 a b c B A B 5 6 1 2 3 X2M X1A X11YA X11YB X11Y X5M 9 10 X1M a b c a Interconnection cable main power supply b Normal kWh rate power supply c Preferential po...

Page 14: ...ng the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or eq...

Page 15: ...valve and a NO normally open valve A M2S B A B 21 28 X2M B 21 29 X2M NO NC 3 Fix the cable with cable ties to the cable tie mountings 6 3 4 To connect the electricity meters Wires 2 per meter 0 75 mm...

Page 16: ...A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of EKRP1HBAA is required b Prewi...

Page 17: ...1 Open the following see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate t...

Page 18: ...le with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the sa...

Page 19: ...10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 B A B X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid contacts Wires Smart Grid pulse meter 0 5...

Page 20: ...essary bundle excessive cable length with a cable tie 6 3 12 To connect the WLAN cartridge delivered as accessory D Wireless gateway 1 Insert the WLAN cartridge into the cartridge slot on the user int...

Page 21: ...a the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home screen For example 2 9 Accessing settings via the code in the overview field settings...

Page 22: ...This setting is read only Code Description 9 2 1 E 05 a E 06 a E 07 a Integrated The backup heater will also be used for domestic hot water heating a Use the menu structure instead of the overview set...

Page 23: ...aller the possibility to indicate whether the system is filled with glycol or water This is important in case glycol is used to protect the water circuit against freezing If NOT set correctly the liqu...

Page 24: ...g 0 Underfloor heating Maximum 55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 70 C Fixed 10 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means t...

Page 25: ...acts upon it Code Description 5 6 6 0D Heat up mode 0 Reheat only Only reheat operation is allowed 1 Schedule reheat The domestic hot water tank is heated according to a schedule and between the sched...

Page 26: ...as climate and the insulation of the building the curve can be adjusted by an installer or user Types of weather dependent curve There are 2 types of weather dependent curves 2 points curve Slope off...

Page 27: ...oint mode to Main zone Heating 2 4 Main zone Setpoint mode WD heating fixed cooling OR Weather dependent Main zone Cooling 2 4 Main zone Setpoint mode Weather dependent Additional zone Heating 3 4 Add...

Page 28: ...tat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external room thermostat will control the room frost protection However the room frost pr...

Page 29: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Page 30: ...ld wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supp...

Page 31: ...e temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2 4 To perform an actuator test run Purpose Perform an actuator test run to confirm the operation of the different act...

Page 32: ...sult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user O...

Page 33: ...ing cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from outdo...

Page 34: ...rnal thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON OFF thermostat wired On OFF thermostat wireless ON OFF thermostat wirele...

Page 35: ...rical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Max...

Page 36: ...ired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core OPTIONAL PART External room thermostat Heat pump con...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P644728 1B 2022 03 Copyright 2021 Daikin 4P644728 1 B 00000002 Verantwortung f r Energie und Umwelt...

Reviews: