10 Technical data

Installation manual

34

ETVH/23E

Daikin Altherma 3 H HT F

4P644728-1B – 2022.03

10.2

Wiring diagram: Indoor unit

See  the  internal  wiring  diagram  supplied  with  the  unit  (on  the  inside  of  the  indoor  unit  switch  box  cover).  The  abbreviations  used  are  listed
below.

Notes to go through before starting the unit

English

Translation

Notes to go through before
starting the unit

Notes to go through before
starting the unit

X1M

Main terminal

X2M

Field wiring terminal for AC

X5M

Field wiring terminal for DC

X6M

Backup heater power supply
terminal

X10M

Smart Grid terminal

Earth wiring

Field supply

1

Several wiring possibilities

Option

Not mounted in switch box

Wiring depending on model

PCB

Note 1: Connection point of the
power supply for the BUH
should be foreseen outside the
unit.

Note 1: Connection point of the
power supply for the backup
heater should be foreseen outside
the unit.

Backup heater power supply

Backup heater power supply

 6T1 (3~, 230 V, 6 kW)

 6T1 (3~, 230 V, 6 kW)

 6V3 (1N~, 230 V, 6 kW)

 6V3 (1N~, 230 V, 6 kW)

 6WN/9WN (3N~, 400 V, 6/9

kW)

 6WN/9WN (3N~, 400 V, 6/9

kW)

User installed options

User installed options

 Remote user interface

 Dedicated Human Comfort

Interface (BRC1HHDA used as
room thermostat)

 Ext. indoor thermistor

 External indoor thermistor

 Ext outdoor thermistor

 External outdoor thermistor

 Digital I/O PCB

 Digital I/O PCB

 Demand PCB

 Demand PCB

 Safety thermostat

 Safety thermostat

 Smart Grid

 Smart Grid

 WLAN module

 WLAN module

 WLAN cartridge

 WLAN cartridge

 Bizone mixing kit

 Bizone mixing kit

Main LWT

Main leaving water temperature

 On/OFF thermostat (wired)

 ON/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 ON/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Add LWT

Additional leaving water
temperature

 On/OFF thermostat (wired)

 ON/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 ON/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Position in switch box

English

Translation

Position in switch box

Position in switch box

Legend

A1P

Main PCB

A2P

* ON/OFF thermostat (PC=power circuit)

A3P

* Heat pump convector

A4P

* Digital I/O PCB

A8P

* Demand PCB

A11P

Main PCB of the MMI (= user interface of the
indoor unit)

A14P

* PCB of the dedicated Human Comfort

Interface (BRC1HHDA used as room
thermostat)

A15P

* Receiver PCB (wireless ON/OFF

thermostat)

A20P

* WLAN module

A30P

* Bizone mixing kit PCB

CN* (A4P)

* Connector

DS1 (A8P)

* DIP switch

F1B

# Overcurrent fuse backup heater

F1U, F2U (A4P)

* Fuse 5 A 250 V for digital I/O PCB

K1A, K2A

* High voltage Smart Grid relay

K1M, K2M

Contactor backup heater

K5M

Safety contactor backup heater

K*R (A1P-A4P)

Relay on PCB

M2P

# Domestic hot water pump

M2S

# 2-way valve for cooling mode

PC (A15P)

* Power circuit

PHC1 (A4P)

* Optocoupler input circuit

Q1L

Thermal protector backup heater

Q4L

# Safety thermostat

Q*DI

# Earth leakage circuit breaker

R1H (A2P)

* Humidity sensor

R1T (A2P)

* Ambient sensor ON/OFF thermostat

R2T (A2P)

* External sensor (floor or ambient)

R6T

* External indoor or outdoor ambient

thermistor

S1S

# Preferential kWh rate power supply contact

S2S

# Electrical meter pulse input 1

S3S

# Electrical meter pulse input 2

S4S

# Smart Grid feed-in

S6S~S9S

* Digital power limitation inputs

S10S-S11S

# Low voltage Smart Grid contact

SS1 (A4P)

* Selector switch

TR1

Power supply transformer

X6M

# Backup heater power supply terminal strip

X10M

* Smart Grid power supply terminal strip

X*, X*A, J*, X*H*,
X*Y

Connector

X*M

Terminal strip

*

Optional

#

Field supply

Translation of text on wiring diagram

English

Translation

(1) Main power connection

(1) Main power connection

Summary of Contents for ETVX16E9W7

Page 1: ...therma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18E 6V ETVH16S23E 6V ETVH16S18E 9W ETVH16S23E 9W ETVX16S18E 6V ETVX16S23E 6V ETVX16S18E 9W ETVX16S23E 9W A B C Z 1 2 3 9 htt...

Page 2: ...m rnicemi nebo p edpisy za p edpokladu e tyto v robky jsou pou v ny v souladu s na imi pokyny u skladu sa sljede om direktivom ma ili odredbom a uz uvjet da se proizvodi koriste sukladno na im uputama...

Page 3: ...te 22 7 2 3 Configuration wizard System 22 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 24 7 2 6 Configuration wizard Additional zone 25 7 2 7 Configuration wizard...

Page 4: ...the instructions from this manual See 5 Piping installation 48 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is...

Page 5: ...isible 4 Unit installation 4 1 Preparing the installation site 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following am...

Page 6: ...lowing cases 4 2 2 To lower the switch box on the indoor unit 46 4 3 2 To connect the drain hose to the drain 47 When you need access to the high voltage switch box 2 T25 5 If you need access to the h...

Page 7: ...hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximum...

Page 8: ...er volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When circulati...

Page 9: ...e field supplied NOTICE Overpressure bypass valve delivered as accessory We recommend to install the overpressure bypass valve in the space heating water circuit Mind the minimum water volume when cho...

Page 10: ...n is then lower than assumed As a result the hydraulic components might freeze up after all Take preventive actions to ensure a minimal exposure of the glycol to air Types of glycol The types of glyco...

Page 11: ...TICE The distance between the high voltage and low voltage cables should be at least 50 mm 6 1 About electrical compliance Only for the backup heater of the indoor unit See 6 3 2 To connect the backup...

Page 12: ...1 6 Room sensor offset Item Description WLAN module See Installation manual of the WLAN module Addendum book for optional equipment Installer reference guide Use the cable delivered with the WLAN modu...

Page 13: ...9 S1S N L 5 6 1N 50 Hz 230 V AC 6 3 A 1 2 3 a b c B A B 5 6 1 2 3 X2M X1A X11YA X11YB X11Y X5M 9 10 X1M a b c a Interconnection cable main power supply b Normal kWh rate power supply c Preferential po...

Page 14: ...ng the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or eq...

Page 15: ...valve and a NO normally open valve A M2S B A B 21 28 X2M B 21 29 X2M NO NC 3 Fix the cable with cable ties to the cable tie mountings 6 3 4 To connect the electricity meters Wires 2 per meter 0 75 mm...

Page 16: ...A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of EKRP1HBAA is required b Prewi...

Page 17: ...1 Open the following see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate t...

Page 18: ...le with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the sa...

Page 19: ...10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 B A B X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid contacts Wires Smart Grid pulse meter 0 5...

Page 20: ...essary bundle excessive cable length with a cable tie 6 3 12 To connect the WLAN cartridge delivered as accessory D Wireless gateway 1 Insert the WLAN cartridge into the cartridge slot on the user int...

Page 21: ...a the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home screen For example 2 9 Accessing settings via the code in the overview field settings...

Page 22: ...This setting is read only Code Description 9 2 1 E 05 a E 06 a E 07 a Integrated The backup heater will also be used for domestic hot water heating a Use the menu structure instead of the overview set...

Page 23: ...aller the possibility to indicate whether the system is filled with glycol or water This is important in case glycol is used to protect the water circuit against freezing If NOT set correctly the liqu...

Page 24: ...g 0 Underfloor heating Maximum 55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 70 C Fixed 10 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means t...

Page 25: ...acts upon it Code Description 5 6 6 0D Heat up mode 0 Reheat only Only reheat operation is allowed 1 Schedule reheat The domestic hot water tank is heated according to a schedule and between the sched...

Page 26: ...as climate and the insulation of the building the curve can be adjusted by an installer or user Types of weather dependent curve There are 2 types of weather dependent curves 2 points curve Slope off...

Page 27: ...oint mode to Main zone Heating 2 4 Main zone Setpoint mode WD heating fixed cooling OR Weather dependent Main zone Cooling 2 4 Main zone Setpoint mode Weather dependent Additional zone Heating 3 4 Add...

Page 28: ...tat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external room thermostat will control the room frost protection However the room frost pr...

Page 29: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Page 30: ...ld wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supp...

Page 31: ...e temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2 4 To perform an actuator test run Purpose Perform an actuator test run to confirm the operation of the different act...

Page 32: ...sult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user O...

Page 33: ...ing cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from outdo...

Page 34: ...rnal thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON OFF thermostat wired On OFF thermostat wireless ON OFF thermostat wirele...

Page 35: ...rical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Max...

Page 36: ...ired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core OPTIONAL PART External room thermostat Heat pump con...

Page 37: ......

Page 38: ......