8 Commissioning

Installation manual

30

ETVH/23E

Daikin Altherma 3 H HT F

4P644728-1B – 2022.03

8

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during the commissioning
and hand-over to the user.

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

NOTICE

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

All  automatic  air  purge  valves  MUST  remain  open  after
commissioning.

INFORMATION

Protective  functions  –  "Installer-on-site  mode"

.  The

software  is  equipped  with  protective  functions,  such  as
room antifrost. The unit automatically runs these functions
when necessary.

During  installation  or  service  this  behaviour  is  undesired.
Therefore, the protective functions can be disabled:

At  first  power-on:

  The  protective  functions  are

disabled  by  default.  After  12  hours  they  will  be
automatically enabled.

Afterwards:

  An  installer  can  manually  disable  the

protective  functions  by  setting  [9.G]: 

Disable

protections

=

Yes

.  After  his  work  is  done,  he  can

enable  the  protective  functions  by  setting  [9.G]:

Disable protections

=

No

.

Also see 

"Protective functions"

 [

4

 22].

8.1

Checklist before commissioning

1

After the installation of the unit, check the items listed below.

2

Close the unit.

3

Power up the unit.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The following 

field wiring

 has been carried out according

to this document and the applicable legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between indoor unit and outdoor unit

▪ Between the local supply panel and the indoor unit

▪ Between the indoor unit and the valves (if applicable)

▪ Between  the  indoor  unit  and  the  room  thermostat  (if

applicable)

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

Backup  heater  circuit  breaker

  F1B  (field  supply)  is

turned ON.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There is NO 

water leak

 inside the indoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

automatic air purge

 valves are open.

The 

pressure  relief  valve

  purges  water  when  opened.

Clean water MUST come out.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions. See "To check the water volume and flow rate"
in 

"5.1 Preparing water piping"

 [

4

 8].

The 

domestic hot water tank

 is filled completely.

8.2

Checklist during commissioning

The 

minimum  flow  rate

  during  backup  heater/defrost

operation  is  guaranteed  in  all  conditions.  See  "To  check
the  water  volume  and  flow  rate"  in 

"5.1  Preparing  water

piping"

 [

4

 8].

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

8.2.1

To check the minimum flow rate

1

Check the hydraulic configuration to find out which
space heating loops can be closed by mechanical,
electronic, or other valves.

2

Close all space heating loops that can be closed.

3

Start the pump test run (see 

"8.2.4 To perform an

actuator test run"

 [

4

 31]).

Summary of Contents for ETVX16E9W7

Page 1: ...therma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18E 6V ETVH16S23E 6V ETVH16S18E 9W ETVH16S23E 9W ETVX16S18E 6V ETVX16S23E 6V ETVX16S18E 9W ETVX16S23E 9W A B C Z 1 2 3 9 htt...

Page 2: ...m rnicemi nebo p edpisy za p edpokladu e tyto v robky jsou pou v ny v souladu s na imi pokyny u skladu sa sljede om direktivom ma ili odredbom a uz uvjet da se proizvodi koriste sukladno na im uputama...

Page 3: ...te 22 7 2 3 Configuration wizard System 22 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 24 7 2 6 Configuration wizard Additional zone 25 7 2 7 Configuration wizard...

Page 4: ...the instructions from this manual See 5 Piping installation 48 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is...

Page 5: ...isible 4 Unit installation 4 1 Preparing the installation site 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following am...

Page 6: ...lowing cases 4 2 2 To lower the switch box on the indoor unit 46 4 3 2 To connect the drain hose to the drain 47 When you need access to the high voltage switch box 2 T25 5 If you need access to the h...

Page 7: ...hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximum...

Page 8: ...er volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When circulati...

Page 9: ...e field supplied NOTICE Overpressure bypass valve delivered as accessory We recommend to install the overpressure bypass valve in the space heating water circuit Mind the minimum water volume when cho...

Page 10: ...n is then lower than assumed As a result the hydraulic components might freeze up after all Take preventive actions to ensure a minimal exposure of the glycol to air Types of glycol The types of glyco...

Page 11: ...TICE The distance between the high voltage and low voltage cables should be at least 50 mm 6 1 About electrical compliance Only for the backup heater of the indoor unit See 6 3 2 To connect the backup...

Page 12: ...1 6 Room sensor offset Item Description WLAN module See Installation manual of the WLAN module Addendum book for optional equipment Installer reference guide Use the cable delivered with the WLAN modu...

Page 13: ...9 S1S N L 5 6 1N 50 Hz 230 V AC 6 3 A 1 2 3 a b c B A B 5 6 1 2 3 X2M X1A X11YA X11YB X11Y X5M 9 10 X1M a b c a Interconnection cable main power supply b Normal kWh rate power supply c Preferential po...

Page 14: ...ng the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or eq...

Page 15: ...valve and a NO normally open valve A M2S B A B 21 28 X2M B 21 29 X2M NO NC 3 Fix the cable with cable ties to the cable tie mountings 6 3 4 To connect the electricity meters Wires 2 per meter 0 75 mm...

Page 16: ...A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of EKRP1HBAA is required b Prewi...

Page 17: ...1 Open the following see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate t...

Page 18: ...le with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the sa...

Page 19: ...10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 B A B X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid contacts Wires Smart Grid pulse meter 0 5...

Page 20: ...essary bundle excessive cable length with a cable tie 6 3 12 To connect the WLAN cartridge delivered as accessory D Wireless gateway 1 Insert the WLAN cartridge into the cartridge slot on the user int...

Page 21: ...a the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home screen For example 2 9 Accessing settings via the code in the overview field settings...

Page 22: ...This setting is read only Code Description 9 2 1 E 05 a E 06 a E 07 a Integrated The backup heater will also be used for domestic hot water heating a Use the menu structure instead of the overview set...

Page 23: ...aller the possibility to indicate whether the system is filled with glycol or water This is important in case glycol is used to protect the water circuit against freezing If NOT set correctly the liqu...

Page 24: ...g 0 Underfloor heating Maximum 55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 70 C Fixed 10 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means t...

Page 25: ...acts upon it Code Description 5 6 6 0D Heat up mode 0 Reheat only Only reheat operation is allowed 1 Schedule reheat The domestic hot water tank is heated according to a schedule and between the sched...

Page 26: ...as climate and the insulation of the building the curve can be adjusted by an installer or user Types of weather dependent curve There are 2 types of weather dependent curves 2 points curve Slope off...

Page 27: ...oint mode to Main zone Heating 2 4 Main zone Setpoint mode WD heating fixed cooling OR Weather dependent Main zone Cooling 2 4 Main zone Setpoint mode Weather dependent Additional zone Heating 3 4 Add...

Page 28: ...tat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external room thermostat will control the room frost protection However the room frost pr...

Page 29: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Page 30: ...ld wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supp...

Page 31: ...e temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2 4 To perform an actuator test run Purpose Perform an actuator test run to confirm the operation of the different act...

Page 32: ...sult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user O...

Page 33: ...ing cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from outdo...

Page 34: ...rnal thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON OFF thermostat wired On OFF thermostat wireless ON OFF thermostat wirele...

Page 35: ...rical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Max...

Page 36: ...ired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core OPTIONAL PART External room thermostat Heat pump con...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P644728 1B 2022 03 Copyright 2021 Daikin 4P644728 1 B 00000002 Verantwortung f r Energie und Umwelt...

Reviews: