7
|
Unit installation
Installer reference guide
70
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
7.1.5 Installation patterns
Depending on the type of room in which you install the indoor unit, different installation patterns are allowed:
Room type
Allowed patterns
Living room, kitchen, garage, attic, basement, storage
room
1, 2, 3
Technical room (i.e. room that is NEVER occupied by
persons)
1, 2, 3, 4
PATTERN 1
PATTERN 2
PATTERN 3
PATTERN 4
a
b
H
release
H
release
1a
b
A
1b
H
release
H
release
2a
b
c2
c1
A
B
2b
A
b
3a
c2
c1
A
Ventilation openings
N/A
Between room A
and B
N/A
Between room A
and outside
Minimum floor area
Room A
Room A + Room B
N/A
N/A
Chimney
Might be needed
Might be needed
Connected to
outside
N/A
Release in case of
refrigerant leakage
Inside room A
Inside room A
Outside
Inside room A
Restrictions
72],
"Tables for PATTERN 1, 2 and 3"
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
a
If no chimney is installed, this is the default point of release in case of
refrigerant leakage.
If needed, you can connect a chimney here.
b
Chimney
c1
Bottom opening for natural ventilation
c2
Top opening for natural ventilation
H
release
Actual release height:
1a
2a
: Without chimney. From floor to top of the unit.
▪
For 180 l units => H
release
=1.66 m
▪
For 230 l units => H
release
=1.86 m
1b
2b
: With chimney. From floor to top of the chimney.
▪
For 180 l units => H
release
=1.66 m + Chimney height
▪
For 230 l units => H
release
=1.86 m + Chimney height