background image

ERHQ006~0 ERLQ006~008BBV3

Outdoor unit for air to water heat pump

4PW68002-1A – 03.2011

Installation manual

11

11. L

EAK

 

TEST

 

AND

 

VACUUM

 

DRYING

When all piping work is complete and the outdoor unit is connected to
the indoor unit, it is necessary to:

check for any leakages in the refrigerant piping

to perform vacuum drying to remove all moisture in the
refrigerant piping.

If there is a possibility of moisture being present in the refrigerant
piping (for example, rainwater may have entered the piping), first
carry out the vacuum drying procedure below until all moisture has
been removed.

11.1. General guidelines

All piping inside the unit has been factory tested for leaks.

Use a 2-stage vacuum pump with a non-return valve which can
evacuate to a gauge pressure of –100.7 kPa (5 Torr absolute,
–755 mm Hg). 

Connect the vacuum pump to the service port of the gas stop
valve.

If using additional refrigerant, perform air purging from the
refrigerant pipes and indoor unit using a vacuum pump, then
charge additional refrigerant.

Use a hexagonal wrench (4 mm) to operate the stop valve rod.

All refrigerant pipe joints should be tightened with a torque
wrench at the specified tightening torque. See 

"10.2. Connecting

the refrigerant piping to the outdoor unit" on page 10

 for details.

1

Pressure meter

2

Gauge manifold

3

Low-pressure valve (Lo)

4

High-pressure valve (Hi)

5

Charging hoses

6

Vacuum pump

7

Service port

8

Valve lids

9

Gas stop valve

10

Liquid stop valve

1

Connect the projection side (on which the worm pin is pressed)
of the charging hose coming from the gauge manifold to the gas
stop valve's service port.

2

Fully open the gauge manifold's low-pressure valve (Lo) and
completely close its high-pressure valve (Hi).
The high-pressure valve subsequently requires no operation.

3

Apply vacuum pumping. Check that the compound pressure
gauge reads –0.1 MPa (–760 mm Hg).

4

Close the gauge manifold's low-pressure valve (Lo) and stop the
vacuum pump.

Leave as is for 4-5 minutes and make sure that the coupling
meter needle does not go back.

5

Remove the covers from the liquid stop valve and gas stop valve.

6

Turn the liquid stop valve's rod 90 degrees counterclockwise with
a hexagonal wrench to open the valve.

Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from the indoor unit's
flare and the outdoor unit's flare and the valve rods.
After the check is complete, wipe all soapy water off.

7

Disconnect the charging hose from the gas stop valve's service
port, then fully open the liquid and gas stop valves.

Do not attempt to turn the valve rod beyond its stop.

8

Tighten the valve lids and service port caps for the liquid and
gas stop valves with a torque wrench at the specified torques.
See 

"10.2. Connecting the refrigerant piping to the outdoor unit"

on page 10

 for details.

NOTICE

Make sure that the gas stop valve and liquid stop
valve are firmly closed before performing the leak test
or vacuum drying.

Use a vacuum pump for R410A exclusively. Using the
same vacuum pump for different refrigerants may
damage the vacuum pump or the unit.

WARNING

Do not mix any substance other than the specified
refrigerant (R410A) into the refrigeration cycle.

When refrigerant gas leaks occur, ventilate the room
as soon and as much as possible.

R410A, as well as other refrigerants, should always
be recovered and never be released directly into the
environment.

INFORMATION

Do not purge the air with refrigerants. Use a vacuum pump
to evacuate the installation.

Pipe length

≤≤≤≤

15 m

>

15 m

Run time

10 minutes

15 minutes

NOTICE

If the meter needle does go back, this may indicate
presence of moisture or leaking from connecting
parts. Repeat steps 2 through 4 after checking all
connecting parts and slightly loosening and
retightening the nuts.

1

4

10

2

6

5

3

7 8 9

8

Summary of Contents for ERHQ006BBV3

Page 1: ...INSTALLATION MANUAL ERHQ006BBV3 ERHQ007BBV3 ERHQ008BBV3 ERLQ006BBV3 ERLQ007BBV3 ERLQ008BBV3 Outdoor unit for air to water heat pump...

Page 2: ...lingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold...

Page 3: ...Forced cooling operation 13 14 Electrical wiring work 13 14 1 Precautions on electrical wiring work 13 14 2 Internal wiring Parts table 14 14 3 Connecting power supply and interunit wiring 14 Notes t...

Page 4: ...vities described in this manual shall be carried out by an installer Be sure to wear adequate personal protection equipment protection gloves safety glasses when performing installation maintenance or...

Page 5: ...se electrical shock and re Electrical work must be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insuf cient capacity or incomplet...

Page 6: ...pressor may result Be sure to con rm the model name and the serial no of the outer front plates when attaching detaching the plates to avoid mistakes When closing the service panels take care that the...

Page 7: ...or 9 Compressor 10 Liquid stop valve 11 Gas stop valve 12 Service port 4 3 Functional diagram 1 Thermistor air 2 Heat exchanger 3 Thermistor heat exchanger 4 Fan motor 5 Filter 6 Electronic expansion...

Page 8: ...n be avoided as much as possible Do not install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit must be covered Do...

Page 9: ...stallation ground so that the unit will not cause any operating vibration or noise after installation 2 Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each eld supply 3 Fix the unit sec...

Page 10: ...ng three sides unit mm 7 1 Outdoor unit installation drawing 1 Wrap the insulation pipe with nishing tape from bottom to top 2 Service cover 3 Stop valve cover 4 250 mm from wall Allow space for pipin...

Page 11: ...into the system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not ow oppositely into the system while the pump is not working Use a vacuum pump which can ev...

Page 12: ...erial polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstan...

Page 13: ...m pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the...

Page 14: ...iphon attached or something similar Be sure to use tools exclusively for R410A to ensure required pressure resistance and to prevent foreign materials from mixing into the system 12 3 Calculating the...

Page 15: ...t it does not come in contact with the piping particularly on the high pressure side Make sure no external pressure is applied to the terminal connectors When installing the earth leakage circuit brea...

Page 16: ...X11A X12A Connector X1M X2M Terminal strip Y1E Electronic expansion valve voil Y1R Reversing solenoid valve coil Z1C Z7C Ferrite core Only for ERLQ 14 3 Connecting power supply and interunit wiring 1...

Page 17: ...y may cause heat and re Strip the wire at terminal block L N 1 2 3 C A 3 1 4 5 4 2 B 2 1 1 Stranded conductor wire 2 Round crimp style terminal 1 Strip wire end to this point 2 Excessive strip length...

Page 18: ...S 18 1 Technical specifications 18 2 Electrical specifications INFORMATION If the circuit breaker trips to shut off the power to the outdoor unit the system will restore the original operation mode wh...

Page 19: ......

Page 20: ...4PW68002 1A 03 2011 Copyright 2011 Daikin...

Reviews: