Daikin ERHQ006BBV3 Installation Manual Download Page 12

Installation manual

10

ERHQ006~0 ERLQ006~008BBV3

Outdoor unit for air to water heat pump

4PW68002-1A – 03.2011

10. R

EFRIGERANT

 

PIPING

10.1. Flaring the pipe end

To flare each pipe end, follow the procedure below:

1

Cut the pipe end with a pipe cutter.

2

Remove burrs with the cut surface facing downward so that the
chips do not enter the pipe.

1

Cut exactly at right angles.

2

Remove burrs

3

Remove the flare nut from the stop valve and put the flare nut on
the pipe.

4

Flare the pipe. Set exactly at the position shown below.

5

Check that the flaring is properly made.

1

Flare's inner surface must be flaw-
free.

2

The pipe end must be evenly flared in 
a perfect circle.

3

Make sure that the flare nut is fitted.

10.2. Connecting the refrigerant piping to the outdoor 

unit

1

When connecting the flare nut, coat the flare inner surface with
ether oil or with ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.

2

When loosening a flare nut, always use two wrenches together.

When connecting the piping, always use a spanner and torque
wrench together to tighten the flare nut to prevent nut cracking
and leaks.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

10.3. Refrigerant piping work

Pipe handling guidelines

All pipe bends should be as gentle as possible. Use a pipe bender for
bending.

Bending radius should be 30 to 40 mm or larger.

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the
following:

Insulation material: polyethylene foam
Heat transfer rate: 0.041 to 0.052 W/mK (0.035 to 0.045 kcal/
mh°C)
Refrigerant gas pipe's surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this
temperature.

Be sure to insulate both the gas and liquid piping and to provide
insulation dimensions as below.

1

Gas pipe

2

Inter-unit wiring

3

Liquid pipe

4

Liquid pipe insulation

5

Finishing tape

6

Gas pipe insulation

Use separate thermal insulation pipes for gas and liquid
refrigerant pipes.

Flare tool for R410A 

(clutch type)

Conventional flare tool

Clutch type 

(Ridgid-type)

Wing nut type 

(Imperial-type)

A

0~0.5 mm

1.0~1.5 mm

1.5~2.0 mm

DANGER

Installation shall be done by an installer, the choice of
materials and installation shall comply with applicable
legislation. In Europe the EN378 is the application
standard that shall be used.

CAUTION

Do not use mineral oil on flared part.
Mineral oil getting into the system would reduce the
lifetime of the units.

Never use piping which has been used for previous
installations. Only use parts which are delivered with
the unit.

Do never install a drier to this R410A unit in order to
guarantee its lifetime. The drying material may
dissolve and damage the system.

Incomplete flaring may cause refrigerant gas leakage.

1

2

A

1

2

3

Flare nut

Flare nut tightening torque

Ø6.4 mm (1/4")

15~17 N•m

Ø15.9 mm (5/8")

63~75 N•m

Valve cap tightening torque

Valve cap

Gas pipe

Ø6.4 mm (1/4")

21.6~27.4 N•m

Ø15.9 mm (5/8")

44.1~53.9 N•m

Service port cap tightening torque

10.8~14.7 N•m

Pipe size

Pipe insulation

Outer diameter

Thickness

Inner diameter

Thickness

6.4 mm (1/4")

0.8 mm

8-10 mm

10 mm

15.9 mm (5/8")

1.0 mm

16-20 mm

13 mm

1

2

3

4

5

6

1

2

4

3

Summary of Contents for ERHQ006BBV3

Page 1: ...INSTALLATION MANUAL ERHQ006BBV3 ERHQ007BBV3 ERHQ008BBV3 ERLQ006BBV3 ERLQ007BBV3 ERLQ008BBV3 Outdoor unit for air to water heat pump...

Page 2: ...lingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold...

Page 3: ...Forced cooling operation 13 14 Electrical wiring work 13 14 1 Precautions on electrical wiring work 13 14 2 Internal wiring Parts table 14 14 3 Connecting power supply and interunit wiring 14 Notes t...

Page 4: ...vities described in this manual shall be carried out by an installer Be sure to wear adequate personal protection equipment protection gloves safety glasses when performing installation maintenance or...

Page 5: ...se electrical shock and re Electrical work must be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insuf cient capacity or incomplet...

Page 6: ...pressor may result Be sure to con rm the model name and the serial no of the outer front plates when attaching detaching the plates to avoid mistakes When closing the service panels take care that the...

Page 7: ...or 9 Compressor 10 Liquid stop valve 11 Gas stop valve 12 Service port 4 3 Functional diagram 1 Thermistor air 2 Heat exchanger 3 Thermistor heat exchanger 4 Fan motor 5 Filter 6 Electronic expansion...

Page 8: ...n be avoided as much as possible Do not install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit must be covered Do...

Page 9: ...stallation ground so that the unit will not cause any operating vibration or noise after installation 2 Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each eld supply 3 Fix the unit sec...

Page 10: ...ng three sides unit mm 7 1 Outdoor unit installation drawing 1 Wrap the insulation pipe with nishing tape from bottom to top 2 Service cover 3 Stop valve cover 4 250 mm from wall Allow space for pipin...

Page 11: ...into the system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not ow oppositely into the system while the pump is not working Use a vacuum pump which can ev...

Page 12: ...erial polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstan...

Page 13: ...m pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the...

Page 14: ...iphon attached or something similar Be sure to use tools exclusively for R410A to ensure required pressure resistance and to prevent foreign materials from mixing into the system 12 3 Calculating the...

Page 15: ...t it does not come in contact with the piping particularly on the high pressure side Make sure no external pressure is applied to the terminal connectors When installing the earth leakage circuit brea...

Page 16: ...X11A X12A Connector X1M X2M Terminal strip Y1E Electronic expansion valve voil Y1R Reversing solenoid valve coil Z1C Z7C Ferrite core Only for ERLQ 14 3 Connecting power supply and interunit wiring 1...

Page 17: ...y may cause heat and re Strip the wire at terminal block L N 1 2 3 C A 3 1 4 5 4 2 B 2 1 1 Stranded conductor wire 2 Round crimp style terminal 1 Strip wire end to this point 2 Excessive strip length...

Page 18: ...S 18 1 Technical specifications 18 2 Electrical specifications INFORMATION If the circuit breaker trips to shut off the power to the outdoor unit the system will restore the original operation mode wh...

Page 19: ......

Page 20: ...4PW68002 1A 03 2011 Copyright 2011 Daikin...

Reviews: