Daikin ERHQ006BBV3 Installation Manual Download Page 6

Installation manual

4

ERHQ006~0 ERLQ006~008BBV3

Outdoor unit for air to water heat pump

4PW68002-1A – 03.2011

For use of units in applications with temperature alarm settings it
is advised to foresee a delay of 10 minutes for signalling the
alarm in case the alarm temperature is exceeded. The unit may
stop for several minutes during normal operation for "defrosting
the unit", or when in "thermostat stop" operation.

Tighten the flare nut according to the specified method such as
with a torque wrench.
If the flare nut is tightened too hard, the flare nut may crack after
a long time and cause refrigerant leakage.

3.

B

EFORE

 

INSTALLATION

3.1.

Scope of the manual

This manual describes the procedures for handling, installing and
connecting ERHQ and ERLQ units. This manual has been prepared
to ensure adequate maintenance of the unit, and it will provide help if
problems occur.

3.2.

Precautions for R410A

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
-

Clean and dry

Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
-

Tight

Read 

"9. Precautions on refrigerant piping" on page 9

 carefully

and follow these procedures correctly.

Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant is
in state of gas, its composition changes and the system will not
work properly).

The connected indoor unit must be the EKHBH/X008 unit
designed exclusively for R410A.

3.3.

Installation

For installation of the indoor unit, refer to the indoor unit
installation manual.

Never operate the unit without the thermistors, burning of the
compressor may result.

Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.

When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.

3.4.

Model identification

ERLQ units include special equipment (insulation, bottom plate
heater,...) to ensure good operation in areas where low ambient
temperature can occur together with high humidity conditions. In such
conditions the ERHQ models may experience problems with severe
ice build up on the aircooled coil. In case such conditions are
expected, the ERLQ must be installed instead. These models contain
countermeasures (insulation, bottom plate heater,...) to prevent
freeze up.

3.5.

Accessories

Check if the following accessories are included with the unit

Possible options

Optional bottom plate heater

WARNING

Since maximum working pressure for this outdoor unit is
4.17 MPa or 41.7 bar, pipes of larger wall thickness may be
required. Refer to paragraph 

"8.1. Selection of piping

material" on page 9

.

ER

H

Q

006

BB

V3

V3=1~, 230 V, 50 Hz

Series

Capacity class (kW)

Outdoor unit on R410A

H=low water temperature – ambient zone (0~–10°C)
L=low water temperature – ambient zone (–10°C~–20°C)

Split outdoor pair heat pump

INFORMATION

An ERLQ0*

BA/BB

 outdoor unit can only be

connected to an EKHBH/X008

BA/BB

 indoor unit

(bottom plate heater at outdoor unit has to be
controlled by indoor unit).

An ERHQ0*

BA/BB

 outdoor unit can be connected to

an EKHBH/X008

BA/BB

 indoor unit or to an EKHBH/

X008

AA

 indoor unit (if a bottom plate heater kit is

required, see 

"Possible options" on page 4

).

Installation manual

1

Fluorinated greenhouse gases 
label

1

Multilingual fluorinated 
greenhouse gases label

1

Bottom plate heater

ERHQ

Optional kit

ERLQ

Standard

(a)

(a) Factory mounted.

EKBPHT08

EKBPHT08BA

EKHBH/X008

AA

Possible

Not allowed

EKHBH/X008

BA/BB

Possible

Possible

Summary of Contents for ERHQ006BBV3

Page 1: ...INSTALLATION MANUAL ERHQ006BBV3 ERHQ007BBV3 ERHQ008BBV3 ERLQ006BBV3 ERLQ007BBV3 ERLQ008BBV3 Outdoor unit for air to water heat pump...

Page 2: ...lingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold...

Page 3: ...Forced cooling operation 13 14 Electrical wiring work 13 14 1 Precautions on electrical wiring work 13 14 2 Internal wiring Parts table 14 14 3 Connecting power supply and interunit wiring 14 Notes t...

Page 4: ...vities described in this manual shall be carried out by an installer Be sure to wear adequate personal protection equipment protection gloves safety glasses when performing installation maintenance or...

Page 5: ...se electrical shock and re Electrical work must be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insuf cient capacity or incomplet...

Page 6: ...pressor may result Be sure to con rm the model name and the serial no of the outer front plates when attaching detaching the plates to avoid mistakes When closing the service panels take care that the...

Page 7: ...or 9 Compressor 10 Liquid stop valve 11 Gas stop valve 12 Service port 4 3 Functional diagram 1 Thermistor air 2 Heat exchanger 3 Thermistor heat exchanger 4 Fan motor 5 Filter 6 Electronic expansion...

Page 8: ...n be avoided as much as possible Do not install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit must be covered Do...

Page 9: ...stallation ground so that the unit will not cause any operating vibration or noise after installation 2 Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each eld supply 3 Fix the unit sec...

Page 10: ...ng three sides unit mm 7 1 Outdoor unit installation drawing 1 Wrap the insulation pipe with nishing tape from bottom to top 2 Service cover 3 Stop valve cover 4 250 mm from wall Allow space for pipin...

Page 11: ...into the system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not ow oppositely into the system while the pump is not working Use a vacuum pump which can ev...

Page 12: ...erial polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstan...

Page 13: ...m pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the...

Page 14: ...iphon attached or something similar Be sure to use tools exclusively for R410A to ensure required pressure resistance and to prevent foreign materials from mixing into the system 12 3 Calculating the...

Page 15: ...t it does not come in contact with the piping particularly on the high pressure side Make sure no external pressure is applied to the terminal connectors When installing the earth leakage circuit brea...

Page 16: ...X11A X12A Connector X1M X2M Terminal strip Y1E Electronic expansion valve voil Y1R Reversing solenoid valve coil Z1C Z7C Ferrite core Only for ERLQ 14 3 Connecting power supply and interunit wiring 1...

Page 17: ...y may cause heat and re Strip the wire at terminal block L N 1 2 3 C A 3 1 4 5 4 2 B 2 1 1 Stranded conductor wire 2 Round crimp style terminal 1 Strip wire end to this point 2 Excessive strip length...

Page 18: ...S 18 1 Technical specifications 18 2 Electrical specifications INFORMATION If the circuit breaker trips to shut off the power to the outdoor unit the system will restore the original operation mode wh...

Page 19: ......

Page 20: ...4PW68002 1A 03 2011 Copyright 2011 Daikin...

Reviews: