4 Installation

Installation manual

8

ERGA04~08DAV3

Daikin Altherma – Low temperature split

4P489913-1B – 2017.10

355 mm

600 mm

Drain  pan  heater.

  You  can  use  the  drain  pan  heater  option

(EKDPH008CA)  to  prevent  freezing-up  of  the  drain  pan.  For  the
installation  instructions,  see  the  installation  manual  of  the  drain
pan heater.

4.2.4

To prevent the outdoor unit from falling
over

In  case  the  unit  is  installed  in  places  where  strong  wind  can  tilt  the
unit, take following measure:

1

Prepare  2  cables  as  indicated  in  the  following  illustration  (field
supply).

2

Place the 2 cables over the outdoor unit.

3

Insert  a  rubber  sheet  between  the  cables  and  the  outdoor  unit
to prevent the cable from scratching the paint (field supply).

4

Attach the cable’s ends. Tighten those ends.

4.3

Connecting the refrigerant piping

DANGER: RISK OF BURNING

4.3.1

To connect the refrigerant piping to the
outdoor unit

1

Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.

a

b

c

a

Liquid stop valve

b

Gas stop valve

c

Service port

2

Connect  the  gas  refrigerant  connection  from  the  indoor  unit  to
the gas stop valve of the outdoor unit.

NOTICE

It  is  recommended  that  the  refrigerant  piping  between
indoor  and  outdoor  unit  is  installed  in  a  ducting  or  the
refrigerant piping is wrapped with finishing tape.

4.4

Checking the refrigerant piping

4.4.1

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution
from  your  wholesaler.  Do  not  use  soap  water,  which  may
cause cracking of flare nuts (soap water may contain salt,
which  absorbs  moisture  that  will  freeze  when  the  piping
gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap
water  may  contain  ammonia  which  causes  a  corrosive
effect between the brass flare nut and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

4.4.2

To perform vacuum drying

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Summary of Contents for ERGA04DAV3

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split ERGA04DAV3 ERGA06DAV3 A ERGA08DAV3 A...

Page 2: ...owieniami Dyrektyw n urma prevederilor 19 20 21 22 23 24 25 ob upo tevanju dolo b vastavalt n uetele laikantis nuostat pateikiam iev rojot pras bas kas noteiktas odr iavaj c ustanovenia bunun ko ullar...

Page 3: ...taava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 4: ...m Outdoor unit 11 6 2 Wiring diagram Outdoor unit 12 1 About the documentation 1 1 About this document Target audience Authorised installers Documentation set This document is part of a documentation...

Page 5: ...stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater 3 1 1 Installation site requirements of the outdoor unit...

Page 6: ...outdoor unit on page 9 4 2 Mounting the outdoor unit 4 2 1 To provide the installation structure This topic shows different installation structures For all use 4 sets of M8 or M10 anchor bolts nuts a...

Page 7: ...o the right 2 Remove the sling by pulling 1 side of the sling 3 Fix the unit 2 3 2 1 a a a Air outlet NOTICE Properly align the unit Make sure the backside of the unit does NOT protrude 3 Remove the p...

Page 8: ...indoor unit to the gas stop valve of the outdoor unit NOTICE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapp...

Page 9: ...1000 kg kg GWP XXX RXXX a f c d e a If a multilingual fluorinated greenhouse gases label is delivered with the unit see accessories peel off the applicable language and stick it on top of a b Factory...

Page 10: ...tie 1 1 5 Connect an earth leakage circuit breaker and fuse to the power supply line 4 7 Finishing the outdoor unit installation 4 7 1 To finish the outdoor unit installation 1 Insulate and fix the r...

Page 11: ...Y1S 4 0 CuT M1F b a c d e f g h i j k k g g a Field piping liquid 6 4 mm flare connection b Field piping gas 15 9 mm flare connection c Stop valve liquid d Stop valve with service port gas e Filter f...

Page 12: ...en YLW yellow 3 Legend AL Connector C Capacitor DB Rectifier bridge DC Connector DP Connector E Connector F1U Fuse T 6 3 A 250 V FU1 FU2 Fuse T 3 15 A 250 V FU3 Fuse T 30 A 250 V H Connector IPM Intel...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...4P489913 1B 2017 10 Copyright 2017 Daikin...

Reviews: