4 Installation

Installation manual

6

ERGA04~08DAV3

Daikin Altherma – Low temperature split

4P489913-1B – 2017.10

In  any  case,  provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally, make sure the unit is positioned at least 100 mm above
the  maximum  expected  level  of  snow.  See 

"4.2  Mounting  the

outdoor unit" on page 6

 for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

4

Installation

4.1

Opening the units

4.1.1

To open the outdoor unit

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING

See 

"4.3.1  To  connect  the  refrigerant  piping  to  the  outdoor  unit"  on

page  8

  and 

"4.6.3  To  connect  the  electrical  wiring  on  the  outdoor

unit" on page 9

.

4.2

Mounting the outdoor unit

4.2.1

To provide the installation structure

This  topic  shows  different  installation  structures.  For  all,  use  4  sets
of M8 or M10 anchor bolts, nuts and washers. In any case, provide
at  least  300  mm  of  free  space  below  the  unit.  Additionally,  make
sure  the  unit  is  positioned  at  least  100  mm  above  the  maximum
expected level of snow.

INFORMATION

The  maximum  height  of  the  upper  protruding  part  of  the
bolts is 15 mm.

Option 1: On mounting feet "flexi-foot with strut"

(mm)

0 mm

<150

a

>300

300

600  

>100

a

Maximum snowfall height

Option 2: On plastic mounting feet

In  this  case,  you  can  use  the  bolts,  nuts,  washers  and  spring
washers delivered with the unit as accessories.

0 mm

Option 3: On a pedestal with the EKFT008D option kit

The  EKFT008D  option  kit  is  recommended  in  areas  with  heavy
snowfall.

300

600

<150

<150

(mm)

>300

100

a

b

0 mm

a

Maximum snowfall height

b

EKFT008D option kit

Option 4: On brackets to the wall with the EKFT008D option kit

The  EKFT008D  option  kit  is  recommended  in  areas  with  heavy
snowfall.

Summary of Contents for ERGA04DAV3

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split ERGA04DAV3 ERGA06DAV3 A ERGA08DAV3 A...

Page 2: ...owieniami Dyrektyw n urma prevederilor 19 20 21 22 23 24 25 ob upo tevanju dolo b vastavalt n uetele laikantis nuostat pateikiam iev rojot pras bas kas noteiktas odr iavaj c ustanovenia bunun ko ullar...

Page 3: ...taava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 4: ...m Outdoor unit 11 6 2 Wiring diagram Outdoor unit 12 1 About the documentation 1 1 About this document Target audience Authorised installers Documentation set This document is part of a documentation...

Page 5: ...stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater 3 1 1 Installation site requirements of the outdoor unit...

Page 6: ...outdoor unit on page 9 4 2 Mounting the outdoor unit 4 2 1 To provide the installation structure This topic shows different installation structures For all use 4 sets of M8 or M10 anchor bolts nuts a...

Page 7: ...o the right 2 Remove the sling by pulling 1 side of the sling 3 Fix the unit 2 3 2 1 a a a Air outlet NOTICE Properly align the unit Make sure the backside of the unit does NOT protrude 3 Remove the p...

Page 8: ...indoor unit to the gas stop valve of the outdoor unit NOTICE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapp...

Page 9: ...1000 kg kg GWP XXX RXXX a f c d e a If a multilingual fluorinated greenhouse gases label is delivered with the unit see accessories peel off the applicable language and stick it on top of a b Factory...

Page 10: ...tie 1 1 5 Connect an earth leakage circuit breaker and fuse to the power supply line 4 7 Finishing the outdoor unit installation 4 7 1 To finish the outdoor unit installation 1 Insulate and fix the r...

Page 11: ...Y1S 4 0 CuT M1F b a c d e f g h i j k k g g a Field piping liquid 6 4 mm flare connection b Field piping gas 15 9 mm flare connection c Stop valve liquid d Stop valve with service port gas e Filter f...

Page 12: ...en YLW yellow 3 Legend AL Connector C Capacitor DB Rectifier bridge DC Connector DP Connector E Connector F1U Fuse T 6 3 A 250 V FU1 FU2 Fuse T 3 15 A 250 V FU3 Fuse T 30 A 250 V H Connector IPM Intel...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...4P489913 1B 2017 10 Copyright 2017 Daikin...

Reviews: