8
|
Piping installation
Installer reference guide
94
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
Part
Description
a
An automatic air intake (for air supply) should be installed at the
highest point. For example, an automatic air purge.
b
Protection for the field piping. The freeze protection valves must
be installed:
▪
vertically to allow water to flow out properly and free from
obstructions.
▪
at all lowest points of the field piping.
▪
in the coldest part and away from heat sources.
Note:
Leave at least 15 cm clearance from the ground to prevent
ice from blocking the water exit.
c
Isolation of water inside the house when there is a power
interruption. Normally closed valves (located indoors near the
piping entry/exit points) can prevent that all water from indoor
piping is drained when the freeze protection valves open.
▪
When there is a power interruption:
The normally closed valves
close and isolate the water inside the house. If the freeze
protection valves open, only the water outside the house is
drained.
▪
In other circumstances
(example: when there is a pump failure):
The normally closed valves remain open. If the freeze protection
valves open, the water from inside the house is also drained.
NOTICE
When freeze protection valves are installed, set the minimum cooling setpoint
(default=7°C) at least 2°C higher than the maximum opening temperature of the
freeze protection valve. If lower, freeze protection valves can open during cooling
operation.
8.2.7 To fill the domestic hot water tank
1
Open every hot water tap in turn to purge air from the system pipe work.
2
Open the cold water supply valve.
3
Close all water taps after all air is purged.
4
Check for water leaks.
8.2.8 To insulate the water piping
The piping in the complete water circuit MUST be insulated to prevent
condensation during cooling operation and reduction of the heating and cooling
capacity.
Outdoor water piping insulation
NOTICE
Outside piping.
Make sure the outside piping is insulated as instructed to protect
against hazards.
For piping in free air, it is recommended to use the insulation thickness as shown in
below table as a minimum (with λ=0.039 W/mK).
Summary of Contents for EPRA08EAV3
Page 289: ...13 13...
Page 290: ......
Page 291: ......
Page 292: ...4P634886 1 2021 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...