5 Starting up the system
Installation manual
6
EKMBU EKMBUHCA9W1
Daikin Altherma low temperature monobloc backup heater
4P405547-1C – 2015.08
Backup heater
type
Connections to
backup heater power
supply
Connections to
terminals
3 kW 1~ 230 V
(*9W)
6 kW 1~ 230 V
(*9W)
L
L
N
N
F1B
1 2 3 4 5 6
X14M
6 kW 3N~ 400 V
(*9W)
9 kW 3N~ 400 V
(*9W)
F1B
L1 L2 L3
1 2 3 4 5 6
X14M
3
Fix the cable with cable ties to the cable tie mountings.
INFORMATION
For more information on the backup heater types, and for
how to configure the backup heater, refer to the
"Configuration" chapter of the installation manual of the
outdoor unit.
During connection of the backup heater, miswiring is possible. To
detect possible miswiring on the *9W model, it is highly
recommended to measure the resistance value of the heater
elements. Depending on the different backup heater types, following
resistance values (see table below) should be measured. ALWAYS
measure the resistance on the contactor clamps K1M, K2M, and
K5M.
3 kW
1~ 230 V
6 kW
1~ 230 V
6 kW
3N~
400 V
9 kW
3N~
400 V
K1M/1
K5M/13
52.9Ω
52.9Ω
∞
∞
K1M/3
∞
∞
105.8Ω
105.8Ω
K1M/5
∞
∞
105.8Ω
105.8Ω
K1M/3
K1M/5
26.5Ω
26.5Ω
105.8Ω
105.8Ω
K2M/1
K5M/13
∞
26.5Ω
∞
∞
K2M/3
∞
∞
52.9Ω
52.9Ω
K2M/5
∞
∞
52.9Ω
52.9Ω
K2M/3
K2M/5
52.9Ω
52.9Ω
52.9Ω
52.9Ω
K1M/5
K2M/1
∞
∞
∞
∞
Example measure resistance between K1M/1 and K5M/13:
K1M
K2M
K2M
1 3 5 13
2 4 6 14
K5M
1 3 5 13
2 4 6 14
1 3 5 13
2 4 6 14
Ω
Ω
4.4.3
To connect the backup heater kit to the
control box
1
For the thermistor, connect 2 wires between backup heater
terminals X15M/1+2 and control box terminals X2M/5+6.
2
For the thermal protector, connect 2 wires between backup
heater terminals X15M/3+4 and control box terminals
X2M/11+12.
3
For the connection with the control box, connect 3 wires
between backup heater terminals X15M/5+6+7 and control box
terminals X2M/13+14+15.
X2M
X8M
X1M
X15M
A4P
F1B
14
13
12
11
6
5
15
1 2 3 4 5 6 7
4
Fix the cable with cable ties to the cable tie mountings.
INFORMATION
▪ For details about the connections, refer to the wiring
diagram.
▪ Use a multi-core cable.
▪ For backup heater kit EKMBUHCA3V3, it is NOT
required to make a connection between backup heater
terminal X15M/6 and control box terminal X2M/14.
5
Starting up the system
For instructions on how to configure and commission the system,
and hand it over to the user, refer to the installation manual of the
outdoor unit.