background image

4 Installation

Installation manual

5

EKMBU EKMBUHCA9W1
Daikin Altherma low temperature monobloc backup heater
4P405547-1C – 2015.08

INFORMATION

Inside  the  backup  heater,  an  automatic  air  purge  valve  is
installed.  For  the  location  of  this  valve,  refer  to  the
"Technical  data"  chapter  of  the  installer  reference  guide.
For instructions on how to perform an air purge, refer to the
"Commissioning"  chapter  of  the  installation  manual  of  the
outdoor unit.

4.4

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.4.1

To connect the electrical wiring on the
backup heater

Routing

Possible cables (depends on the installed options)

a

Low voltage

▪ Backup  heater  kit  thermistor  (interconnection  with

control box EKCB07CAV3)

▪ Backup heater kit thermal protector (interconnection

with control box EKCB07CAV3)

▪ Backup  heater  kit  connection  (to  control  box

EKCB07CAV3)

b

High
voltage

▪ Main power supply

1

Insert the wiring from the bottom of the backup heater.

2

Inside the backup heater, route the wiring as follows:

Backup heater

type

Routing

*3V

a

b

a

 Low voltage wiring

b

 High voltage wiring

*9W

a

b

a

 Low voltage wiring

b

 High voltage wiring

3

Fix the wiring with cable ties to the cable tie mountings.

NOTICE

The  distance  between  the  high  voltage  and  low  voltage
cables should be at least 25 mm.

4.4.2

To connect the backup heater power
supply

CAUTION

To  guarantee  the  unit  is  completely  earthed,  always
connect  the  backup  heater  power  supply  and  the  earth
cable.

CAUTION

If a tank with a built‑in electrical booster heater (EKHW) is
part  of  the  system,  use  a  dedicated  power  circuit  for  the
backup  heater  and  booster  heater.  NEVER  use  a  power
circuit  shared  by  another  appliance.  This  power  circuit
must  be  protected  with  the  required  safety  devices
according to the applicable legislation.

Depending on the model, the backup heater capacity can vary. Make
sure that the power supply is in accordance with the backup heater
capacity, as listed in the table below.

Backup

heater type

Backup

heater

capacity

Power

supply

Maximum

running

current

Z

max

(Ω)

*3V

3 kW

1~ 230 V

13 A

*9W

3 kW

1~ 230 V

13 A

6 kW

1~ 230 V

26 A

(a)(b)

6 kW

3N~ 400 V

8.6 A

9 kW

3N~ 400 V

13 A

(a)

Equipment complying with EN/IEC 61000-3-12 (European/
International Technical Standard setting the limits for
harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and
≤75 A per phase.).

(b)

This equipment complies with EN/IEC 61000‑3‑11
(European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and flicker in
public low-voltage supply systems for equipment with rated
current ≤75 A) provided that the system impedance Z

sys

 is

less than or equal to Z

max

 at the interface point between the

user's supply and the public system. It is the responsibility
of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if
necessary, that the equipment is connected only to a
supply with a system impedance Z

sys

 less than or equal to

Z

max

.

1

Connect  the  backup  heater  power  supply.  For  *3V  models,  a
double‑pole  fuse  is  used  for  F1B.  For  *9W  models,  a  4‑pole
fuse is used for F1B.

2

If required, modify the connection on terminal X14M.

Backup heater

type

Connections to

backup heater power

supply

Connections to

terminals

3 kW 1~ 230 V
(*3V)

L N

L N

F1B

Summary of Contents for EKMBUHCA3V3

Page 1: ...Installation manual Daikin Altherma low temperature monobloc backup heater English Installation manual Daikin Altherma low temperature monobloc backup heater EKMBUHCA3V3 EKMBUHCA9W1 ...

Page 2: ... manual Installation instructions Format Paper in the box of the outdoor unit Control box installation manual Installation instructions Format Paper in the box of the control box Option box installation manual Installation instructions Format Paper in the box of the option box Backup heater installation manual Installation instructions Format Paper in the box of the backup heater Installer referen...

Page 3: ...d minimum water flow rate is guaranteed at all times For more information refer to the installation manual of the outdoor unit 3 3 Preparing electrical wiring 3 3 1 Overview of electrical connections for external and internal actuators Item Description Wires Maximum running current Interconnection cable 1 Backup heater kit thermistor 2 a 2 Backup heater kit thermal protector 2 a 3 Backup heater ki...

Page 4: ... m 1 Connect the water piping field supply to the water in and outlet of the backup heater b a a Water inlet b Water outlet NOTICE When the backup heater is installed in a reversible system EBLQ05 07CAV3 and below conditions are met see illustration condensation may occur inside the backup heater To provide a bypass for the condensate install valve kit EKMBHBP1 Do NOT install any other valve kit t...

Page 5: ...rt of the system use a dedicated power circuit for the backup heater and booster heater NEVER use a power circuit shared by another appliance This power circuit must be protected with the required safety devices according to the applicable legislation Depending on the model the backup heater capacity can vary Make sure that the power supply is in accordance with the backup heater capacity as liste...

Page 6: ... 8Ω 105 8Ω K1M 5 105 8Ω 105 8Ω K1M 3 K1M 5 26 5Ω 26 5Ω 105 8Ω 105 8Ω K2M 1 K5M 13 26 5Ω K2M 3 52 9Ω 52 9Ω K2M 5 52 9Ω 52 9Ω K2M 3 K2M 5 52 9Ω 52 9Ω 52 9Ω 52 9Ω K1M 5 K2M 1 Example measure resistance between K1M 1 and K5M 13 K1M K2M K2M 1 3 5 13 2 4 6 14 K5M 1 3 5 13 2 4 6 14 1 3 5 13 2 4 6 14 Ω Ω 4 4 3 To connect the backup heater kit to the control box 1 For the thermistor connect 2 wires between...

Page 7: ......

Page 8: ...4P405547 1C 2015 08 Copyright 2015 Daikin ...

Reviews: