E260A + EK260AA

Domestic hot water tank for air to water heat pump system

4PW53247-1B

Installation manual

7

3

Only for domestic hot water tanks with a service opening
(EKHTSP): 

For cleaning of the hot water tank interior and the heat
exchanger, remove front decoration panels and insulation piece,
drain the domestic hot water tank and remove the service cover
with a socket spanner of 32 mm, like indicated in the figure
below.

Descaling

Depending on the water quality and set temperature, scale
candeposit on the heat exchanger inside the domestic hot water tank
and can restrict heat transfer. For this reason, descaling of the heat
exchanger may be required at certain intervals.

Draining

Follow the next steps to drain the domestic hot water tank:

1

Switch off the power supply.

2

Turn off the cold water supply valve.

3

Open the hot water taps.

4

Open the drain valve.

T

ROUBLESHOOTING

This section provides useful information for diagnosing and
correcting certain troubles which may occur in the unit.

General guidelines

Before starting the troubleshooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.

When a safety device was activated, stop the unit and find out why
the safety device was activated before resetting it. Under no
circumstances safety devices may be bridged or changed to a value
other than the factory setting. If the cause of the problem cannot be
found, call your local dealer.

General symptoms

Symptom 1: No water flow from hot taps

Symptom 2: Water from hot taps is cold

Symptom 3: Intermittent water discharge

D

ISPOSAL

 

REQUIREMENTS

Dismantling of the unit and treatment of parts must be done in
accordance with relevant local and national legislation.

1

Front decoration panels

2

Insulation piece

3

Service cover

When using means for descaling, it must be ensured that
the water quality remains compliant with the requirements
of EU directive 98/83/EC.

1 2

3

2x

2x

2x

When carrying out an inspection on the supply panel or on
the switch box of the unit, always make sure that the circuit
breaker of the unit is switched off.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The main water supply is off.

Check that all shut off valves of the 
water circuit are completely open.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The thermal cut-out located in the 
indoor unit has operated

• Check and find the cause of tripping 

and then reset button.

• Check if thermistor is correctly 

installed in thermistor socket.

Procedure: remove front panel and 
insulation, replace or fix the sensor.

The indoor unit (EKHBRD) is not 
operating.

Check the indoor unit operation. 
Refer to the manual delivered with 
the indoor unit.
If any faults are suspected, contact 
your local dealer.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Thermal control failure (water will be 
hot).

Contact your local dealer.

The expansion vessel is broken.

Replace the expansion vessel.

Summary of Contents for EKHTS200A

Page 1: ...INSTALLATION MANUAL EKHTS200A EKHTS260A EKHTSP200AA EKHTSP260AA EKHTSU200AA EKHTSU260AA EKUHWHTA Domestic hot water tank for air to water heat pump system ...

Page 2: ... 5x 1x 1x 1x 1 3 6 7 5 2 4 1x 340 mm 11 10 12 12 13 2 1 5 4 6 8 3 9 1 2 7 772 902 1032 H 120 Ø 6 0 1156 778 653 694 443 600 300 5 B C 250 250 A 600 30 D 30 2x 8 9 6 1 2 1 2 5 9 3 5 9 3 7 6 10 10 4 10 4 KHBRD 2 1 3 4 ...

Page 3: ... identification ACCESSORIES Accessories supplied with the domestic hot water tank See figure 1 Optional equipment EKFMAHTA Connection kit for installation of the domestic hot water tank on the floor next to the indoor unit Refer to the installation manual of the kit for more details EKHTS200A EKHTSP200AA EKHTS260A EKHTSP260AA Domestic hot water tank for air to water heat pump system Installation m...

Page 4: ...ve connection D Pressure relief valve field supply E Recirculation connection G 1 2 Male F Thermistor socket G Flow inlet connection from the main EKHBRD indoor unit at the bottom of the tank quick coupling H Heat exchanger coil J Return outlet connection to the main EKHBRD indoor unit at the bottom of the tank quick coupling K Cold water in connection G 3 4 Female L Thermistor A H K G J F E M Q P...

Page 5: ...op plate of the indoor unit To take away the front decoration panel remove the 2 bottom screws and then unhitch the panel Mount the top plate of the indoor unit on the domestic hot water tank module 4 Connect the 3 way valve 1 Remove drain plate on top of the indoor unit before installing the 3 way valve 2 Installation position The 3 way valve must be installed in the indoor unit Installation shal...

Page 6: ...s action so as to maintain the valve position as set during step 4 7 Put the turn knob on the valve motor cover as shown below Make sure that the turn knob is completely pushed in to allow the turn knob being operated automatically by the unit If the turn knob is lifted slightly manual operation is possible 8 Make sure to firmly fix the power supply cord onto the 3 way valve body with a field supp...

Page 7: ...oo see figure 4 7 Fix the side bottom decoration panels of the domestic hot water tank to the indoor unit 8 Connect the pressure relief valve field supply opening pressure maximum 10 bar and drain 9 Connect the thermistor wire to the indoor unit switch box Make sure power supply is switched off Refer to the wiring diagram delivered with the indoor unit The distance between the thermistor cable and...

Page 8: ...ng the hot water tank by the side of the indoor unit Refer to the manual delivered with the kit EKFMAHTA MAINTENANCE In order to ensure optimal availability of the unit a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals The described checks must be executed at least once a year by qualified personnel 1 Domestic hot water tank pressure re...

Page 9: ...devices may be bridged or changed to a value other than the factory setting If the cause of the problem cannot be found call your local dealer General symptoms Symptom 1 No water flow from hot taps Symptom 2 Water from hot taps is cold Symptom 3 Intermittent water discharge DISPOSAL REQUIREMENTS Dismantling of the unit and treatment of parts must be done in accordance with relevant local and natio...

Page 10: ...00 x 695 1610 x 600 x 695 Connections Quick coupling G 3 4 F Quick coupling G 3 4 F Quick coupling G 3 4 F Quick coupling G 3 4 F Inspection opening G1 2 M Recirculation connection G1 2 M Recirculation connection Ø125 mm Inspection and cleaning Ø125 mm Inspection and cleaning Weight empty 70 78 75 83 Mounting On top of EKHBRD or floor mounted On top of EKHBRD or floor mounted On top of EKHBRD or f...

Page 11: ...NOTES NOTES ...

Page 12: ...4PW53247 1B Copyright Daikin ...

Reviews: