EKHBH/XE008BA

Indoor unit for air to water heat pump system and options

4PW56302-1

Operation manual

14

6

Repeat step 2 through 4 to change other field settings as
required.

7

When finished, press the 

z

 button to exit FIELD SET MODE.

Detailed description

[0] User permission level

If required, certain user interface buttons can be made unavailable for
the user.

Three permission levels are defined (see the table below). Switching
between level 1 and level 2/3 is done by simultaneously pressing
buttons 

pfi

  and 

pfj

  immediately followed by

simultaneously pressing buttons 

s

  and 

ba

, and keeping all 4

buttons pressed for at least 5 seconds (in normal mode). Note that no
indication on the user interface is given. When level 2/3 is selected,
the actual permission level – either level 2 or level 3 – is determined
by the field setting [0-00].

[1] Weather dependent set point (heating operation only)

The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: colder outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C.

[1-00] Low ambient temperature (Lo_A): low outdoor
temperature.

[1-01] High ambient temperature (Hi_A): high outdoor
temperature.

[1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A). 
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is
required.

[1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A). 
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.

[2] Disinfection function

Applies only to installations with a domestic hot water tank.

The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.

[2-00] Operation interval: day(s) of the week at which the
domestic hot water should be heated.

[2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).

[2-02] Start time: time of the day at which the domestic hot
water should be heated.

[2-03] Set point: high water temperature to be reached.

[2-04] Interval: time period defining how long the set point
temperature should be maintained.

NOTE

Changes made to a specific field setting are only
stored when the 

pr

 button is pressed. Navigating to a

new field setting code or pressing the 

z

  button will

discard the change made.

Before shipping, the set values have been set as
shown under 

"Field settings table" on page 16

.

When exiting FIELD SET MODE, "

88

" may be

displayed on the user interface LCD while the unit
initialises itself.

Only relevant field settings are explained.

Button

Permission level

1

2

3

Quiet mode button 

s

operable

Weather dependent 
set point button

ba

operable

Schedule timer 
enable/disable button 

pr

operable

operable

Programming button 

<

operable

Time adjust buttons

pf

i

pf

j

operable

Inspection/test 
operation button 

z

operable

T

t

Target water temperature

T

A

Ambient (outdoor) temperature

= Shift value

CAUTION

The disinfection function field settings must be configured
by the installer according to local and national regulations.

T

DHW

Domestic hot water temperature

T

U

User set point temperature (as set on the user interface)

T

H

High set point temperature [2-03]

t

Time

WARNING

Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.

If this high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rise above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to local and national regulations.

Lo_Ti

Lo_A

Hi_A

T

A

T

t

+ 05

00

– 05

Hi_Ti

Shift value

00.00

22.00

24.00

01.00

23.00

t

T

DHW

T

H

T

U

[2-02]

[2-03]

[2-04]

Summary of Contents for EKHBHE008BA3V3

Page 1: ...OPERATION MANUAL EKHBHE008BA3V3 EKHBXE008BA3V3 Indoor unit for air to water heat pump system and options For installation WITH restricted power supply condition 6 kW ...

Page 2: ...timer by means of the controller maintain the unit and solve operational problems General information Thank you for purchasing this indoor unit The unit is the indoor part of the air to water ERHQ or ERLQ heat pumps These units are designed for wall mounted indoor installation The units can be combined with Daikin fan coil units floor heating applications low temperature radiators Daikin domestic ...

Page 3: ...and will stop the outdoor unit and the indoor circulation pump when the room temperature is above the thermostat set point Next recommendations only apply to installations with an optional domestic hot water tank Make sure the domestic hot water is only heated up to the domestic hot water temperature you require Start with a low domestic hot water temperature set point e g 45 C and only increase i...

Page 4: ... unit If during backup heater operation the heating load is higher than the heater capacity the water temperature can not increase In this case refer to Re start at low outdoor ambient temperatures in the installation manual Balance between space heating cooling demand and domestic hot water demand Only if the unit is correctly sized then at some point during space cooling heating operation the un...

Page 5: ...rogramming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addre...

Page 6: ...roller is set in permission level 2 or 3 refer to Field settings on page 13 the quiet mode button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enables the user to schedule operations Setting the clock and day of the week is required to be able to use the schedule timer ...

Page 7: ...oid overheating space heating is not operable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 13 Temperature range for cooling 5 C to 22 C 3 Switch on the unit by pushing the y button The operation LED 0 lights up The space cooling temperature set point can only be set manually refer to Manual operation on pag...

Page 8: ...r disabled p icon not displayed by pressing the pr button To set up the SCHEDULE TIMER refer to chapter Programming and consulting the schedule timer on page 8 What can the schedule timer do The schedule timer allows the programming of 1 Space heating and space cooling refer to Programming space heating or space cooling on page 9 Switch on the desired mode at a scheduled time in combination with a...

Page 9: ...with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the predefined default cooling set point Conversely when programming cooling actions time and set point heating actions are added automatically at the same time but with ...

Page 10: ...n to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the hig...

Page 11: ...s Consulting space heating or space cooling is carried out as follows 1 Use the button to select the operation mode cooling or heating you want to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the butto...

Page 12: ... 3 are stored but 4 and 5 are deleted Deleting a mode 1 Press the button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to delete quiet mode s booster heating m or domestic water heating w The selected mode is blinking 3 Press the and ba button simultaneously for 5 seconds to delete the selected mode Deleting a day of the week cooling or heating mode 1 Use the ...

Page 13: ...ton to select action number 2 11 Use the pi and pj buttons to set the action time to 4 00 12 Use the ba buttons to select what the unit should do from 4 00 onwards 9 set the tempearature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 13 Press the button for 5 seconds to store the programmed actions You automatically return to step 4 By pressing...

Page 14: ...d domestic hot water schedule timers are used make sure they are enabled during the period that space heating cooling is disabled Example pattern 0 0 0 0 0 0 0 00 0 0 0 1 1 1 1 0 0 0 00 0 0 0 2 2 2 2 0 0 0 00 0 0 0 3 3 3 3 0 0 0 00 0 0 0 4 4 4 4 0 0 0 00 0 0 0 5 5 5 5 0 0 0 00 0 0 0 6 6 6 6 0 0 0 00 0 0 0 7 7 7 7 0 0 0 00 0 0 0 2 2 2 23 3 3 3 5 5 5 59 9 9 9 Space heating cooling Domestic water hea...

Page 15: ...mestic hot water tank The disinfection function disinfects the domestic hot water tank by periodically heating the domestic hot water to a specific temperature 2 00 Operation interval day s of the week at which the domestic hot water should be heated 2 01 Status defines whether the disinfection function is turned on 1 or off 0 2 02 Start time time of the day at which the domestic hot water should ...

Page 16: ... information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identification example 11 E 03 Readout of the liquid refrigerant temperature E 04 Readout of the inlet water temperature Space heating cooling always has priority over the disinfection function The disinfection function is only possible when the unit is ...

Page 17: ...o restart 00 Status 0 ON 0 1 4 Space heating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 25 14 25 1 C 03 Installation related setting 04 Installation related setting 5 Installation related settings 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Installation related setting 04 In...

Page 18: ...I O PCB 00 Solar priority mode setting 0 0 1 1 01 Installation related setting 02 Installation related setting 03 Installation related setting 04 Installation related setting D Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Local shift value weather dependent 0 0 1 2 3 4 E Unit information readout 00 Software v...

Page 19: ...gerant of oil and other parts must be done by a qualified installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative consequences for the environment and human health Please contact the installer or loca...

Page 20: ...NOTES NOTES ...

Page 21: ......

Page 22: ...4PW56302 1 Copyright Daikin ...

Reviews: