ROUBLESHOOTING

To  set up the system and make trouble shooting possible, it is
required to connect the remote controller to the option kit.

Not a malfunction of the air conditioner

The system does not operate

The system does not restart immediately after the cooling is
requested.
If the operation lamp lights, the system is in normal operating
condition.
It does not restart immediately because one of its safety devices
actuates to prevent the system from being overloaded. The
system will turn on again automatically after 3 minutes.

The system does not restart immediately after the power supply
is turned on.
Wait 1 minute until the micro computer is prepared for operation.

Trouble shooting

If one of the following malfunctions occurs, take the measures shown
below and contact your dealer.

The system must be repaired by a qualified service person.

If a safety device such as a fuse, a breaker, or an earth leakage
breaker frequently actuates, or ON/OFF switch does not
properly work.
Turn off the main power switch.

If the display 

, the unit number and the operation lamp

flash and the malfunction code appears;
Notify your dealer and report the malfunction code.

If the system does not operate properly, and none of the above
mentioned malfunctions is evident, investigate the system according
to the following procedures.

If the system does not operate at all

Check if there is a power failure.
Wait until power is restored. If power failure occurs during
operation, the system automatically restarts immediately after
the power supply recovers.

Check if the fuse has blown or breaker has been tripped.
Change the fuse or set the breaker.

If the system stops operating after operation is complete

Check if the air inlet or outlet of outdoor or evaporator (air
handling unit) is blocked by obstacles.
Remove the obstacle and make it well-ventilated.

Check if the air filter is clogged.
Ask a qualified service person to clean the air filter.

The error signal is given and the system stops.
If the error resets after 5-10 minutes, the unit safety device was
activated but the unit restarted after evaluation time.
If the error persists, contact your dealer.

If the system operates but it does not sufficiently cool

Check if the air inlet or outlet of the evaporator (air handling unit)
or the outdoor unit is blocked with obstacles.
Remove the obstacle and make it well-ventilated.

Check if the air filter is clogged.
Ask a qualified service person to clean the air filter.

Check if the doors or the windows are open.
Shut doors or windows to prevent wind from coming in.

Check if direct sunlight enters the room.
Use curtains or blinds.

Check if there are too many inhabitants in the room.
Cooling effect decreases if heat gain of the room is too large.

Check if the heat source of the room is excessive.
Cooling effect decreases if heat gain of the room is too large.

The evaporator (air handling unit) is freezing up

The liquid thermistor (R2T) is not put on the coldest position and
part of the evaporator is freezing up.
Thermistor must be put on the coldest position.

The thermistor has come loose.
The thermistor must be fixed.

The evaporator fan is not operating continuously.
When the outdoor unit stops operating, the evaporator fan must
continue operation to melt the ice that was accumulated during
outdoor unit operation.
Ensure that the evaporator fan keeps operating.

In these cases, contact your dealer.

M

AINTENANCE

D

ISPOSAL

 

REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.

Only a qualified service person is allowed to perform
maintenance.

Before obtaining access to terminal devices, all power
supply circuits must be interrupted.

Water or detergent may deteriorate the insulation of
electronic components and result in burn-out of these
components.

Summary of Contents for EKEXMCBV3

Page 1: ...INSTALLATION AND OPERATION MANUAL EKEXMCBV3 Option kit for combination of Daikin condensing units with field supplied evaporators ...

Page 2: ...Y4 Y3 Y2 Y1 Y6 Y5 Y4 Y3 Y2 Y1 expansion valve gas liquid N L R2T R1T air R5 R6 P1 P2 remocon outdoor F2 F1 F1 F2 T1 T2 ON OFF H1 H2 H3 H4 H6 H5 H8 H7 3 4 1 2 6 H1 H3 H5 H5 H4 H2 H7 H6 H8 X24A 6 7 10 3 2 11 5 1 4 9 8 5 3 NOTES 1 2 3 ...

Page 3: ...tępujących norm i innych dokumentów normalizacyjnych pod warunkiem że używane są zgodnie z naszymi instrukcjami 18 sunt în conformitate cu următorul următoarele standard e sau alt e document e normativ e cu condiţia ca acestea să fie utilizate în conformitate cu instrucţiunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili 2...

Page 4: ...system to DIII net devices This could result in malfunction or breakdown of the total system INSTALLATION For installation of the air handling unit refer to the air handling unit installation manual Never operate the air conditioner with the discharge pipe thermistor R3T suction pipe thermistor R2T and pressure sensors S1NPH S1NPL removed Such operation may burn out the compressor ACCESSORIES Obli...

Page 5: ...mined by the outdoor unit EKEXMCB Remote controller 1 Parts and components 1 Outdoor unit 2 Control box 3 Air handling unit field supply 4 Field piping field supply 5 Expansion valve kit Wiring connections 6 Outdoor unit power supply 7 Control box wiring Power supply and communication between control box and outdoor unit 8 Evaporator thermistors 9 Power supply and control wiring for evaporator air...

Page 6: ...ere the air contains high levels of salt such as air near the ocean Where sulphurous gas is present such as that in areas of hot spring In vehicles or vessels Where voltage fluctuates a lot such as that in factories Where high concentration of vapor or spray are present Where machines generating electromagnetic waves are present Where acidic or alkaline vapor is present The option boxes must be in...

Page 7: ...replacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so that it can be felt on the skin For detai...

Page 8: ...al installation 1 Fix the control box with its hanger brackets to the mounting surface Use 4 screws for holes of Ø6 mm 2 Open the lid of the control box 3 For electrical wiring refer to paragraph Electric wiring work on page 5 4 Install the screw nuts 5 Close the unnecessary openings with stoppers closing cups 6 Close the lid securely after installation to ensure that the control box is watertight...

Page 9: ...th leakage breaker R1T Thermistor air R2T Thermistor liquid R3T Thermistor gas T1R Transformer 220 V 21 8 V X1M X3M Terminal block Y1E Electronic expansion valve X1M R1 R2 Thermistor liquid X1M R3 R4 Thermistor gas X1M R5 R6 Thermistor air X1M Y1 6 Expansion valve X1M P1 P2 Communication remote controller X1M T1 T2 Input ON OFF X1M F1 F2 Communication line Field wiring L Live N Neutral Connector W...

Page 10: ...rmistor cable or loosening of the thermistor may result in bad contact and incorrect temperature measurement Fixation of the thermistor 1 Fix the thermistor with insulating aluminum tape field supply in order to ensure a good heat transference 2 Put the supplied piece of rubber around the thermistor R2T R3T in order to avoid loosening of the thermistor after some years 3 Fasten the thermistor with...

Page 11: ...nd the remote controller Operation setting in case of power failure OPERATION AND DISPLAY SIGNALS The connection must be made on an accessible location To make the connection waterproof the connection can also be made in a switch box or connector box The thermistor cable should be located at least 50 mm away from power supply wire Not following this guideline may result in malfunction due to elect...

Page 12: ...ir handling unit is blocked by obstacles Remove the obstacle and make it well ventilated Check if the air filter is clogged Ask a qualified service person to clean the air filter The error signal is given and the system stops If the error resets after 5 10 minutes the unit safety device was activated but the unit restarted after evaluation time If the error persists contact your dealer If the syst...

Page 13: ...NOTES NOTES ...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW32096 1 ...

Reviews: