Operation manual
19
EKCBX/H008BBV3
Unit for air to water heat pump system
4PW67442-1A – 12.2010
8
Installation related setting
00
Installation related setting
01
Installation related setting
02
Installation related setting
03
Installation related setting
04
Installation related setting
9
Heating and cooling set point ranges
00
Heating set point upper limit
55
37~55
1
°C
01
Heating set point lower limit
25
15~37
1
°C
02
Cooling set point upper limit
22
18~22
1
°C
03
Cooling set point lower limit
5
5~18
1
°C
04
Installation related setting
Automatic set back function
05
Set back operation
0 (OFF)
0/1
1
—
06
Set back operation start time
23:00
0:00~23:00
1:00
hour
07
Set back operation stop time
5:00
0:00~23:00
1:00
hour
08
Leaving water set back value
2
0~10
1
°C
C
Solar kit
00
Solar priority mode setting
0
0/1
1
—
01
Installation related setting
02
Installation related setting
03
Installation related setting
04
Installation related setting
05
Not applicable. Do not change the default setting.
—
—
—
—
d
Local shift value weather dependent
00
Installation related setting
01
Installation related setting
02
Installation related setting
03
Local shift value weather dependent
0 (OFF)
0/1/2/3/4
1
—
04
Not applicable. Do not change the default value.
—
—
—
—
05
Installation related setting
06
Not applicable. Do not change the default value.
—
—
—
—
E
Unit information readout
00
Software version
Read only
—
—
—
01
EEPROM version
Read only
—
—
—
02
Unit model identification.
depending
on model
—
—
—
03
Liquid refrigerant temperature
Read only
—
1
°C
04
Inlet water temperature
Read only
—
1
°C
F
Installation related setting
00
Installation related setting
01
Installation related setting
02
Installation related setting
03
Installation related setting
04
Installation related setting
Installation related setting
05
Installation related setting
06
Installation related setting
07
Installation related setting
08
Installation related setting
09
Installation related setting
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value