Operation manual
13
EKCBX/H008BBV3
Unit for air to water heat pump system
4PW67442-1A – 12.2010
5.
F
IELD
SETTINGS
The indoor unit shall be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user demand. However, the field settings mentioned in
can be modified to customer preferences. Thereto,
a number of so called field settings are available. These field settings
are accessible and programmable through the user interface on the
indoor unit.
Each field setting is assigned a 3-digit number or code, for example
[1-03], which is indicated on the user interface display. The first digit
[1] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under
. In this same list, we provided for 2
columns to register the date and value of altered field settings at
variance with the default value.
A detailed description of each field setting is given under
5.1.
Procedure
To change one or more field settings, proceed as follows.
1
Press the
z
button for a minimum of 5 seconds to enter FIELD
SET MODE.
The
$
icon (3) will be displayed. The current selected field
setting code is indicated
;
(2), with the set value displayed to
the right
-
(1).
2
Press the
bgi
button to select the appropriate field setting
first code.
3
Press the
bgj
button to select the appropriate field setting
second code.
4
Press the
pfi
button and
pfj
button to change
the set value of the select field setting.
5
Save the new value by pressing the
pr
button.
6
Repeat step 2 through 4 to change other field settings as
required.
7
When finished, press the
z
button to exit FIELD SET MODE.
NOTICE
The default values mentioned in
are the values from factory. The actual initial
values shall be selected according to your application.
These values shall be confirmed by your installer.
CAUTION
■
The field settings [2] depends on the applicable
legislation.
■
The field settings [9] depends on the application.
■
Before changing these settings, the new values shall
be confirmed by the installer and/or shall be according
to the applicable legislation.
NOTICE
Changes made to a specific field setting are only stored
when the
pr
button is pressed. Navigating to a new field
setting code or pressing the
z
button will discard the
change made.
INFORMATION
■
Before shipping, the set values have been set as
shown under
"Field settings table" on page 18
■
When exiting FIELD SET MODE, "
88
" may be
displayed on the user interface LCD while the unit
initialises itself.