Daikin EKCBX008BBV3 Operation Manual Download Page 14

Operation manual

13

EKCBX/H008BBV3

Unit for air to water heat pump system

4PW67442-1A – 12.2010

5.

F

IELD

 

SETTINGS

The indoor unit shall be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user demand. However, the field settings mentioned in 

"Field settings

table" on page 18

 can be modified to customer preferences. Thereto,

a number of so called field settings are available. These field settings
are accessible and programmable through the user interface on the
indoor unit.

Each field setting is assigned a 3-digit number or code, for example
[1-03], which is indicated on the user interface display. The first digit
[1] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.

A list of all field settings and default values is given under 

"Field

settings table" on page 18

. In this same list, we provided for 2

columns to register the date and value of altered field settings at
variance with the default value.

A detailed description of each field setting is given under 

"Detailed

description" on page 14

.

5.1.

Procedure

To change one or more field settings, proceed as follows.

1

Press the 

z

 button for a minimum of 5 seconds to enter FIELD

SET MODE.
The 

$

 icon (3) will be displayed. The current selected field

setting code is indicated 

;

 (2), with the set value displayed to

the right 

-

 (1).

2

Press the 

bgi

 button to select the appropriate field setting

first code.

3

Press the 

bgj

 button to select the appropriate field setting

second code.

4

Press the 

pfi

 button and 

pfj

 button to change

the set value of the select field setting.

5

Save the new value by pressing the 

pr

 button.

6

Repeat step 2 through 4 to change other field settings as
required.

7

When finished, press the 

z

 button to exit FIELD SET MODE.

NOTICE

The default values mentioned in 

"Field settings table" on

page 18

 are the values from factory. The actual initial

values shall be selected according to your application.
These values shall be confirmed by your installer.

CAUTION

The field settings [2] depends on the applicable
legislation.

The field settings [9] depends on the application.

Before changing these settings, the new values shall
be confirmed by the installer and/or shall be according
to the applicable legislation.

NOTICE

Changes made to a specific field setting are only stored
when the 

pr

 button is pressed. Navigating to a new field

setting code or pressing the 

z

 button will discard the

change made.

INFORMATION

Before shipping, the set values have been set as
shown under 

"Field settings table" on page 18

.

When exiting FIELD SET MODE, "

88

" may be

displayed on the user interface LCD while the unit
initialises itself.

2

3

1

Summary of Contents for EKCBX008BBV3

Page 1: ...OPERATION MANUAL EKCBX008BBV3 EKCBH008BBV3 Unit for air to water heat pump system...

Page 2: ...manual speci ed for a certain product or application explaining how to install con gure and maintain it Operation manual Instruction manual speci ed for a certain product or application explaining how...

Page 3: ...er Refer to the operation manual of the indoor unit and to the installation manual of the digital I O PCB for more information Refer to the wiring diagram or connection diagram for connecting this PCB...

Page 4: ...tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open ame or any electrical applia...

Page 5: ...9 OFF ICON x This icon indicates that the OFF action is selected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installatio...

Page 6: ...ing the clock 33 DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS wbi and wbj These buttons are used to adjust the current set point of the domestic hot water temperature only for 4 03 0 1 2 or 3 These b...

Page 7: ...unit will immediately heat up the domestic water tank untill domestic hot water storage set point upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a sc...

Page 8: ...isappears from the display Selecting powerful domestic water heating operation 1 Press v for 5 seconds to activate powerful domestic water heating operation Icons w and m start ashing Powerful domesti...

Page 9: ...t water temperature INFORMATION Only use the pr button to enable or disable the schedule timer The schedule timer overrules the y button The y button only overrules the schedule timer until the next p...

Page 10: ...e schedule timer remind Familiarise yourself with the icons and the buttons You will need them when programming Refer to Name and function of buttons and icons on page 4 Fill out the form at the very...

Page 11: ...8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the temperature by me...

Page 12: ...on time 8 Use the ba button to select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation Fo...

Page 13: ...e next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press the button The actual mode is blinking 2 Use the pi and pj buttons to selec...

Page 14: ...D SET MODE The icon 3 will be displayed The current selected eld setting code is indicated 2 with the set value displayed to the right 1 2 Press the bgi button to select the appropriate eld setting rs...

Page 15: ...rature Lo_A Note that the Lo_Ti value should be higher than Hi_Ti as for low outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing...

Page 16: ...g Scheduled domestic hot water storage The storage set point can be accessed directly using the wi and wj buttons 6 03 Scheduled storage de nes whether the scheduled domestic water heating storage dur...

Page 17: ...omestic hot water user interface set point 9 Heating and cooling set point ranges The purpose of this eld setting is to prevent the user from selecting a wrong i e too hot or too cold leaving water te...

Page 18: ...d settings of the weather dependent set point 1 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model...

Page 19: ...eating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 25 14 25 1 C 03 Installation related setting 04 Not applicable Do not change the...

Page 20: ...lated setting 05 Not applicable Do not change the default setting d Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting...

Page 21: ...li ed installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is dispo...

Page 22: ...NOTES NOTES...

Page 23: ......

Page 24: ...Copyright 2010 Daikin 4PW67442 1A 12 2010...

Reviews: