Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.2.2.6.3
[C-09]
Digital I/O PCB
Alarm output
R/W
0: Normally open
1: Normally closed
A.2.2.6.4
[F-04]
Digital I/O PCB
Bottom plate heater
R/W
0: No
1: Yes
A.2.2.7
[D-04]
R/W
0: No
1: Pwr consmp ctrl
A.2.2.8
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.2.2.9
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.2.2.A
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
3: Circul. Pump
4: CP & disinf. Sh
A.2.2.B
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
└─
Capacities
A.2.3.1
[6-02]
R/W
0~10 kW, step: 0,2 kW
2,4 kW
A.2.3.2
[6-03]
R/W
0~10 kW, step: 0,2 kW
3 kW
A.2.3.3
[6-04]
R/W
0~10 kW, step: 0,2 kW
3 kW
A.2.3.6
[6-07]
R/W
0~200W, step: 10W
0W
Space operation
└─
LWT settings
└──────────────────
Main
A.3.1.1.1
R/W
0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
A.3.1.1.2.1
[9-01]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.1.2.2
[9-00]
Temperature range
Maximum temp (heating)
R/W
37~depending on outdoor unit, step: 1°C
55°C
A.3.1.1.5
[8-05]
R/W
0: No
1: Yes
A.3.1.1.6.1
[F-0B]
Shut-off valve
Thermo On/OFF
R/W
0: No
1: Yes
A.3.1.1.7
[9-0B]
R/W
0: Quick
1: Slow
└──────────────────
Additional
A.3.1.2.1
R/W
0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
A.3.1.2.2.1
[9-05]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.2.2.2
[9-06]
Temperature range
Maximum temp (heating)
R/W
37~depending on outdoor unit, step: 1°C
55°C
└──────────────────
Delta T source
A.3.1.3.1
[9-09]
R/W
3~10°C, step: 1°C
5°C
└─
Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
Minimum temp (heating)
R/W
12~18°C, step: A.3.2.4
12°C
A.3.2.1.2
[3-06]
Room temp. range
Maximum temp (heating)
R/W
18~30°C, step: A.3.2.4
30°C
A.3.2.2
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.3
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.4
R/W
0: 0,5 °C
1: 1 °C
└─
Operation range
14~35°C, step: 1°C
25°C (*1)
14~35°C, step: 1°C
35°C (*2)
└─
Domestic hot water (DHW)
└─
Type
A.4.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Disinfection
A.4.4.1
[2-01]
R/W
0: No
1: Yes
A.4.4.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.4.4.3
[2-02]
R/W
0~23 hour, step: 1 hour
23
A.4.4.4
[2-03]
R/O
60°C
A.4.4.5
[2-04]
R/W
40~60 min, step: 5 min
40 min
A.3.3.1
[4-02]
R/W
Duration
Demand PCB
External kWh meter 1
External kWh meter 2
DHW pump
External sensor
Booster heater
BUH: step 1
BUH: step 2
Bottom plate heater
LWT setpoint mode
Modulated LWT
Emitter type
LWT setpoint mode
Heating
Room temp. offset
Ext. room sensor offset
Room temp. step
Space heating OFF temp
Disinfection
Operation day
Start time
Temperature target
(*1) *04/08*_(*2) *11/16*