4/8
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
└─
Maximum setpoint
A.4.5
[6-0E]
R/W
40~65°C, step: 1°C
65°C
└─
SP mode
A.4.6
R/W
0: Fixed
1: Weather dep.
└─
Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
Leaving water value for high ambient temp. for
DHW WD curve.
R/W
35~[6-0E]°C, step: 1°C
55°C
A.4.7
[0-0C]
Weather-dependent curve
Leaving water value for low ambient temp. for
DHW WD curve.
R/W
45~[6-0E]°C, step: 1°C
65°C
A.4.7
[0-0D]
Weather-dependent curve
High ambient temp. for DHW WD curve.
R/W
10~25°C, step: 1°C
15°C
A.4.7
[0-0E]
Weather-dependent curve
Low ambient temp. for DHW WD curve.
R/W
-40~5°C, step: 1°C
-10°C
└─
Heat sources
└─
Backup heater
A.5.1.1
[4-00]
R/W
0~2
0: Disabled
1: Enabled
A.5.1.3
[4-07]
R/W
0: No
1: Yes
A.5.1.4
[5-01]
R/W
-15~35°C, step: 1°C
0°C
└─
System operation
└─
Auto restart
A.6.1
[3-00]
R/W
0: No
1: Yes
└─
Preferential kWh rate
A.6.2.1
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
A.6.2.2
[D-05]
R/W
0: Forced off
1: As normal
└─
Pwr consumpt. Control
A.6.3.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
A.6.3.2
[4-09]
R/W
0: Current
1: Power
A.6.3.3
[5-05]
R/W
0~50 A, step: 1 A
50 A
A.6.3.4
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.5.1
[5-05]
Amp. limits for DI
Limit DI1
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.2
[5-06]
Amp. limits for DI
Limit DI2
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.3
[5-07]
Amp. limits for DI
Limit DI3
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.4
[5-08]
Amp. limits for DI
Limit DI4
R/W
0~50 A, step: 1 A
50 A
A.6.3.6.1
[5-09]
kW limits for DI
Limit DI1
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2
[5-0A]
kW limits for DI
Limit DI2
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3
[5-0B]
kW limits for DI
Limit DI3
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4
[5-0C]
kW limits for DI
Limit DI4
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.7
[4-01]
R/W
0: None
1: BSH
2: BUH
└─
Averaging time
A.6.4
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─
Ext amb. sensor offset
A.6.5
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
└─
Boiler efficiency
A.6.A
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
└─
Emergency
A.6.C
R/W
0: Manual
1: Automatic
└─
Overview settings
A.8
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
A.8
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
45°C
A.8
[0-02]
R/W
10~25°C, step: 1°C
15°C
A.8
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
A.8
[0-04]
8
A.8
[0-05]
12
A.8
[0-06]
35
A.8
[0-07]
20
A.8
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55°C
A.8
[0-0C]
R/W
45~[6-0E]°C, step: 1°C
65°C
A.8
[0-0D]
R/W
10~25°C, step: 1°C
15°C
A.8
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
--
--
--
Operation mode
Enable BUH step 2
Equilibrium temp.
Allowed heaters
Forced pump OFF
Mode
Type
Amp. value
kW value
Priority
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
--
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
4P449983-1 - 2016.06
(*1) *04/08*_(*2) *11/16*