6 Troubleshooting

Operation manual

11

08S23DAV
Daikin Altherma – Low temperature split
4P499572-1 – 2017.06

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The  refrigerant  inside  the  unit  is  mildly  flammable,  but
normally does not leak. If the refrigerant leaks in the room
and comes in contact with fire from a burner, a heater, or a
cooker, this may result in fire, or the formation of a harmful
gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room,  and  contact  the  dealer  from  which  you  purchased
the unit.

Do not use the unit until a service person confirms that the
portion from which the refrigerant leaked is repaired.

5.2

To find the contact/helpdesk
number

1

Go to [8.3]: Information > Dealer information.

6

Troubleshooting

6.1

To display the help text in case of
a malfunction

In  case  of  a  malfunction,  the  following  will  appear  on  the  home
screen depending on the severity:

: Error

: Malfunction

You  can  get  a  short  and  a  long  description  of  the  malfunction  as
follows:

1

Press the left dial to open the main menu and go to
Malfunctioning.

Result: 

A short description of the error and the error

code is displayed on the screen.

2

Press   in the error screen.

Result: 

A long description of the error is displayed

on the screen.

6.2

Symptom: You are feeling too cold
(hot) in your living room

Possible cause

Corrective action

The desired room temperature is
too low (high).

Increase (decrease) the desired
room temperature.

If the problem recurs daily, do
one of the following:

▪ Increase  (decrease)  the  room

temperature preset value.

▪ Adjust  the  room  temperature

schedule.

The desired room temperature
cannot be reached.

Increase the desired leaving
water temperature in accordance
with the heat emitter type.

6.3

Symptom: The water at the tap is
too cold

Possible cause

Corrective action

You ran out of domestic hot
water because of unusual high
consumption.

If you immediately need domestic
hot water, activate the DHW tank
Powerful operation. However,
this consumes extra energy.

If you can wait, overrule
(increase) the active or next
scheduled desired temperature
so that more hot water will be
produced exceptionally.

If the problems recurs daily, do
one of the following:

▪ Increase 

the 

DHW 

tank

temperature preset value.

▪ Adjust 

the 

DHW 

tank

temperature 

schedule.

Example: 

Program 

to

additionally 

heat 

up 

the

DHW  tank  to  a  preset  value
(Eco  setpoint  =  lower  tank
temperature) during the day.

The desired DHW tank
temperature is too low.

6.4

Symptom: Heat pump failure

When the heat pump fails to operate, the optional backup heater and
anti-legionella heater can serve as an emergency heater and either
automatically or non-automatically take over the heat load.

▪ When auto emergency is set to Automatic and a heat pump failure

occurs, the optional backup heater will automatically take over the
heat  load,  and  the  anti-legionella  heater  will  automatically  take
over the domestic hot water production.

▪ When  auto  emergency  is  set  to  Manual  and  a  heat  pump  failure

occurs,  the  domestic  hot  water  and  space  heating  operation  will
stop  and  need  to  be  recovered  manually.  The  user  interface  will
then  ask  you  to  confirm  whether  the  optional  backup  heater  or
anti-legionella heater can take over the heat load or not.

When  the  heat  pump  fails, 

  or 

  will  appear  on  the  user

interface.

Possible cause

Corrective action

Heat pump is damaged.

See 

"6.1 To display the help text

in case of a malfunction" on
page 11

.

INFORMATION

When  the  backup  heater  or  anti-legionella  heater  takes
over  the  heat  load,  electricity  consumption  will  be
considerably higher.

7

Disposal

NOTICE

Do not try to dismantle the system yourself: the dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  must  comply  with  applicable  legislation.  Units  must
be  treated  at  a  specialised  treatment  facility  for  reuse,
recycling and recovery.

Summary of Contents for EHVH08S23DAG

Page 1: ...Operation manual Daikin Altherma Low temperature split English Operation manual Daikin Altherma Low temperature split EHVH04S23DAV G EHVH08S23DAV G...

Page 2: ...e installer to inform you about the settings that he used to configure your system Check if he has filled in the installer settings tables If not request him to do so Keep the documentation for future...

Page 3: ...screen darkens Pressing any button or rotating any dial awakens the display The time of non interaction differs depending on the user permission level User or Advanced user 15 min Installer 1 h Dials...

Page 4: ...dditional zone h3 h1 h2 h1 Heat emitter type Underfloor heating Fancoil unit Radiator h2 Leaving water temperature setpoint h3 Room thermostat type External control Hidden Leaving water temperature co...

Page 5: ...ubmenu e Turn or press the left dial to go to the submenu 3 2 4 Detailed screen with values a b a Settings b Values Go through the list of settings Confirm changes and proceed Change the value Go to t...

Page 6: ...ge The amount of information you can read out in the menu structure depends on your user permission level User Standard mode Advanced user You can read out more information 3 5 1 To change the user pe...

Page 7: ...opy Edit Copy Result C is displayed next to the copied day 3 Select Tuesday Mon Sat Wed Fri Thu Tue Sun User defined 1 C 4 Select Paste Copy Paste C Result Mon Sat Wed Fri Thu Tue Sun User defined 1 C...

Page 8: ...on manual 8 EHVH04 08S23DAV Daikin Altherma Low temperature split 4P499572 1 2017 06 2 Select the Rename option Delete Rename 3 Browse through the character list and confirm the selected character 4 C...

Page 9: ...file 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule 7 5 Electricity price High Medium Low Schedule 7 2 Time date Hours Minutes AM PM Year Month Day Daylight savings time Format 8 Infor...

Page 10: ...ode Tips about DHW tank temperature Use a weekly schedule for your normal domestic hot water needs only in scheduled mode Program to heat up the DHW tank to a preset value Storage comfort higher DHW t...

Page 11: ...r type 6 3 Symptom The water at the tap is too cold Possible cause Corrective action You ran out of domestic hot water because of unusual high consumption If you immediately need domestic hot water ac...

Page 12: ...3DAV Daikin Altherma Low temperature split 4P499572 1 2017 06 8 Glossary DHW Domestic hot water Hot water used in any type of building for domestic purposes LWT Leaving water temperature Water tempera...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...4P499572 1 2017 06 Copyright 2017 Daikin 4P499572 1 0000000Y...

Reviews: