6 Parameter settings
6.1 Explanation of the parameter tables
The parameter tables listed in the sections 6.2 to 6.11 contain im-
portant information concerning all parameters that are available
in the individual rotary switch setting on the controller (1st menu
level, 2nd menu level).
In addition to the parameter designations, the tables contain de-
tails for the setting ranges, factory settings, setting options or
setting step distances and brief function explanations.
In addition, they provide explanation of the access rights for the
operation of the controller. The following abbreviations are
available for appropriate catheterisation:
Status:
6.2 Rotary switch setting: Configuration
6.2.1 Level "Setup"
6.2.2 Level "System Configuration"
BE
Access right for the operator
HF
Access permission with Technician password
N
Not visible
E
Visible and configurable
S
Visible
Sub-
le
vel
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Language
Language of the display text in the operating panel
E
E
German
English
French
Dutch
Italian
Spanish
Portuguese
German
1
Date
Current date in format Day / Month / Year. The current day of the week is calculated au-
tomatically from the date.
E
E
Time
Time in format Hours / Minutes.
E
E
Keylock Function
Release of the keylock function:
Off: Button block cannot be activated.
On: The button block can be activated using the rotary switch (see chapter 3.3).
E
E
Off
On
Off
-
Access Rights
Entering access code. Setting character by character like a combination lock (see
chapter 3.6.1).
E
E
0 - 9
0000
1
Tab. 6-1 Parameter in rotary switch setting "Configuration" level "Setup"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Equilibrium Temp
Only if the parameter [Equilibrium Func.] = On is in delivery status is this function activated. It
can only be changed with a technician code. Contact your specialist heating technician in this
regard:
Outdoor temperature from which the optional ancillary heating is activated for supporting the
room heating. The bivalent temperature is relevant for operation of the optional ancillary heater
based on a backup demand (room heating operation). The temperature of the sensor integrat-
ed into the external unit for heat pump (info value TA2) is used.
The displayed info value TA2 may deviate from the value in the standard display.
E
E
-15°C to +35°C
0 °C
1 °C
Quite Mode
Mode for low-noise operation with reduced output (see section: 3.4.10).
0: Deactivated
1: Activated
2: Operated in whisper mode only at night between 22:00 and 6:00 hours.
E
E
0 - 2
0
-
Tab. 6-2 Parameter in rotary switch setting "Configuration" level "System Configuration"
Depending on the version of the device software certain
information parameters for the device, not described in
tab. 6-2, can be displayed at this level. For this see
tab. 6-12.