Proper air distribution is vital to coil performance. Airflow 
anywhere on the coil face should not vary by more than 
20%.

2

The drain pan and associated piping (drain line and trap) 
should be installed so that there is no standing water in the 
drain pan and that no blow-through occurs.

3

Air velocities should be maintained between 200-550 feet 
per minute.

Maintenance

General

1

Filters should be inspected on a regular basis and changed 
as needed. Maintaining clean filters is a cost effective way 
to help maintain maximum coil performance and service 
life.

2

Periodic inspection of the coil for signs of corrosion and/or 
leaks is recommended. Repair and replacement of the coil 
and the connecting piping, valves, etc., should be 
performed as needed by a qualified individual(s).

3

Should the coil surface need cleaning, caution should be 
exercised in selecting the cleaning solution as well as the 
cleaning equipment. Improper selection can result in 
damage to the coil and/or health hazards. 

4

Suggested cleaning instructions:

a

When handling strong chemicals, be sure to wear 
chemical impervious gloves, apron, and splash goggles.

b

Acti-Brite (AB-1) is the recommended cleaning 
solution. Contact your local 

Daikin

 Parts Distributor.

c

Determine required dilution for the specific application. 
It is recommended to start with a dilution ratio of 10:1 
and increase concentration until the desired results are 
achieved.

d

As with mixing all acids, place the desired amount of 
water into the tank and then add the chemicals.

e

Turn off fans and allow hot coils to cool before 
applying.

f

Using plain water, wet both the coil as well as the area 
surrounding the equipment. Wetting the coil with water 
aids in product penetration and performance.

g

Apply properly diluted product to coil surface. 
Whenever possible, apply solution from the outlet side 
of the coil. Allow solution to remain on surface, 
normally 5-10 minutes. Do not allow solution to dry on 
the coil. 

Note: 

In extreme cases, application may have to be 

repeated to achieve desired results.

h

If foaming does not occur, check for extreme grease 
buildup which will slow cleaning process. Foaming may 
not occur if coil is coated or painted.

i

Rinse coils, tools, and surrounding area thoroughly after 
the coil cleaning.

5

Clean the coil from the leaving airside so that foreign 
material will be washed out of the coil rather than pushed 
further in. 

6

Periodic inspection of the coil for signs of corrosion and for 
leaks is recommended. Small leaks can be detected using a 
Halide torch. Repair and replacement of the coil and the 
connecting piping, valves, etc., should be performed as 
needed by a qualified individual.

7

The use of filter-dryers in the system piping is 
recommended along with a sight glass that has a moisture 
indicator. Replace the filter dryer(s) as needed.

Note: 

Refrigerant conversions are beyond the scope of this 

manual and should only be performed by qualified 
parties.

DANGER

Follow the manufacturer’s guidelines for lockout/tagout and 
disconnect all power to the unit before performing maintenance. 
Contact with high voltage power will cause electrical shock, 
resulting in severe personal injury or death.

WARNING

Moving parts, high pressure, and/or high temperature fluids can 
cause serious personal injury.

CAUTION

Carefully read and follow the manufacturer's recommendations 
before using any cleaning fluid.

Summary of Contents for EF series

Page 1: ... 2008 Daikin Applied Installation and Maintenance Manual IM 902 Daikin Direct Expansion DX Cooling Coils Types EN EF ER EJ EK Group Applied Air Part Number IM 902 Date February 2008 ...

Page 2: ...d Identification Information 3 Receiving Instructions 3 Coil Types 3 Model EN 3 Model EF 3 Model ER 3 Model EJ 3 Model EK 3 Nomenclature 4 Installation 5 Mounting 5 Installation 5 Operation and Maintenance 7 Operation 7 General 7 Maintenance 7 General 7 ...

Page 3: ...ired Model EN Figure 1 evaporators utilize dual suction connections when multiple distributors are used Model EF Face control model EF Figure 1 is another evaporator coil option offered Face control is the simplest form of capacity control These coils are normally furnished with two distributors and two suction connections offering 50 capacity reduction capabilities Model ER Daikin offers a row co...

Page 4: ...be O D Coil Type Circuiting 3 3 8 4 1 2 5 5 8 E Evaporator N Normal F Face Control R Row Control J Interlaced K Interlaced Face Control Finned Length inches Finned Height inches Rows Deep Fins Per Inch Fin Design A flat AI Cu B corrugated AI Cu C sine wave AI Cu F flat SS CS ...

Page 5: ...ed to be relocated into the hot gas bypass assembly Figure 3 4 All field brazing and welding should be performed using high quality materials and an inert gas purge such as nitrogen to reduce oxidation of the internal surface of the coil Figure 2 Distributor Figure 3 Hot Gas Bypass Kit 5 If a hot gas bypass kit was ordered with the coil install it now refer to Figure 4 for a general installation d...

Page 6: ...n likely one or more small leaks which should be located and repaired Pressure losses greater than 5 psi would indicate a larger leak which should be isolated and repaired Be sure to check valves and fittings as potential sites for leakage or bleed If the coil is found to be leaking contact your local Daikin coil representative Note Unauthorized repair of the coil may void the coil s warranty see ...

Page 7: ...w hot coils to cool before applying f Using plain water wet both the coil as well as the area surrounding the equipment Wetting the coil with water aids in product penetration and performance g Apply properly diluted product to coil surface Whenever possible apply solution from the outlet side of the coil Allow solution to remain on surface normally 5 10 minutes Do not allow solution to dry on the...

Page 8: ...raining or call 540 248 9646 and ask for the Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 43285Y To find your local Daikin Representative go to www DaikinApplied com This document contains the most current product info...

Reviews: