Installation

Installation

Mounting

Position the coil such that the suction header is at the entering 
airside of the coil and the distributor tubes are at the leaving 
airside of the coil. This orientation provides counter flow heat 
exchange that is required for proper coil performance.

The suction connection is located at the bottom of the coil 
when properly installed (see Figure 1 on page 3).

Installation

If you are unsure about any portion of the installation, contact 
your local steam specialist for assistance

.

1

Carefully remove the coil from the shipping package to 
avoid damage to the finned area. Damaged fins can be 
straightened using an appropriate fin comb. 

2

Proper clearance should be maintained between the coil 
and other structures such as the fan, filter racks, transition 
areas, etc.

3

Inspect the refrigerant distributor and verify that the nozzle 
is in place. The nozzle is generally held in place by a 
retaining ring or it is an integral part of the distributor itself 

(Figure 2). If a hot gas bypass kit was ordered with the coil, 
the nozzle that is in the distributor will need to be relocated 
into the hot gas bypass assembly (Figure 3).

4

All field brazing and welding should be performed using 
high quality materials and an inert gas purge (such as 
nitrogen) to reduce oxidation of the internal surface of the 
coil.

Figure 2: Distributor

Figure 3: Hot Gas Bypass Kit

5

If a hot gas bypass kit was ordered with the coil, install it 
now (refer to Figure 4 for a general installation diagram). 
Complete installation instructions are in the box that 
contains the hot gas bypass kit. Align the side port with the 
hot gas line prior to brazing into place (Figure 4).

Figure 4: Hot Gas Bypass Kit Installed

CAUTION

Sharp edges on sheet metal and fasteners can cause 
personal injury. 

This equipment must be installed, operated, 

and serviced only by an experienced installation company and 
fully trained personnel.
Protective equipment such as safety glasses, steel toe boots 
and gloves are recommended during the installation and 
routine maintenance of the coil.

CAUTION

Failure to properly install the coil can result in irreparable 
damage to the coil as well as other components in the system.

Retainer
Ring

Nozzle

Distributor

Coil

Suction Header

Distributor

Equalizer Line

Nozzle

Liquid Line

Expansion Valve

Suction Line

Remote Sensing Bulb

Straps

Suction Connection

Hot Gas By-Pass

Hot Gas Side Port

Summary of Contents for EF series

Page 1: ... 2008 Daikin Applied Installation and Maintenance Manual IM 902 Daikin Direct Expansion DX Cooling Coils Types EN EF ER EJ EK Group Applied Air Part Number IM 902 Date February 2008 ...

Page 2: ...d Identification Information 3 Receiving Instructions 3 Coil Types 3 Model EN 3 Model EF 3 Model ER 3 Model EJ 3 Model EK 3 Nomenclature 4 Installation 5 Mounting 5 Installation 5 Operation and Maintenance 7 Operation 7 General 7 Maintenance 7 General 7 ...

Page 3: ...ired Model EN Figure 1 evaporators utilize dual suction connections when multiple distributors are used Model EF Face control model EF Figure 1 is another evaporator coil option offered Face control is the simplest form of capacity control These coils are normally furnished with two distributors and two suction connections offering 50 capacity reduction capabilities Model ER Daikin offers a row co...

Page 4: ...be O D Coil Type Circuiting 3 3 8 4 1 2 5 5 8 E Evaporator N Normal F Face Control R Row Control J Interlaced K Interlaced Face Control Finned Length inches Finned Height inches Rows Deep Fins Per Inch Fin Design A flat AI Cu B corrugated AI Cu C sine wave AI Cu F flat SS CS ...

Page 5: ...ed to be relocated into the hot gas bypass assembly Figure 3 4 All field brazing and welding should be performed using high quality materials and an inert gas purge such as nitrogen to reduce oxidation of the internal surface of the coil Figure 2 Distributor Figure 3 Hot Gas Bypass Kit 5 If a hot gas bypass kit was ordered with the coil install it now refer to Figure 4 for a general installation d...

Page 6: ...n likely one or more small leaks which should be located and repaired Pressure losses greater than 5 psi would indicate a larger leak which should be isolated and repaired Be sure to check valves and fittings as potential sites for leakage or bleed If the coil is found to be leaking contact your local Daikin coil representative Note Unauthorized repair of the coil may void the coil s warranty see ...

Page 7: ...w hot coils to cool before applying f Using plain water wet both the coil as well as the area surrounding the equipment Wetting the coil with water aids in product penetration and performance g Apply properly diluted product to coil surface Whenever possible apply solution from the outlet side of the coil Allow solution to remain on surface normally 5 10 minutes Do not allow solution to dry on the...

Page 8: ...raining or call 540 248 9646 and ask for the Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 43285Y To find your local Daikin Representative go to www DaikinApplied com This document contains the most current product info...

Reviews: