Operation manual

7

E(D/B)(H/L)Q011~016BB

Unit and options for air to water heat pump system

4PW67905-1A – 2013.02

Quiet mode operation (

s

)

Quiet mode operation means that the unit works at reduced capacity
so that the sound produced by the unit drops. This implies that the
heating (cooling) capacity will also drop. Beware of this when a
certain level of heating (cooling) is required indoors.

Two quiet modes are available.

Disinfection function

When the 

w

ç

é

 and 

m

(1)

, or 

w

ç

é

 and 

§

(2)

 icons are blinking

together, the disinfection function has been activated. This is not a
malfunction. Refer to "[2] Disinfection function" in the installation
manual for more details.

Freeze protection function

When the 

h

é

 and 

§

 icons are blinking together, the freeze

protection has been activated. This is not a malfunction. Refer to "[4]
Backup/booster heater operation and space heating off temperature"
in the installation manual for more details.

4.6.

Controller operations

Manual operation

In manual operation, the user manually controls the settings of the
installation. The last setting remains active until the user changes it or
until the schedule timer forces another setting (refer to 

"Schedule

timer operation" on page 8

).

As the controller can be used for a wide variety of installations, it is
possible to select a function which is not available on your
installation. In that case the message 

n

 will appear.

Switching on and setting space heating (

h

) and space cooling

(

c

)

1

Use the 

=

 button to select space heating (

h

) or space cooling

(

c

).

Icon 

h

 or 

c

 appears on the display as well as the corresponding

water temperature set point.

2

Use the 

bi

 and 

bj

 buttons to set the desired water

temperature.

Temperature range for heating: 25°C to 55°C
The temperature for heating can be set as low as 15°C (see

"5. Field settings" on page 13

). However, the temperature for

heating should only be set lower than 25°C during
commissioning of the installation. When set lower than 25°C,
only the backup heater will operate.
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (as set through field setting [4-02], refer to

"5. Field settings" on page 13

).

Temperature range for cooling: 5°C to 22°C

3

Switch on the unit by pushing the 

y

 button.

The operation LED 

0

 lights up.

Selection and setting of domestic water heating (

w

)

1

Use the 

v

 button to activate domestic water heating (

w

).

Icon 

w

 appears on the display.

2

Use the 

wi

 or 

wj

 button to display the actual

temperature set point and subsequently, to set the correct
temperature.

The actual temperature set point only appears on the display
after pressing one of the buttons 

wi

 or 

wj

. If no button is

pressed for 5 seconds, the temperature set point will
automatically disappear from the display again.
Temperature range for domestic water heating: 
-

For EKHW* only: 30°C to 78°C

-

For EKHTS only: 30°C to 60°C

3

Press the 

v

 button to deactivate domestic water heating (

w

).

Icon 

w

 disappears from the display.

Selecting powerful domestic water heating operation

1

Press 

v

 for 5 seconds to activate powerful domestic water

heating operation.

-

For EKHW* only: Icons 

w

 and 

m

 start flashing

(3)

.

-

For EKHTS only: Icons 

w

 and 

§

 start flashing

(4)

.

Powerful domestic water heating is deactivated automatically
when the set point for the domestic hot water is reached.

Selecting quiet mode operation (

s

)

1

Use the 

s

 button to activate quiet mode operation (

s

).

Icon 

s

 appears on the display.

If the controller is set in permission level 2 or 3 (refer to 

"5. Field

settings" on page 13

), the 

s

 button will not be operable.

(1) Only applicable for tank with built-in electrical booster heater (EKHW*).
(2) Only applicable for tank without electrical booster heater (EKHTS).

CAUTION

The actual operation range depends on the values set on
field setting [9].

These values shall be determined based on the
application.

INFORMATION

In heating mode (

h

) or cooling mode (

c

), the water

temperature set point can also be weather dependent (icon

a

 is shown).

This means that the controller calculates the water
temperature set point based on the outdoor temperature.

In this case the controller shows the calculated controller
set point. The 

bi

 button or 

bj

 button can be used to

display the actual "shift value" and subsequently, to set the
correct value. This shift value is the temperature difference
between the temperature set point calculated by the
controller and the real set point. E.g. a positive shift value
means that the real temperature set point will be higher
than the calculated set point.

INFORMATION

When the unit is connected to an external room
thermostat, buttons 

=

 and 

y

 are not operable and the

icon 

e

 is shown. In this case, the external room

thermostat switches the unit on or off and determines the
operation mode (space heating or space cooling).

INFORMATION

The domestic hot water set point set on the controller
is the actual domestic hot water set point ([4-03]=0, 1,
2, or 3) or the domestic hot water storage set point
([4-03]=4, or 5). See 

"Domestic water heating

operation (

w

)" on page 6

.

INFORMATION

Remark that pushing the 

y

 button has no influence

on the domestic water heating. Domestic water
heating is only switched on or off by means of the

v

 button.

(3) Only applicable for tank with built-in electrical booster heater (EKHW*).
(4) Only applicable for tank without electrical booster heater (EKHTS).

Summary of Contents for EDHQ011BB6V3

Page 1: ...B6W1 EDLQ011BB6V3 EDLQ014BB6V3 EDLQ016BB6V3 EDLQ011BB6W1 EDLQ014BB6W1 EDLQ016BB6W1 EBHQ011BB6V3 EBHQ014BB6V3 EBHQ016BB6V3 EBHQ011BB6W1 EBHQ014BB6W1 EBHQ016BB6W1 EBLQ011BB6V3 EBLQ014BB6V3 EBLQ016BB6V3...

Page 2: ...ed according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction manual speci ed for a ce...

Page 3: ...er EKHTS in 2 different sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Room thermost...

Page 4: ...o dissipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure th...

Page 5: ...aler 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This ico...

Page 6: ...storage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or di...

Page 7: ...t upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time o...

Page 8: ...ctual temperature set point only appears on the display after pressing one of the buttons wi or wj If no button is pressed for 5 seconds the temperature set point will automatically disappear from the...

Page 9: ...ion with a set point weather dependent or manually set Four actions can be programmed These actions are repeated daily 3 Quiet mode refer to Programming space cooling quiet mode or booster heater mode...

Page 10: ...t a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will...

Page 11: ...e programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the...

Page 12: ...o select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heat...

Page 13: ...ton The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button...

Page 14: ...p 2 through 4 to change other eld settings as required 7 When nished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons c...

Page 15: ...Hi2_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer...

Page 16: ...esis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic hot wa...

Page 17: ...tivating automatic storage during night default setting If it seems that the domestic hot water night storage operation is not suf cient for your needs an additional scheduled reheat during daytime ca...

Page 18: ...refer to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent eld setting is only relevant in case weat...

Page 19: ...Fri Mon Sun All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 xed 5 C 03 Set poi...

Page 20: ...tallation related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1...

Page 21: ...Not applicable Do not change the default value E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identi cation Do not change the default value dependi...

Page 22: ...avoid injury give the piping time to return to normal temperature or be sure to wear proper gloves Do not touch any switch with wet ngers Touching a switch with wet ngers can cause electrical shock W...

Page 23: ...shall not be mixed with unsorted household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a quali...

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4PW67905 1A 2013 02 Copyright 2011 Daikin 4PW67905 1 A 0000000T...

Reviews: