Only for tank without electrical booster heater (EKHTS)

According to local and national regulations, it may be required to
disinfect the domestic hot water tank at a higher temperature
(>60°C). In that case Daikin suggests to install a shunt pump and a
heater element parallel on the domestic hot water tank according to
the figure below.

1

Domestic hot water tank

2

Shunt pump (field supply)

3

Heater element (field supply)

4

Non-return valve (field supply)

5

Shower (field supply)

6

Unit

[3] Auto restart

When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.

Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the 

pr

 button to enable the schedule timer again.

[3-00] Status: defines whether the auto restart function is
turned 

ON (0)

 or 

OFF (1)

.

[4] Space heating off temperature

Space heating off temperature

[4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off to avoid overheating.

[6] Scheduled storage and reheat domestic water heating

Scheduled domestic hot water storage

The storage set point can be accessed directly using the 

wi

 and

wj

 buttons.

[6-03] Scheduled storage: defines whether the scheduled
domestic water heating storage during night is enabled (1) or
not (0).

[6-04] Scheduled storage start time: time of the night at which
the domestic water should be heated.

Scheduled/continuous domestic hot water reheat

[6-05] Reheat: defines whether the scheduled domestic water
reheat during daytime is enabled (1) or continuous reheat is
enabled (2) or reheat is disabled (0)

[6-06] Scheduled reheat start time: time of the day at which the
domestic water should be heated.

[6-07] Domestic hot water reheat set point

[6-08] Domestic hot water reheat set point hysteresis

Example 1

: Scheduled storage [6-03]=1, scheduled reheat [6-05]=1,

disinfection function [2-01]=1 activated.

A Scheduled storage operation:

 activated at [6-04], heat 

up domestic hot water untill domestic hot water user 
interface set point T

DHW

 (e.g 55°C) is reached.

B Scheduled reheat operation

: activated at [6-06], heat up 

domestic hot water untill domestic hot water reheat set 
point [6-07] (e.g 45°C ) is reached. 

C Disinfection operation

 (if activated): activated at [2-02], 

heat up domestic hot water untill domestic hot water 
disinfection set point [2-03] (e.g 60°C) is reached. Refer to 

"[2] Disinfection function" on page 14

.

t

Time

T

Domestic hot water temperature

T

DHW

Domestic hot water user interface set point

Example 2

: Scheduled storage [6-03]=1, continuous reheat [6-05]=2,

disinfection function [2-01]=1 activated.

A Scheduled storage operation:

 activated at [6-04], heat 

up domestic hot water untill domestic hot water user 
interface set point T

DHW

 (e.g 55°C) is reached.

B Continuous reheat operation

: continues activated heat 

up domestic water till domestic hot water reheat set point 
[6-07] (e.g 45°C) is reached with a hysteresis of [6-08]. 

C Disinfection operation

 (if activated): activated at [2-02], 

heat up domestic hot water untill domestic hot water 
disinfection set point [2-03] (e.g 60°C) is reached. Refer to 

"[2] Disinfection function" on page 14

.

t

Time

T

Domestic hot water temperature

T

DHW

Domestic hot water user interface set point

WARNING

Never heat up the domestic water tank temperature higher
than 80°C. This will cause damage to the equipment and
potentially danger of leakage of hot water which can cause
burning wounds.

NOTICE

It is therefore recommended to leave the auto restart
function enabled.

NOTICE

If the benefit kWh rate power supply is of the type that
power supply is interrupted, then always allow the auto
restart function.

If you feel unsure about this topic, contact your installer for
advice and information.

INFORMATION

The scheduled storage and reheat domestic water heating
will only be carried out when [4-03]=4 or 5 and the
domestic water heating mode is enabled by the 

w

 button.

2

1

6

3

5

4

A

B

C

T

t

[2-03]

T

DHW

[6-07]

[6-04]

[6-06]

[2-02]

A

B

C

[6-08]

B

T

t

[2-03]

[6-07]

T

DHW

[6-04]

[2-02]

Summary of Contents for EDHQ011BB6V3

Page 1: ...B6W1 EDLQ011BB6V3 EDLQ014BB6V3 EDLQ016BB6V3 EDLQ011BB6W1 EDLQ014BB6W1 EDLQ016BB6W1 EBHQ011BB6V3 EBHQ014BB6V3 EBHQ016BB6V3 EBHQ011BB6W1 EBHQ014BB6W1 EBHQ016BB6W1 EBLQ011BB6V3 EBLQ014BB6V3 EBLQ016BB6V3...

Page 2: ...ed according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction manual speci ed for a ce...

Page 3: ...er EKHTS in 2 different sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Room thermost...

Page 4: ...o dissipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure th...

Page 5: ...aler 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This ico...

Page 6: ...storage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or di...

Page 7: ...t upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time o...

Page 8: ...ctual temperature set point only appears on the display after pressing one of the buttons wi or wj If no button is pressed for 5 seconds the temperature set point will automatically disappear from the...

Page 9: ...ion with a set point weather dependent or manually set Four actions can be programmed These actions are repeated daily 3 Quiet mode refer to Programming space cooling quiet mode or booster heater mode...

Page 10: ...t a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will...

Page 11: ...e programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the...

Page 12: ...o select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heat...

Page 13: ...ton The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button...

Page 14: ...p 2 through 4 to change other eld settings as required 7 When nished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons c...

Page 15: ...Hi2_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer...

Page 16: ...esis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic hot wa...

Page 17: ...tivating automatic storage during night default setting If it seems that the domestic hot water night storage operation is not suf cient for your needs an additional scheduled reheat during daytime ca...

Page 18: ...refer to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent eld setting is only relevant in case weat...

Page 19: ...Fri Mon Sun All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 xed 5 C 03 Set poi...

Page 20: ...tallation related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1...

Page 21: ...Not applicable Do not change the default value E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identi cation Do not change the default value dependi...

Page 22: ...avoid injury give the piping time to return to normal temperature or be sure to wear proper gloves Do not touch any switch with wet ngers Touching a switch with wet ngers can cause electrical shock W...

Page 23: ...shall not be mixed with unsorted household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a quali...

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4PW67905 1A 2013 02 Copyright 2011 Daikin 4PW67905 1 A 0000000T...

Reviews: