background image

Operation manual

13

E(D/B)(H/L)Q011~016BB

Unit and options for air to water heat pump system

4PW67905-1A – 2013.02

5.

F

IELD

 

SETTINGS

The unit shall be configured by the installer to match the installation
environment (outdoor climate, installed options, etc.) and user
demand. However, the field settings mentioned in 

"Field settings

table" on page 18

 can be modified to customer preferences. Thereto,

a number of so called field settings are available. These field settings
are accessible and programmable through the user interface on the
unit.

Each field setting is assigned a 3-digit number or code, for example
[1-03], which is indicated on the user interface display. The first digit
[1] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.

A list of all field settings and default values is given under 

"Field

settings table" on page 18

. In this same list, we provided for 2

columns to register the date and value of altered field settings at
variance with the default value.

A detailed description of each field setting is given under 

"Detailed

description" on page 13

.

5.1.

Procedure

To change one or more field settings, proceed as follows.

1

Press the 

z

 button for a minimum of 5 seconds to enter FIELD

SET MODE.
The 

$

 icon (3) will be displayed. The current selected field

setting code is indicated 

;

 (2), with the set value displayed to

the right 

-

 (1).

2

Press the 

bgi

 button to select the appropriate field setting

first code.

3

Press the 

bgj

 button to select the appropriate field setting

second code.

4

Press the 

pfi

 button and 

pfj

 button to change

the set value of the select field setting.

5

Save the new value by pressing the 

pr

 button.

6

Repeat step 2 through 4 to change other field settings as
required.

7

When finished, press the 

z

 button to exit FIELD SET MODE.

Detailed description

[0] User permission level

If required, certain user interface buttons can be made unavailable for
the user.

Three permission levels are defined (see the table below). Switching
between level 1 and level 2/3 is done by simultaneously pressing
buttons 

pfi

 and 

pfj

 immediately followed by

simultaneously pressing buttons 

s

 and 

ba

, and keeping all 4

buttons pressed for at least 5 seconds (in normal mode). Note that no
indication on the user interface is given. When level 2/3 is selected,
the actual permission level – either level 2 or level 3 – is determined
by the field setting [0-00].

NOTICE

The default values mentioned in 

"Field settings table" on

page 18

 are the values from factory. The actual initial

values shall be selected according to your application.
These values shall be confirmed by your installer.

CAUTION

The field settings [2] depends on the applicable
legislation.

The field settings [9] depends on the application.

Before changing these settings, the new values shall
be confirmed by the installer and/or shall be according
to the applicable legislation.

2

3

1

NOTICE

Changes made to a specific field setting are only stored
when the 

pr

 button is pressed. Navigating to a new field

setting code or pressing the 

z

 button will discard the

change made.

INFORMATION

Before shipping, the set values have been set as
shown under 

"Field settings table" on page 18

.

When exiting FIELD SET MODE, "

88

" may be

displayed on the user interface LCD while the unit
initialises itself.

Button

Permission level

1

2

3

Quiet mode button 

s

operable

Weather dependent 
set point button

ba

operable

Schedule timer enable/
disable button 

pr

operable

operable

Programming button 

<

operable

Time adjust buttons

pfi
pfj

operable

Inspection/test 
operation button 

z

operable

Summary of Contents for EDHQ011BB6V3

Page 1: ...B6W1 EDLQ011BB6V3 EDLQ014BB6V3 EDLQ016BB6V3 EDLQ011BB6W1 EDLQ014BB6W1 EDLQ016BB6W1 EBHQ011BB6V3 EBHQ014BB6V3 EBHQ016BB6V3 EBHQ011BB6W1 EBHQ014BB6W1 EBHQ016BB6W1 EBLQ011BB6V3 EBLQ014BB6V3 EBLQ016BB6V3...

Page 2: ...ed according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction manual speci ed for a ce...

Page 3: ...er EKHTS in 2 different sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Room thermost...

Page 4: ...o dissipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure th...

Page 5: ...aler 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This ico...

Page 6: ...storage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or di...

Page 7: ...t upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time o...

Page 8: ...ctual temperature set point only appears on the display after pressing one of the buttons wi or wj If no button is pressed for 5 seconds the temperature set point will automatically disappear from the...

Page 9: ...ion with a set point weather dependent or manually set Four actions can be programmed These actions are repeated daily 3 Quiet mode refer to Programming space cooling quiet mode or booster heater mode...

Page 10: ...t a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will...

Page 11: ...e programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the...

Page 12: ...o select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heat...

Page 13: ...ton The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button...

Page 14: ...p 2 through 4 to change other eld settings as required 7 When nished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons c...

Page 15: ...Hi2_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer...

Page 16: ...esis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic hot wa...

Page 17: ...tivating automatic storage during night default setting If it seems that the domestic hot water night storage operation is not suf cient for your needs an additional scheduled reheat during daytime ca...

Page 18: ...refer to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent eld setting is only relevant in case weat...

Page 19: ...Fri Mon Sun All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 xed 5 C 03 Set poi...

Page 20: ...tallation related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1...

Page 21: ...Not applicable Do not change the default value E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identi cation Do not change the default value dependi...

Page 22: ...avoid injury give the piping time to return to normal temperature or be sure to wear proper gloves Do not touch any switch with wet ngers Touching a switch with wet ngers can cause electrical shock W...

Page 23: ...shall not be mixed with unsorted household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a quali...

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4PW67905 1A 2013 02 Copyright 2011 Daikin 4PW67905 1 A 0000000T...

Reviews: