[k
Pa
]
[P
si]
E
S
P
23
V
3
30V
238V
8
8V
2
2
20
V
V
0V
V
0
08
20
NOTE
below.
90 13
■
2
3
4
5
■
6
■
7
■
NOTE
Powering up the unit
Field settings
When power supply to the unit is turned on, "88" is displayed on the
The unit shall be configured by the installer to match the installation
user interface during its initialisation, which might take up to 30
environment (outdoor climate, installed options, etc.) and user
seconds. During this process the user interface cannot be operated.
demand. Thereto, a number
of so called field settings are available.
These field settings are accessible and programmable through the
user interface.
Setting the pump speed
Each field setting is assigned a 3-digit number or code, for example
The pump speed can be selected on the pump (see "Main
components" on page 12).
[5-
03], which is indicated on the user interface display. The first digit
[5] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.
The default setting is high speed (I). If the water flow in the system is
too high (e.g., noise of running water in the installation) the speed
can be set to low speed (II).
A list of all field settings and default values is given under "Field
settings table" on page 35. In this same list, we provided for 2
columns to register the date and value of altered field settings at
The speed dial on the pump indicates 3 speed
variance with the default value.
settings. However, only 2 speed settings exist: low
A detailed description of each field setting is given under "Detailed
speed and high speed. The indicated medium speed
description" on page 26.
setting on the speed dial is equal to low speed.
Procedure
The available external static pressure (ESP, expressed in psi (kPa)) in
function of the
water flow ((gallons/min) (l/min)) is shown in the graph
To change one or more field settings, proceed as follows.
Temperature values displayed on the digital controller
(user interface) are in °C.
Temperature values in °C are between brackets.
Conversion from °C to °F is for information only.
83 12
76 11
69 10
62 9
55 8
3
1
48 7
2
41 6
34 5
28 4
21 3
14 2
7 1
0 0
4
16
6
23
8
30
10
38
12
45
14
53
16
61
18 [gallons/min]
68 [l/min]
1
Press the
z
button for a minimum of 5 seconds to enter FIELD
SET MODE.
The
$
icon (3) will be displayed. The current selected field
setting code is indicated
;
(2), with the set value displayed to
Failure diagnosis at the moment of first installation
the right
-
(1).
In case nothing is displayed on the remote controller (the current
set temperature does not display), check for any of the following
Press the
bgi
button to select the appropriate field
setting first code.
abnormalities before you can diagnose possible malfunction
Press the
bgj
button to select the appropriate field
codes.
setting second code.
■
Disconnection or wiring error (between power supply and unit
Press the
pfi
button and
pfj
button to change
and between unit and remote controller).
the set value of the select field setting.
■
The fuse on the PCB may have run out.
Save the new value by pressing the
pr
button.
If the remote controller shows
"
E3
", "
E4
"
or
"
L8
"
as an error code,
there is a possibility that either the stop valves are closed, or that
air inlet or air outlet are blocked.
Repeat step 2 through 4 to change other field settings as
required.
If the error code
"
U2
"
is displayed on the remote controller, check
When finished, press the
z
button to exit FIELD SET MODE.
for voltage imbalance.
If the error code
"L4"
is displayed on the remote controller, it is
possible that air inlet or air outlet are blocked.
Changes made to a specific field setting are only
stored when the
pr
button is pressed. Navigating to a
new field setting code or pressing the
z
button will
discard the change made.
EDLQ036~054B EBLQ036~054BA6VJU1
Installation manual
Unit for air to water heat pump system
4PW56182-1
25