of time.
Connection to a benefit kWh rate power supply
Electricity companies throughout the world work hard to provide
[D-01]=1
[D-01]=2
reliable electric service at competitive prices and are often authorized
to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates,
Wärmepumpentarif in Germany and Austria, ... .
This equipment allows for connection to such benefit rate power
1
1
L N
1
1
L N
supply delivery systems.
2
S2S
2
S2S
Consult with the electricity company acting as provider at the site
where this equipment is to be installed to know whether it is
3
4
3
4
appropriate to connect the equipment in one of the benefit kWh rate
power supply delivery systems available, if any.
When the equipment is connected to such benefit kWh rate power
supply, the electricity company is allowed to:
1
2
2
L N
S2S
1
2
2
L N
S2S
interrupt power supply to the equipment for certain periods of
time;
■
demand that the equipment only consumes a limited amount of
electricity during certain periods of time.
The unit is designed to receive an input signal by which the unit
switches into forced off mode. At that moment, the outdoor unit
compressor will not operate.
3
1
2
3
L N
S2S
4
3
1
2
3
L N
S2S
4
CAUTION
3
3
for a benefit kWh rate power supply like illustrated
below as type 1
If the benefit kWh rate power supply is of the type that
power supply is not interrupted, then control of the
heaters is still possible.
3
4
For the different possibilities of controlling heaters at
17 18
X2M
moments that benefit kWh rate is active, refer to
"[D] Benefit kWh rate power supply/Local shift value
weather dependent" on page 33.
If heaters must be controlled at moments that the
*
DHQ/
*
DLQ/
*
BHQ/
*
BLQ
benefit kWh rate power supply is off, then these
Benefit kWh rate power supply box
heaters shall be connected to a separate power
supply.
During the period that the benefit kWh rate is active
and power supply is continuous, then stand-by power
Receiver controlling the signal of the electricity company
Power supply to outdoor unit
Voltage free contact
consumption is possible (PCB, controller, pump, ...).
0
Allowed
for a benefit kWh rate power supply like illustrated
Not allowed (unless glycol is added to the water system)
below as types 2 or 3
Unless glycol is added to the water system, benefit kWh
rate power supplies that completely shut power supply are
not allowed for this application because of the water freeze
prevention that would not be powered. (Refer to Caution:
"Use of glycol" on page 16.)
When the outdoor unit is connected to a benefit kWh rate power
supply, the voltage free contact of the receiver controlling the benefit
kWh rate signal of the electricity company must be connected to
clamps 17 and 18 of X2M (as illustrated in the figure above).
When parameter [D-
01]=1 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will open and
If during benefit kWh rate power supply the power supply is
the unit will go in forced off mode
(1)
.
shut off, then heaters can not be controlled.
When parameter [D-01]=2 at the moment that the
benefit kWh rate
This power supply interruption should not be longer
than 2 hours, otherwise the real time clock of the
signal is sent by the electricity company, that contact will close and
the unit will go in forced off mode
(2)
.
controller will be reset.
Type 1
During power supply interruption, the controller
This type of benefit kWh rate power supply is not interrupted.
display will be blank.
Type 2
Possible types of benefit kWh rate power supply
This type of benefit kWh rate power supply is interrupted after elapse
Possible connections and requirements to connect the equipment to
such power supply are illustrated in the figure below:
Type 3
This type of benefit kWh rate power supply is interrupted
immediately.
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to "[3] Auto restart" on page 27.
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to "[3] Auto restart" on page 27.