background image

13

HEAT PUMP OPERATION

Cooling Cycle

When the heat pump is in the cooling cycle, it operates 

exactly as a Summer Air Conditioner unit. In this mode, 

all the charts and data for service that apply to summer 

air conditioning apply to the heat pump. Most apply on 

the heating cycle except the “condenser” becomes the 

“evaporator”, “evaporator” becomes “condenser”, “cooling” 

becomes “heating”.

Heating Cycle

The heat pump switches from cooling cycle by redirecting 

refrigerant flow through the refrigerant circuit external to 

the compressor. This is accomplished by the reversing 

valve. Hot discharge vapor from the compressor is directed 

to the indoor coil (evaporator on the cooling cycle) where 

the heat is removed, and the vapor condenses to liquid. 

It then goes through the expansion device to the outdoor 

coil (condenser on the cooling cycle) where the liquid is 

evaporated, and the vapor goes to the compressor. 

The following figures show a schematic of a heat pump on 

the cooling cycle and the heating cycle. The heat pump 

is equipped with thermal expansion valves for the indoor 

and outdoor coils. It is also provided with a defrost control 

system.

Heating

When the heat pump is on the heating cycle, the outdoor 

coil is functioning as an evaporator. The temperature 

of the refrigerant in the outdoor coil must be below the 

temperature of the outdoor air in order to extract heat from 

the air. Thus, the greater the difference in the outdoor 

temperature and the outdoor coil temperature, the greater 

the heating capacity of the heat pump. This phenomenon 

is a characteristic of a heat pump. It is a good practice to 

provide supplementary heat for all heat pump installations 

in areas where the temperature drops below 45° F. It is 

also a good practice to provide sufficient supplementary 

heat to handle the entire heating requirement should 

there be a component failure of the heat pump, such as a 

compressor, or refrigerant leak, etc. 

Since the temperature of the refrigerant in the outdoor 

coil on the heating cycle is generally below freezing point, 

frost forms on the surfaces of the outdoor coil under 

certain weather conditions of temperature and relative 

humidity. Therefore, it is necessary to reverse the flow of 

the refrigerant to provide hot gas in the outdoor coil to melt 

the frost accumulation. This is accomplished by reversing 

the heat pump to the cooling cycle. At the same time, the 

outdoor fan stops to hasten the temperature rise of the 

outdoor coil and lessen the time required for defrosting. 

The indoor blower continues to run and the supplementary 

heaters are energized.

Defrost Control

During operation the Defrost signal to the circuit board 

is controlled by a temperature sensor, which is clamped 

to a feeder tube entering the outdoor coil. Defrost timing 

periods of 30,60 and 90 minutes may be selected 

by connecting the circuit board jumper to 30, 60 and 

90 respectively. Accumulation of time for the timing 

period selected starts when the sensor contact closes 

(approximately 31°F), and when the wall thermostat calls 

for heat. At the end of the timing period, the unit’s defrost 

cycle will be initiated provided the sensor contact remains 

closed. When the sensor contact opens (approximately 75° 

F), the defrost cycle is terminated and the timing period 

is reset. If the defrost cycle is not terminated due to the 

sensor temperature, a ten minute override interrupts the 

unit’s defrost period.

Summary of Contents for DP16H M Series

Page 1: ...19 Wiring Diagrams 20 Start UpChecklist 21 Only personnel that have been trained to install adjust service or repair hereinafter service the equipment specified in this manual should service the equip...

Page 2: ...ence CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use...

Page 3: ...where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any code or r...

Page 4: ...Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local...

Page 5: ...ES Unit Clearances In situations that have multiple units a 36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenanc...

Page 6: ...the following bullet points must be observed when installing the unit Unit must be lifted by the four lifting holes located at the base frame corners Lifting cables should be attached to the unit wit...

Page 7: ...present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not tamper with factory wiring The intera...

Page 8: ...vided for this purpose Do not use the ground lug for connecting a neutral conductor Connect power wiring to the electrical power block located within the main control box Control Box control box Conne...

Page 9: ...g thermostat sub base NOTE Refer to unit wiring diagrams for thermostat or remote sensor connections CIRCULATING AIR AND FILTERS Ductwork The supply duct from the unit through a wall may be installed...

Page 10: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Page 11: ...r speed setting than the G Y1 and W1 speed setting If Electric Heater kit is installed use the red wire provided with the literature kit to jumper terminal TB1 W1 to an unoccupied speed tap that satis...

Page 12: ...unning with the reversing valve in the deenergized heating position After giving the unit time to settle out make sure the unit is supplying heated air Note If the outdoor ambient is above 80 F the un...

Page 13: ...to provide supplementary heat for all heat pump installations in areas where the temperature drops below 45 F It is also a good practice to provide sufficient supplementary heat to handle the entire h...

Page 14: ...ficiency or equipment damage due to dust and lint build up on internal parts never operate unit without an air filter installed in the return air system Every application may require a different frequ...

Page 15: ...15 Wiring Example Electric Heat Wiring Example...

Page 16: ...0 0 8 1960 1045 0 86 0 2 2189 902 0 81 0 2 2234 960 0 86 0 4 2119 943 0 84 0 4 2162 1003 0 90 0 6 2059 979 0 88 0 6 2101 1042 0 93 0 8 2012 1009 0 90 0 8 2053 1073 0 96 0 2 2254 923 0 88 0 2 2300 982...

Page 17: ...5 7 2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 DP16HM60 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83...

Page 18: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Page 19: ...MODEL NUMBER DP16HM60 kW MINIMUM SCFM AIR FLOW FOR ELECTRIC HEAT 2500 MAXIMUM SCFM HEATER KIT MODEL NUMBER NOMENCLATURE E H S 15 1 2 3 4 5 6 7 Electric Heater Heater Type X Staged S SCR modulating Vol...

Page 20: ...E INSTALLED NOTES 4 3 2 1 5 6 BLACK BLUE BLUE WITH PINK STRIPE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW YELLOW WITH PINK STRIPE BK BL BL PK BR GR GY OR PK PU RD TN WH YL YL PK HIGH VOL...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 24: ...o the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process an...

Reviews: