background image

7

Y

X

CG

COMPRESSOR

CONDENSER COIL

RETURN

EVAPORATOR COIL

B

C

D

A

SUPPLY

Corner and center of gravity locations 

Note: Unit should be lifted at a point above center 

of gravity. 

A

B

C

D

DP16HM6041

688

630

150

194

165

121

33.5

27.6

Model

Shipping 

Weight (lb)

Operating 

Weight (lb)

Corner Weights (lb)

X (in) Y (in) 

CAUTION

To prevent damage to the wiring, protect 

wiring from sharp edges. follow national 

electrical code and all local codes and 

ordinances. Do not route wires through 

removable access panels.

CAUTION

To prevent severe damage to the bottom of 

the unit, do not fork lift unit after wood 

struts have been removed. 

Bring condenser end of unit into alignment with the curb 

first.  Lower unit carefully onto roof mounting curb.  When a 

rectangular cantilever curb is used, care should be taken to 

center the unit.  Check for proper alignment and orientation 

of supply and return openings with duct.

Rigging Removal 

CAUTION

To prevent damage to the unit, do not allow 

crane hooks and spreader bars to rest on the 

roof of the unit.

Remove spreader bars, lifting cables and other rigging 

equipment. 

ELECTRICAL WIRING 

WARNING

HIGH VOLTAGE!

Disconnect all power before 

servicing or installing this unit.  

Multiple power sources may be 

present.  Failure to do so may cause 

property damage, personal injury or 

death.

WARNING

HIGH VOLTAGE!

To avoid personal injury or death 

due to electrical shock, do not 

tamper with factory wiring. The 

interanl power and control wiring 

of these units are factory-installed 

and have been thoroughly tested 

prior to shipment. Contact your 

local representative if assistance is 

required. 

CAUTION

Conduit and fittings must be weather-tight to 

prevent water entry into the building. 

For unit protection, use a fuse or HACR circuit breaker that 

is in excess of the circuit ampacity, but less than or equal 

to the maximum overcurrent protection device. DO NOT 

EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE 

SHOWN ON UNIT DATA PLATE.

All line voltage connections must be made through 

weatherproof fittings.  All exterior power supply and ground 

wiring must be in approved weatherproof conduit.

The main power supply wiring to the unit and low voltage 

wiring to accessory controls must be done in accordance 

with these instructions, the latest edition of the National 

Electrical Code (ANSI/NFPA 70), and all local codes and 

ordinances.  

The unit is factory wired for the voltage shown on the unit’s 

data plate. Refer to model nomenclature in Appendix B for 

voltage requirement for your unit. 

NOTE: If supply voltage is 208V, lead on primary 

of transformer(s) must be moved from the 230V 

to the 208V tap. Refer to wiring diagram on unit 

for details.

Summary of Contents for DP16H M Series

Page 1: ...19 Wiring Diagrams 20 Start UpChecklist 21 Only personnel that have been trained to install adjust service or repair hereinafter service the equipment specified in this manual should service the equip...

Page 2: ...ence CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use...

Page 3: ...where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any code or r...

Page 4: ...Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local...

Page 5: ...ES Unit Clearances In situations that have multiple units a 36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenanc...

Page 6: ...the following bullet points must be observed when installing the unit Unit must be lifted by the four lifting holes located at the base frame corners Lifting cables should be attached to the unit wit...

Page 7: ...present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not tamper with factory wiring The intera...

Page 8: ...vided for this purpose Do not use the ground lug for connecting a neutral conductor Connect power wiring to the electrical power block located within the main control box Control Box control box Conne...

Page 9: ...g thermostat sub base NOTE Refer to unit wiring diagrams for thermostat or remote sensor connections CIRCULATING AIR AND FILTERS Ductwork The supply duct from the unit through a wall may be installed...

Page 10: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Page 11: ...r speed setting than the G Y1 and W1 speed setting If Electric Heater kit is installed use the red wire provided with the literature kit to jumper terminal TB1 W1 to an unoccupied speed tap that satis...

Page 12: ...unning with the reversing valve in the deenergized heating position After giving the unit time to settle out make sure the unit is supplying heated air Note If the outdoor ambient is above 80 F the un...

Page 13: ...to provide supplementary heat for all heat pump installations in areas where the temperature drops below 45 F It is also a good practice to provide sufficient supplementary heat to handle the entire h...

Page 14: ...ficiency or equipment damage due to dust and lint build up on internal parts never operate unit without an air filter installed in the return air system Every application may require a different frequ...

Page 15: ...15 Wiring Example Electric Heat Wiring Example...

Page 16: ...0 0 8 1960 1045 0 86 0 2 2189 902 0 81 0 2 2234 960 0 86 0 4 2119 943 0 84 0 4 2162 1003 0 90 0 6 2059 979 0 88 0 6 2101 1042 0 93 0 8 2012 1009 0 90 0 8 2053 1073 0 96 0 2 2254 923 0 88 0 2 2300 982...

Page 17: ...5 7 2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 DP16HM60 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83...

Page 18: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Page 19: ...MODEL NUMBER DP16HM60 kW MINIMUM SCFM AIR FLOW FOR ELECTRIC HEAT 2500 MAXIMUM SCFM HEATER KIT MODEL NUMBER NOMENCLATURE E H S 15 1 2 3 4 5 6 7 Electric Heater Heater Type X Staged S SCR modulating Vol...

Page 20: ...E INSTALLED NOTES 4 3 2 1 5 6 BLACK BLUE BLUE WITH PINK STRIPE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW YELLOW WITH PINK STRIPE BK BL BL PK BR GR GY OR PK PU RD TN WH YL YL PK HIGH VOL...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 24: ...o the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process an...

Reviews: