background image

8

Main power wiring should be sized for the minimum circuit 

ampacity shown on the unit’s database.  Size wires in 

accordance with the ampacity tables in Article 310 of the 

National Electrical Code.  If long wires are required, it 

may be necessary to increase the wire size to prevent 

excessive voltage drop.  Wires should be sized for a 

maximum of 3% voltage drop.

CAUTION

To avoid risk of property damage, personal 

injury or fire, use only copper conductors.

CAUTION

Label all wires prior to disconnection when 

servicing controls. Wiring errors can cause 

improper and dangerous operation. Verify 

proper operation after servicing. 

NOTE: A weather-tight disconnect switch, 

properly sized for the unit total load, must be 

field or factory installed.  An external field 

supplied disconnect may be mounted on the 

exterior panel.

Ensure the data plate is not covered by the field-supplied 

disconnect switch.

•   Some disconnect switches are not fused.  Protect 

the power leads at the point of distribution in 

accordance with the unit data plate.

•   The unit must be electrically grounded in accordance 

with local codes or, in the absence of local codes, 

with the latest edition of the National Electrical Code 

ANSI/NFPA 70, and/or the Canadian Electrical Code, 

CSA C22.1, Part 1.  A ground lug is provided for this 

purpose.  Do not use the ground lug for connecting a 

neutral conductor.

•   Connect power wiring to the electrical power block 

located within the main control box.

Control Box

control box Connections

note: depending on the options installed, the 

location of the components may vary in some 

models. 

WARNING

Failure of unit due to operation on improper 

line voltage or with excessive phase unbalance 

constitutes product abuse and will void your 

warranty and may cause severe damage to the 

unit electrical components.

Areas Without Convenience Outlet

It is recommended that an independent 115V power source 

be brought to the vicinity of the roof top unit for portable 

lights and tools used by the service mechanic.

NOTE: Refer to local codes for requirements. 

These outlets can also be factory installed.

Units installed on Roof Tops

Main power and low voltage wiring may enter the unit 

through the condenser end of unit or through the roof curb. 

Install conduit connectors at the desired entrance locations.  

External connectors must be weatherproof.  All holes in the 

unit base must be sealed (including those around conduit 

nuts) to prevent water leakage into building.  All required 

conduit and fittings are to be field supplied.

Supply voltage to roof top unit must not vary by more than 

10% of the value indicated on the unit data plate.  Phase 

voltage unbalance must not exceed 2%.  Contact your 

local power company for correction of improper voltage or 

phase unbalance.

Summary of Contents for DP16H M Series

Page 1: ...19 Wiring Diagrams 20 Start UpChecklist 21 Only personnel that have been trained to install adjust service or repair hereinafter service the equipment specified in this manual should service the equip...

Page 2: ...ence CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use...

Page 3: ...where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any code or r...

Page 4: ...Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local...

Page 5: ...ES Unit Clearances In situations that have multiple units a 36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenanc...

Page 6: ...the following bullet points must be observed when installing the unit Unit must be lifted by the four lifting holes located at the base frame corners Lifting cables should be attached to the unit wit...

Page 7: ...present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not tamper with factory wiring The intera...

Page 8: ...vided for this purpose Do not use the ground lug for connecting a neutral conductor Connect power wiring to the electrical power block located within the main control box Control Box control box Conne...

Page 9: ...g thermostat sub base NOTE Refer to unit wiring diagrams for thermostat or remote sensor connections CIRCULATING AIR AND FILTERS Ductwork The supply duct from the unit through a wall may be installed...

Page 10: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Page 11: ...r speed setting than the G Y1 and W1 speed setting If Electric Heater kit is installed use the red wire provided with the literature kit to jumper terminal TB1 W1 to an unoccupied speed tap that satis...

Page 12: ...unning with the reversing valve in the deenergized heating position After giving the unit time to settle out make sure the unit is supplying heated air Note If the outdoor ambient is above 80 F the un...

Page 13: ...to provide supplementary heat for all heat pump installations in areas where the temperature drops below 45 F It is also a good practice to provide sufficient supplementary heat to handle the entire h...

Page 14: ...ficiency or equipment damage due to dust and lint build up on internal parts never operate unit without an air filter installed in the return air system Every application may require a different frequ...

Page 15: ...15 Wiring Example Electric Heat Wiring Example...

Page 16: ...0 0 8 1960 1045 0 86 0 2 2189 902 0 81 0 2 2234 960 0 86 0 4 2119 943 0 84 0 4 2162 1003 0 90 0 6 2059 979 0 88 0 6 2101 1042 0 93 0 8 2012 1009 0 90 0 8 2053 1073 0 96 0 2 2254 923 0 88 0 2 2300 982...

Page 17: ...5 7 2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 DP16HM60 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83...

Page 18: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Page 19: ...MODEL NUMBER DP16HM60 kW MINIMUM SCFM AIR FLOW FOR ELECTRIC HEAT 2500 MAXIMUM SCFM HEATER KIT MODEL NUMBER NOMENCLATURE E H S 15 1 2 3 4 5 6 7 Electric Heater Heater Type X Staged S SCR modulating Vol...

Page 20: ...E INSTALLED NOTES 4 3 2 1 5 6 BLACK BLUE BLUE WITH PINK STRIPE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW YELLOW WITH PINK STRIPE BK BL BL PK BR GR GY OR PK PU RD TN WH YL YL PK HIGH VOL...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 24: ...o the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process an...

Reviews: