background image

4

www.daikincomfort.com

SS-DM96SN-U

SS-DM96SN-U

www.daikincomfort.com

5

Airflow Specificatoins 

Minimum Filter Sizes

DM96SN

 

0403BU

DM96SN

0603BU

DM96SN

0805CU

Filter Size (in²) (Qty)

(1) 16 x 25 

 

(side or bottom)

(1) 20 x 25 (bottom) 

 

or (2) 16 x 25 (side)

Note: Other size filters of equal or greater dimensions may be used. Filters may also be centrally located.

COOLING & CIRCULATION AIRFLOW

MODEL

THERMOSTAT 

CALL

TAP #

EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

DM96SN 

0403BU*

Y1 / Y2 / G

F01

714

667

620

573

528

483

439

394

F02

841

803

765

725

686

645

605

565

F03

862

823

784

745

706

666

626

586

F04

1043

1011

976

945

912

879

845

810

F05^

1080

1051

1021

990

961

932

903

867

F06

1182

1155

1129

1102

1075

1048

1020

992

F07

1193

1164

1136

1108

1080

1052

1025

997

F08^^

1280

1256

1231

1206

1183

1156

1132

1107

F09

1333

1306

1280

1255

1231

1205

1180

1155

DM96SN 

0603BU*

Y1 / Y2 / G

F01

767

712

655

592

528

476

431

388

F02

919

871

824

774

723

665

612

565

F03

925

889

842

797

748

693

636

589

F04^

1099

1060

1018

977

935

891

848

803

F05

1125

1086

1047

1008

970

931

885

844

F06

1239

1200

1163

1127

1095

1053

1014

974

F07^^

1317

1283

1249

1214

1179

1146

1110

1073

F08

1337

1304

1269

1235

1206

1167

1133

1097

F09

1415

1383

1353

1321

1288

1256

1222

1190

DM96SN 

0805CU*

Y1 / Y2 / G

F01

999

934

877

814

740

681

615

554

F02

1297

1245

1194

1143

1096

1044

991

933

F03

1407

1354

1307

1257

1210

1164

1118

1067

F04^

1532

1488

1440

1396

1352

1304

1259

1210

F05^^

1641

1594

1552

1509

1477

1425

1388

1347

F06

1687

1644

1604

1560

1519

1479

1441

1409

F07

1831

1791

1755

1718

1680

1642

1607

1570

F08

1895

1860

1822

1788

1753

1716

1684

1650

F09

2258

2222

2186

2151

2135

2087

2055

2020

HEATING AIFLOW

MODEL

THERMOSTAT 

CALL

TAP #

EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

CFM

CFM

DM96SN 

0403BU*

W/W1

F04^

1043

34

1011

35

976

36

945

38

912

39

879

845

810

F05

1080

33

1051

34

1021

35

990

36

961

37

932

903

867

DM96SN 

0603BU*

W/W1

F04

1099

49

1060

50

1018

52

977

55

935

57

891

848

803

F05

1125

47

1086

49

1047

51

1008

53

970

55

931

885

844

F06^

1239

43

1200

44

1163

46

1127

47

1095

49

1053

1014

974

DM96SN 

0805CU*

W/W1

F03

1407

51

1354

53

1307

54

1257

57

1210

59

1164

1118

1067

F04^

1532

46

1488

48

1440

49

1396

51

1352

53

1304

1259

1210

Defaullt speed is F01 for circulation for all models

 

^ Default Y1 speed 

 

^^ Default Y2 speed 

 

 

 

^ Default Heat Speed 

Summary of Contents for DM96SN

Page 1: ...y Management District SCAQMD Rule 1111 and San Joaquin Valley Air Pollution Control District SJVAPCD Rule 4905 Learn more at www aqmd gov and www valleyair org AHRI Certified ETL Listed Designed for multi position installation DM96SN Upflow horizontal left or right Certified for direct vent 2 pipe or non direct vent 1 pipe Easy to install top venting with optional side venting Convenient left or r...

Page 2: ...ease B 1st Revision Configuration M Upflow Horizontal Major Revision A Initial Release B 1st Revision AFUE 80 80 AFUE Nox 96 96 AFUE U Ultra Low NOx 14 ng J NOx Gas Valve S 1 STAGE Cabinet Width A 14 Motor B 17 5 N Multi Speed ECM 9 TAPS C 21 D 24 5 MBTU h Maximum CFM 040 40 000 BTU h 3 1200 CFM 060 60 000 BTU h 4 1600 CFM 080 80 000 BTU h 5 2000 CFM ...

Page 3: ...ipe is dependent on installation code requirements and must be 2 or 3 diameter PVC 4 Minimum Circuit Ampacity 1 25 x Circulator Blower Amps ID Blower amps Wire size should be determined in accordance with National Electrical Codes Extensive wire runs will require larger wire sizes 5 Maximum Overcurrent Protection Device refers to maximum recommended fuse or circuit breaker size May use fuses or HA...

Page 4: ...r Discharge LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW Condensate Drain Trap Exterior Connection Right or Left Side PVC Vent Flue Pipe 2 PVC Alternate Vent Flue Location Right Side Drain Trap Exterior Holes High Voltage Electrical Outlet Alternate Gas Supply Low Voltage Electrical Outlet Standard Gas Supply Location Center Dimple For Alternate Air Intake Pipe 3 OD Hole Air Intake 2 Pipe Left Side D...

Page 5: ...95 1053 1014 974 F07 1317 1283 1249 1214 1179 1146 1110 1073 F08 1337 1304 1269 1235 1206 1167 1133 1097 F09 1415 1383 1353 1321 1288 1256 1222 1190 DM96SN 0805CU Y1 Y2 G F01 999 934 877 814 740 681 615 554 F02 1297 1245 1194 1143 1096 1044 991 933 F03 1407 1354 1307 1257 1210 1164 1118 1067 F04 1532 1488 1440 1396 1352 1304 1259 1210 F05 1641 1594 1552 1509 1477 1425 1388 1347 F06 1687 1644 1604 ...

Page 6: ...UT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT CFM x 1 08 x RISE RISE BTU OUTPUT 1 08 CFM 800 Temperature Rise Output BTU h x 1 000 Formulas BTU h Output CFM x 1 08 x Rise Rise BTU H Output CFM x 1 08 BTU Output Vs Temperature Rise Chart ...

Page 7: ...sed E E 2 Open High Limit Switch E E 3 Flame Detected When No Flame Should Be Present E E 4 Open Fuse E E 5 Low Flame Signal E E 6 Ignitor Fault Or Ignitor Relay Fault E E 7 Reversed Line Polarity E E A Grounding Error E 1 0 Inernal Gas Valve Error E E b External Gas Valve Error E E C Aux Limit Switch Open E E d Burner Limit Switch Open E 1 I ALI 1 HLI 7 NOTE 5 NOTE 6 0140F02647 A CR48 SW1 SW2 E28...

Page 8: ...3BU DM96SN 0805CU 72950 Concentric Vent Kit 2 72951 Concentric Vent Kit 3 RF000142 Drain Kit Horizontal Left Vertical Flue EFR02 External Filter Rack with 16 x25 Permanent Filter 0170K00000S Flush Mount Vent Kit 3 or 2 0170K00001S Flush Mount Vent Kit 2 0270F05404 Horizontal Drain Tubing Kit ...

Reviews: