6
CAUTION
If units are lifted two at a time, the fork holes on the
condenser end of the unit must not be used. Minimum fork
length is 42” to prevent damage to the unit; however, 48” is
recommended.
Provisions for forks have been included in the
unit base frame. No other fork locations are
approved.
WARNING
To prevent possible equipment damage, property damage,
personal injury or death, the following bullet points must
be observed when installing the unit.
•
Unit must be lifted by the four lifting holes located at
the base frame corners.
•
Lifting cables should be attached to the unit with
shackles.
•
The distance between the crane hook and the top of
the unit must not be less than 60”.
•
Two spreader bars must span over the unit to
prevent damage to the cabinet by the lift cables.
Spreader bars must be of sufficient length so that
cables do not come in contact with the unit during
transport. Remove wood struts mounted beneath
unit base frame before setting unit on roof curb.
These struts are intended to protect unit base frame
from fork lift damage. Removal is accomplished by
extracting the sheet metal retainers and pulling the
struts through the base of the unit. Refer to rigging
label on the unit.
IMPORTANT: If using bottom discharge with roof
curb, ductwork should be attached to the curb
prior to installing the unit. Ductwork dimensions
are shown in Roof Curb Installation Instructions.
Refer to the Roof Curb Installation Instructions for proper
curb installation. Curbing must be installed in compliance
with the National Roofing Contractors Association Manual.
To assist in determining rigging requirements, unit weights
and center of gravity are shown as follows:
AA
B
D
C
Corner and Center of Gravity Locations
Note: Unit should be lifted at a point above
center of gravity.
Length Width
A
B
C
D
X (in)
Y(in)
DFC0361D
554
484
117 142 80 145 34.4
28.6
DFC0363D
552
482
117 140 80 145 34.5
28.6
DFC0364D
560
490
117 142 80 151 34.9
28.9
DFC0367D
560
490
117 142 80 151 34.9
28.9
DFC0481D
577
507
134 152 87 134 32.3
27.2
DFC0483D
572
502
134 147 87 134 32.6
27.0
DFC0484D
576
506
134 147 87 138 32.9
27.2
DFC0487D
576
506
134 147 87 138 32.9
27.2
DFC0601D
582
512
113 166 104 129 33.7
27.8
DFC0603D
578
508
113 162 104 129 33.9
27.7
DFC0604D
582
512
113 162 104 133 34.3
27.8
DFC0607D
582
512
113 162 104 133 34.3
27.8
DFC0723D
651
581
143 178 90 170 33.1
28.9
DFC0724D
651
581
143 178 90 170 33.1
28.9
DFC0727D
651
581
143 178 90 170 33.1
28.9
Model
Shipping Weight (lbs) Operating Weight (lbs)
Corner Weights (lbs)
The numbers may slightly vary depending on installed options.
CAUTION
To prevent damage to the wiring, protect wiring from sharp
edges. Follow national electrical code and all local codes
and ordinances. Do not route wires through removable
access panels.