APPENDIX A BLOWER PERFORMANCE TABLES - AC

TAP

STATIC

AIRFLOW (CFM)

RPM

WATTS

BHP

0.6

2085

1080

869

0.90

0.7

2050

1105

888

0.92

0.8

2015

1135

907

0.94

0.9

1955

1160

927

0.97

1.0

1940

1195

932

0.99

1.1

1910

1210

961

1.01

1.2

1880

1235

982

1.03

1.3

1845

1260

1000

1.05

1.4

1820

1285

1021

1.07

1.5

1790

1310

1041

1.09

1.6

1750

1335

1058

1.11

1.7

1715

1355

1078

1.13

1.8

1680

1380

1097

1.15

0.6

1890

1025

713

0.72

0.7

1855

1055

731

0.75

0.8

1815

1080

749

0.76

0.9

1765

1115

765

0.79

1.0

1745

1150

776

0.81

1.1

1710

1165

800

0.82

1.2

1675

1195

817

0.84

1.3

1640

1220

835

0.86

1.4

1625

1245

865

0.88

1.5

1585

1275

884

0.90

1.6

1550

1305

901

0.92

1.7

1510

1330

920

0.94

1.8

1475

1355

938

0.96

0.6

2555

1215

1385

1.43

0.7

2520

1235

1408

1.45

0.8

2485

1265

1431

1.49

0.9

2430

1285

1455

1.51

1.0

2425

1320

1462

1.56

1.1

2400

1325

1499

1.56

1.2

2370

1345

1522

1.58

1.3

2340

1365

1543

1.61

1.4

2300

1385

1558

1.63

1.5

2270

1410

1580

1.66

1.6

2240

1430

1600

1.68

1.7

2210

1450

1621

1.71

1.8

2175

1470

1643

1.73

0.6

2660

1245

1534

1.57

0.7

2625

1270

1559

1.61

0.8

2595

1290

1583

1.63

0.9

2530

1310

1608

1.66

1.0

2530

1345

1618

1.70

1.1

2500

1350

1654

1.71

1.2

2470

1370

1676

1.73

1.3

2445

1390

1699

1.76

1.4

2410

1415

1716

1.79

1.5

2380

1435

1739

1.81

1.6

2345

1450

1760

1.83

1.7

2320

1470

1782

1.86

1.8

2285

1490

1804

1.88

0.6

2650

1240

1520

1.56

0.7

2615

1265

1544

1.59

0.8

2585

1290

1568

1.62

0.9

2525

1310

1593

1.65

1.0

2520

1340

1604

1.68

1.1

2490

1350

1639

1.70

1.2

2465

1370

1662

1.72

1.3

2435

1385

1685

1.74

1.4

2400

1410

1701

1.77

1.5

2370

1430

1724

1.80

1.6

2340

1450

1745

1.82

1.7

2310

1470

1767

1.85

1.8

2275

1490

1789

1.87

T5

DFC0723W / DFC0724W / DFC0727W HORIZONTAL

T1

T2

T3

T4

TAP

STATIC

AIRFLOW (CFM)

RPM

WATTS

BHP

0.6

2245

1125

1019

1.06

0.7

2205

1150

1040

1.08

0.8

2170

1175

1060

1.11

0.9

2120

1200

1081

1.13

1.0

2110

1235

1085

1.16

1.1

2075

1245

1117

1.17

1.2

2045

1270

1140

1.20

1.3

2015

1295

1159

1.22

1.4

1980

1315

1175

1.24

1.5

1950

1340

1195

1.26

1.6

1915

1360

1213

1.28

1.7

1880

1385

1233

1.31

1.8

1845

1410

1253

1.33

0.6

2040

1065

829

0.85

0.7

2000

1090

848

0.87

0.8

1965

1125

866

0.90

0.9

1910

1150

885

0.92

1.0

1895

1185

891

0.95

1.1

1860

1200

919

0.96

1.2

1825

1225

939

0.98

1.3

1800

1245

958

1.00

1.4

1775

1275

981

1.02

1.5

1740

1300

999

1.04

1.6

1700

1325

1016

1.06

1.7

1665

1350

1037

1.08

1.8

1625

1375

1056

1.10

0.6

2710

1260

1605

1.64

0.7

2675

1285

1630

1.68

0.8

2640

1305

1654

1.70

0.9

2580

1325

1680

1.73

1.0

2580

1355

1692

1.77

1.1

2550

1365

1727

1.78

1.2

2520

1380

1750

1.80

1.3

2490

1400

1773

1.83

1.4

2455

1425

1791

1.86

1.5

2430

1445

1815

1.88

1.6

2395

1465

1836

1.91

1.7

2370

1480

1857

1.93

1.8

2335

1500

1881

1.96

0.6

2780

1285

1720

1.76

0.7

2745

1305

1746

1.78

0.8

2715

1325

1771

1.81

0.9

2650

1345

1798

1.84

1.0

2650

1370

1814

1.87

1.1

2620

1380

1848

1.89

1.2

2590

1400

1871

1.91

1.3

2560

1425

1895

1.95

1.4

2525

1445

1916

1.97

1.5

2495

1465

1940

2.00

1.6

2465

1480

1962

2.02

1.7

2445

1500

1984

2.05

1.8

2410

1515

2008

2.07

0.6

2810

1295

1780

1.81

0.7

2780

1310

1806

1.83

0.8

2750

1335

1832

1.87

0.9

2685

1355

1858

1.89

1.0

2685

1380

1876

1.93

1.1

2655

1390

1910

1.94

1.2

2625

1415

1932

1.98

1.3

2595

1435

1957

2.01

1.4

2560

1455

1980

2.03

1.5

2535

1470

2004

2.06

1.6

2500

1490

2027

2.08

1.7

2475

1510

2049

2.11

1.8

2445

1525

2073

2.13

T4'

T5'

DFC0723W / DFC0724W / DFC0727W HORIZONTAL

T1'

T2'

T3'

Summary of Contents for DFC0361D

Page 1: ...rsonnel that have been trained to install adjust service or repair hereinafter service the equipment specified in this manual should service the equipment The manufacturer will not be responsible for...

Page 2: ...any part has been under water Immediately call a qualified service technician to inspect the furnace and to replace any part of the control system and any gas control having been under water WARNING...

Page 3: ...transit must be re tightened In the event of damage the receiver should 1 Make notation on delivery receipt of any visible damage to shipment or container 2 Notify carrier promptly and request an insp...

Page 4: ...r or architect Do not skid or slide on any surface as this may damage unit base The unit must be stored on a flat level surface Protect the condenser coil because it is easily damaged Roof Curb Instal...

Page 5: ...sure gasket has been applied properly Gasket should be firmly applied to the top of the curb perimeter duct flanges and any exposed duct connection frame If gasket is loose re apply using strong weath...

Page 6: ...curb prior to installing the unit Ductwork dimensions are shown in Roof Curb Installation Instructions Refer to the Roof Curb Installation Instructions for proper curb installation Curbing must be in...

Page 7: ...t be done in accordance with these instructions the latest edition of the National Electrical Code ANSI NFPA 70 and all local codes and ordinances The unit is factory wired for the voltage shown on th...

Page 8: ...denser end of unit or through the roof curb Install conduit connectors at the desired entrance locations External connectors must be weatherproof All holes in the unit base must be sealed including th...

Page 9: ...on CONDENSATE DRAIN CONNECTION Condensate Drain Connection A 3 4 female NPT drain connection is supplied on the end of the unit and bottom of the drain pan for condensate piping An external trap must...

Page 10: ...ect installation The unit and curb assembly should be level Inspect the flashing of the roof mounting curb to the roof especially at the corners for good workmanship Also check for leaks around gasket...

Page 11: ...HEAT BR X X X X X X X X INDOOR MOTOR TAPS T1 T2 T3 T4 T5 T1 T2 T3 T4 T5 FAN GR X X COOLING STG1 YL X X COOLING STG2 PU X X X X X X HIGH HEAT BR X X X X X X RECOMMENDED SPEED TAPS 3 5T HIGH STATIC RECO...

Page 12: ...ostat at the appropriate setting for cooling and heating or automatic changeover for normal use 14 Be sure the Owner is instructed on the unit operation filter servicing correct thermostat operation e...

Page 13: ...t shut down periods where corrosive deposits accumulate on the MCHE Cleaning Procedure Relative to tube fin heat exchangers MicroChannel heat exchanger coils tend to accumulate more dirt on the surfac...

Page 14: ...ying and prevent pooling Daikin recommends a quarterly cleaning of the coils as the minimum The cleaning frequency should be increased depending on the level of dirt dust accumulation and the environm...

Page 15: ...05 321 0 35 0 6 1315 845 334 0 37 0 7 1260 880 348 0 38 0 8 1205 920 360 0 40 T5 DFC0361D DFC0363D DOWNSHOT T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1110 505 85 0 09 0 2 925 540 100 0 10 0...

Page 16: ...810 322 0 35 0 6 1325 845 334 0 37 0 7 1275 875 346 0 38 0 8 1230 910 357 0 39 T4 DFC0364D DFC0367D DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 965 485 81 0 09 0 2 895 545 89 0 10 0...

Page 17: ...1200 605 0 69 1 7 1085 1230 617 0 70 1 8 1040 1260 631 0 72 T5 T4 DFC0363W DFC0364W DFC0367W DOWNSHOT T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1500 955 474 0 53 0 9 1455 985 486 0 54 1 0 141...

Page 18: ...220 614 0 70 1 7 1070 1250 626 0 71 1 8 1025 1280 640 0 73 T5 DFC0363W DFC0364W DFC0367W HORIZONTAL T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1480 970 481 0 54 0 9 1435 1000 493 0 55 1 0 13...

Page 19: ...570 0 64 0 6 1755 960 585 0 66 0 7 1710 990 601 0 68 0 8 1650 1020 622 0 70 T4 DFC0481D DFC0483D DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1235 610 185 0 19 0 2 1170 660 195 0 20...

Page 20: ...541 0 60 0 6 1720 955 556 0 62 0 7 1670 990 573 0 64 0 8 1620 1015 589 0 66 T5 T4 DFC0484D DFC0487D DOWNSHOT T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1250 615 179 0 19 0 2 1195 660 191 0 20...

Page 21: ...285 952 1 08 1 7 1545 1310 967 1 10 1 8 1510 1325 980 1 11 T4 DFC0483W DFC0484W DFC0487W DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1750 1040 664 0 74 0 9 1695 1070 680 0 76 1 0 164...

Page 22: ...1 1 11 1 7 1530 1350 996 1 13 1 8 1495 1365 1009 1 14 T5 DFC0483W DFC0484W DFC0487W HORIZONTAL T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1735 1070 684 0 76 0 9 1680 1100 700 0 79 1 0 1625 1...

Page 23: ...0 94 0 8 2000 1090 850 0 97 0 9 1950 1115 864 0 99 1 0 1895 1145 882 1 01 T1 T2 T3 DFC0601D DFC0603D DOWNSHOT T4 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1520 705 299 0 32 0 2 1460 750 314 0 34 0...

Page 24: ...2 0 96 0 8 2005 1095 849 0 98 0 9 1960 1120 865 1 00 1 0 1915 1140 883 1 02 DFC0604D DFC0607D DOWNSHOT T1 T2 T3 T4 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1540 705 288 0 31 0 2 1485 740 302 0 32 0...

Page 25: ...365 1222 1 31 1 9 1845 1380 1240 1 32 2 0 1810 1400 1256 1 34 DFC0603W DFC0604W DFC0607W DOWNSHOT T1 T3 T2 T5 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1950 1085 812 0 85 0 9 1920 1105 830 0 87 1 0...

Page 26: ...5 1259 1 35 1 9 1825 1420 1277 1 36 2 0 1790 1440 1294 1 38 T4 T5 DFC0603W DFC0604W DFC0607W HORIZONTAL T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1930 1115 836 0 88 0 9 1900 1140 855 0 90 1 0...

Page 27: ...0 6 2290 1080 932 1 03 0 7 2255 1100 947 1 05 0 8 2220 1120 963 1 07 T4 DFC0723D DFC0724D DFC0727D DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1995 790 452 0 49 0 2 1960 815 466 0 5...

Page 28: ...75 1400 1678 1 76 1 7 2345 1420 1699 1 78 1 8 2310 1440 1720 1 81 T5 T4 DFC0723W DFC0724W DFC0727W DOWNSHOT T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 6 2280 1085 980 1 02 0 7 2240 1110 1000 1 05...

Page 29: ...1450 1745 1 82 1 7 2310 1470 1767 1 85 1 8 2275 1490 1789 1 87 T5 DFC0723W DFC0724W DFC0727W HORIZONTAL T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 6 2245 1125 1019 1 06 0 7 2205 1150 1040 1 0...

Page 30: ...20 18 2 20 4 3 23 5 25 0 5 18 8 20 4 3 0 5 24 2 25 25 7 30 4 3 31 1 35 0 5 26 3 30 4 3 0 5 31 7 35 10 2 15 4 3 14 5 20 0 5 10 7 15 4 3 0 5 15 20 10 6 15 4 3 16 20 0 5 11 3 15 4 3 0 5 16 6 20 18 2 20 4...

Page 31: ...5 47 5 53 2 50 60 9 6 8 7 1 7 1 5 59 5 64 1 60 70 58 1 66 1 60 70 9 6 8 7 70 1 77 0 80 80 1 7 1 5 60 2 68 0 70 70 9 6 8 7 1 7 1 5 72 2 78 8 80 80 11 15 4 3 15 3 20 0 5 11 5 15 4 3 0 5 15 8 20 11 15 4...

Page 32: ...0 39 9 50 50 29 7 29 7 45 45 9 6 8 7 39 3 38 4 50 50 1 7 1 5 31 4 31 2 45 45 9 6 8 7 1 7 1 5 41 0 39 9 50 50 35 7 39 7 45 45 9 6 8 7 47 7 50 6 50 60 1 7 1 5 37 8 41 6 45 45 9 6 8 7 1 7 1 5 49 8 52 4 5...

Page 33: ...5 45 9 6 8 7 1 7 1 5 49 8 52 4 50 60 48 7 54 7 50 60 9 6 8 7 60 7 65 6 70 70 1 7 1 5 50 8 56 6 60 60 9 6 8 7 1 7 1 5 62 8 67 5 70 70 61 5 69 5 70 70 9 6 8 7 73 5 80 3 80 90 1 7 1 5 63 6 71 3 70 80 9 6...

Page 34: ...16 5 20 12 4 15 3 5 15 9 20 0 6 13 15 3 5 0 6 16 5 20 16 8 20 3 5 21 2 25 0 6 17 5 20 3 5 0 6 21 9 25 22 8 25 3 5 27 2 30 0 6 23 5 25 3 5 0 6 27 9 30 28 8 30 3 5 33 2 35 0 6 29 6 30 3 5 0 6 33 9 35 40...

Page 35: ...47 5 8 73 3 8 MODEL SIZE DIM A 3 TON 39 7 8 4 TON 39 7 8 5 TON 39 7 8 6 TON 43 1 2 Horizontal Discharge 5 6 3 16 7 3 8 SUPPLY 12 X 17 RETURN 11 X 25 4 1 2 5 7 8 7 5 8 19 1 2 27 3 4 5 5 16 47 9 16 7 1...

Page 36: ...6 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S06 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S06 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S32 30 EH D S06 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S3...

Page 37: ...FLOAT SWITCH OR SMOKE DETECTOR IS INSTALLED UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE IF MULTIPLE SAFETIES ARE INSTALLED PLUG IN THE ADDITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SA...

Page 38: ...L DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT...

Page 39: ...RE INSTALLED PLUG IN THE ADDITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND...

Page 40: ...INSTALLED PLUG IN THE ADDITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIR...

Page 41: ...41...

Page 42: ...42...

Page 43: ...43 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 44: ...2021 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincom...

Reviews: