background image

12

6.  Set the thermostat to Cool mode and slowly 

lower the cooling temperature until the unit starts. 

The compressor, blower and fan should now be 

operating. Allow the unit to run 10 minutes, make 

sure cool air is being supplied by the unit.

7.  Check that the compressor is operating correctly. 

The scroll compressors in these units MUST operate 

in the proper rotation. To ensure the compressors 

are operating in the correct direction, check the 

compressor discharge line pressure or temperature 

after the compressor is started. The discharge 

pressure and discharge line temperature should 

increase. If this does not occur and the compressor 

is producing an exceptional amount of noise,this 

indicates that there is a phasing issue. Perform the 

following to correct: 

 

 

7.1  Turn power to the unit OFF.

 

7.2  Switch any two leads of power supply at unit    

      Single Point Power Block.

 

7.3  Turn power to the unit ON.

 

7.4  Perform step 7 again.

 

8.  Turn the temperature setting to the highest position, 

stopping the unit. The indoor blower will continue to 

run for 60 seconds.

9.  Turn the thermostat system switch to “OFF” and 

disconnect all power when servicing the unit.

 

 

NOTE: The compressor has 180 second re-start 

delay on timer to avoid short cycling.

WARNING

HIGH VOLTAGE!

Disconnect all power before servicing or 

installing this unit.  Multiple power sources 

may be present.  Failure to do so may cause 

property damage, personal injury or death.

Final System Checks

10. 

Check to see if all supply and return air grilles are 

adjusted and the air distribution system is balanced 

for the best compromise between heating and 

cooling.

11.  Check for air leaks in the ductwork. See Sections on 

Air Flow Adjustments.

12. Make sure the unit is free of “rattles”, and the tubing 

in the unit is free from excessive vibration. Also 

make sure tubes or lines are not rubbing against 

each other or sheet metal surfaces or edges. If so, 

correct the trouble.

13. 

Set the thermostat at the appropriate setting for 

cooling and heating or automatic changeover for 

normal use.

14. Be sure the Owner is instructed on the unit 

operation, filter, servicing, correct thermostat 

operation, etc.

Refrigeration Performance Check

Check that compressor RLA corresponds to values shown 

in Appendix B. RLA draw can be much lower than values 

listed at low load conditions and low ambient condensing 

temperatures. Values in Appendix B can slightly exceed 

at high load conditions and high ambient condensing 

temperatures.

MAINTENANCE

WARNING

HIGH VOLTAGE!

Disconnect all power before servicing or 

installing this unit.  Multiple power sources 

may be present.  Failure to do so may cause 

property damage, personal injury or death.

WARNING

To prevent personal injury or death due to improper in-

stallation, adjustment, alteration, service or maintenance, 

refer to this manual. For additional assistance or informa-

tion, consult a qualified installer, servicer agency or the 

gas supplier. 

CAUTION

Sheet metal parts, screws, clips and similar items inherently 

have sharp edges, and it is necessary that the installer and 

service personnel exercise caution. 

The Self Contained Packaged Air Conditioner should 

operate for many years without excessive service calls if 

the unit is installed properly. However it is recommended 

that the owner inspect the unit before a seasonal start up.  

The coils should be free of debris so adequate airflow is 

achieved. The return and supply registers should be free of 

any obstructions. The filters should be cleaned or replaced. 

These few steps will help to keep the product up time to a 

maximum. The Service section that follows should help in 

identifying problems if the unit does not operate properly.

CAUTION

To prevent property damage due to fire and loss of equip-

ment efficiency or equipment damage due to dust and lint 

build up on internal parts, never operate unit without an air 

filter installed in the return air system.

Filters

Every application may require a different frequency of 

replacement of dirty filters. Filters must be replaced at least 

every three (3) months during operating seasons.

Summary of Contents for DFC0361D

Page 1: ...rsonnel that have been trained to install adjust service or repair hereinafter service the equipment specified in this manual should service the equipment The manufacturer will not be responsible for...

Page 2: ...any part has been under water Immediately call a qualified service technician to inspect the furnace and to replace any part of the control system and any gas control having been under water WARNING...

Page 3: ...transit must be re tightened In the event of damage the receiver should 1 Make notation on delivery receipt of any visible damage to shipment or container 2 Notify carrier promptly and request an insp...

Page 4: ...r or architect Do not skid or slide on any surface as this may damage unit base The unit must be stored on a flat level surface Protect the condenser coil because it is easily damaged Roof Curb Instal...

Page 5: ...sure gasket has been applied properly Gasket should be firmly applied to the top of the curb perimeter duct flanges and any exposed duct connection frame If gasket is loose re apply using strong weath...

Page 6: ...curb prior to installing the unit Ductwork dimensions are shown in Roof Curb Installation Instructions Refer to the Roof Curb Installation Instructions for proper curb installation Curbing must be in...

Page 7: ...t be done in accordance with these instructions the latest edition of the National Electrical Code ANSI NFPA 70 and all local codes and ordinances The unit is factory wired for the voltage shown on th...

Page 8: ...denser end of unit or through the roof curb Install conduit connectors at the desired entrance locations External connectors must be weatherproof All holes in the unit base must be sealed including th...

Page 9: ...on CONDENSATE DRAIN CONNECTION Condensate Drain Connection A 3 4 female NPT drain connection is supplied on the end of the unit and bottom of the drain pan for condensate piping An external trap must...

Page 10: ...ect installation The unit and curb assembly should be level Inspect the flashing of the roof mounting curb to the roof especially at the corners for good workmanship Also check for leaks around gasket...

Page 11: ...HEAT BR X X X X X X X X INDOOR MOTOR TAPS T1 T2 T3 T4 T5 T1 T2 T3 T4 T5 FAN GR X X COOLING STG1 YL X X COOLING STG2 PU X X X X X X HIGH HEAT BR X X X X X X RECOMMENDED SPEED TAPS 3 5T HIGH STATIC RECO...

Page 12: ...ostat at the appropriate setting for cooling and heating or automatic changeover for normal use 14 Be sure the Owner is instructed on the unit operation filter servicing correct thermostat operation e...

Page 13: ...t shut down periods where corrosive deposits accumulate on the MCHE Cleaning Procedure Relative to tube fin heat exchangers MicroChannel heat exchanger coils tend to accumulate more dirt on the surfac...

Page 14: ...ying and prevent pooling Daikin recommends a quarterly cleaning of the coils as the minimum The cleaning frequency should be increased depending on the level of dirt dust accumulation and the environm...

Page 15: ...05 321 0 35 0 6 1315 845 334 0 37 0 7 1260 880 348 0 38 0 8 1205 920 360 0 40 T5 DFC0361D DFC0363D DOWNSHOT T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1110 505 85 0 09 0 2 925 540 100 0 10 0...

Page 16: ...810 322 0 35 0 6 1325 845 334 0 37 0 7 1275 875 346 0 38 0 8 1230 910 357 0 39 T4 DFC0364D DFC0367D DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 965 485 81 0 09 0 2 895 545 89 0 10 0...

Page 17: ...1200 605 0 69 1 7 1085 1230 617 0 70 1 8 1040 1260 631 0 72 T5 T4 DFC0363W DFC0364W DFC0367W DOWNSHOT T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1500 955 474 0 53 0 9 1455 985 486 0 54 1 0 141...

Page 18: ...220 614 0 70 1 7 1070 1250 626 0 71 1 8 1025 1280 640 0 73 T5 DFC0363W DFC0364W DFC0367W HORIZONTAL T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1480 970 481 0 54 0 9 1435 1000 493 0 55 1 0 13...

Page 19: ...570 0 64 0 6 1755 960 585 0 66 0 7 1710 990 601 0 68 0 8 1650 1020 622 0 70 T4 DFC0481D DFC0483D DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1235 610 185 0 19 0 2 1170 660 195 0 20...

Page 20: ...541 0 60 0 6 1720 955 556 0 62 0 7 1670 990 573 0 64 0 8 1620 1015 589 0 66 T5 T4 DFC0484D DFC0487D DOWNSHOT T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1250 615 179 0 19 0 2 1195 660 191 0 20...

Page 21: ...285 952 1 08 1 7 1545 1310 967 1 10 1 8 1510 1325 980 1 11 T4 DFC0483W DFC0484W DFC0487W DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1750 1040 664 0 74 0 9 1695 1070 680 0 76 1 0 164...

Page 22: ...1 1 11 1 7 1530 1350 996 1 13 1 8 1495 1365 1009 1 14 T5 DFC0483W DFC0484W DFC0487W HORIZONTAL T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1735 1070 684 0 76 0 9 1680 1100 700 0 79 1 0 1625 1...

Page 23: ...0 94 0 8 2000 1090 850 0 97 0 9 1950 1115 864 0 99 1 0 1895 1145 882 1 01 T1 T2 T3 DFC0601D DFC0603D DOWNSHOT T4 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1520 705 299 0 32 0 2 1460 750 314 0 34 0...

Page 24: ...2 0 96 0 8 2005 1095 849 0 98 0 9 1960 1120 865 1 00 1 0 1915 1140 883 1 02 DFC0604D DFC0607D DOWNSHOT T1 T2 T3 T4 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1540 705 288 0 31 0 2 1485 740 302 0 32 0...

Page 25: ...365 1222 1 31 1 9 1845 1380 1240 1 32 2 0 1810 1400 1256 1 34 DFC0603W DFC0604W DFC0607W DOWNSHOT T1 T3 T2 T5 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1950 1085 812 0 85 0 9 1920 1105 830 0 87 1 0...

Page 26: ...5 1259 1 35 1 9 1825 1420 1277 1 36 2 0 1790 1440 1294 1 38 T4 T5 DFC0603W DFC0604W DFC0607W HORIZONTAL T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 8 1930 1115 836 0 88 0 9 1900 1140 855 0 90 1 0...

Page 27: ...0 6 2290 1080 932 1 03 0 7 2255 1100 947 1 05 0 8 2220 1120 963 1 07 T4 DFC0723D DFC0724D DFC0727D DOWNSHOT T1 T2 T3 T5 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 1 1995 790 452 0 49 0 2 1960 815 466 0 5...

Page 28: ...75 1400 1678 1 76 1 7 2345 1420 1699 1 78 1 8 2310 1440 1720 1 81 T5 T4 DFC0723W DFC0724W DFC0727W DOWNSHOT T1 T2 T3 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 6 2280 1085 980 1 02 0 7 2240 1110 1000 1 05...

Page 29: ...1450 1745 1 82 1 7 2310 1470 1767 1 85 1 8 2275 1490 1789 1 87 T5 DFC0723W DFC0724W DFC0727W HORIZONTAL T1 T2 T3 T4 TAP STATIC AIRFLOW CFM RPM WATTS BHP 0 6 2245 1125 1019 1 06 0 7 2205 1150 1040 1 0...

Page 30: ...20 18 2 20 4 3 23 5 25 0 5 18 8 20 4 3 0 5 24 2 25 25 7 30 4 3 31 1 35 0 5 26 3 30 4 3 0 5 31 7 35 10 2 15 4 3 14 5 20 0 5 10 7 15 4 3 0 5 15 20 10 6 15 4 3 16 20 0 5 11 3 15 4 3 0 5 16 6 20 18 2 20 4...

Page 31: ...5 47 5 53 2 50 60 9 6 8 7 1 7 1 5 59 5 64 1 60 70 58 1 66 1 60 70 9 6 8 7 70 1 77 0 80 80 1 7 1 5 60 2 68 0 70 70 9 6 8 7 1 7 1 5 72 2 78 8 80 80 11 15 4 3 15 3 20 0 5 11 5 15 4 3 0 5 15 8 20 11 15 4...

Page 32: ...0 39 9 50 50 29 7 29 7 45 45 9 6 8 7 39 3 38 4 50 50 1 7 1 5 31 4 31 2 45 45 9 6 8 7 1 7 1 5 41 0 39 9 50 50 35 7 39 7 45 45 9 6 8 7 47 7 50 6 50 60 1 7 1 5 37 8 41 6 45 45 9 6 8 7 1 7 1 5 49 8 52 4 5...

Page 33: ...5 45 9 6 8 7 1 7 1 5 49 8 52 4 50 60 48 7 54 7 50 60 9 6 8 7 60 7 65 6 70 70 1 7 1 5 50 8 56 6 60 60 9 6 8 7 1 7 1 5 62 8 67 5 70 70 61 5 69 5 70 70 9 6 8 7 73 5 80 3 80 90 1 7 1 5 63 6 71 3 70 80 9 6...

Page 34: ...16 5 20 12 4 15 3 5 15 9 20 0 6 13 15 3 5 0 6 16 5 20 16 8 20 3 5 21 2 25 0 6 17 5 20 3 5 0 6 21 9 25 22 8 25 3 5 27 2 30 0 6 23 5 25 3 5 0 6 27 9 30 28 8 30 3 5 33 2 35 0 6 29 6 30 3 5 0 6 33 9 35 40...

Page 35: ...47 5 8 73 3 8 MODEL SIZE DIM A 3 TON 39 7 8 4 TON 39 7 8 5 TON 39 7 8 6 TON 43 1 2 Horizontal Discharge 5 6 3 16 7 3 8 SUPPLY 12 X 17 RETURN 11 X 25 4 1 2 5 7 8 7 5 8 19 1 2 27 3 4 5 5 16 47 9 16 7 1...

Page 36: ...6 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S06 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S06 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S32 30 EH D S06 5 EH D S11 10 EH D S17 15 EH D S23 20 EH D S3...

Page 37: ...FLOAT SWITCH OR SMOKE DETECTOR IS INSTALLED UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE IF MULTIPLE SAFETIES ARE INSTALLED PLUG IN THE ADDITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SA...

Page 38: ...L DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT...

Page 39: ...RE INSTALLED PLUG IN THE ADDITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND...

Page 40: ...INSTALLED PLUG IN THE ADDITIONAL DEVICES IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIR...

Page 41: ...41...

Page 42: ...42...

Page 43: ...43 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 44: ...2021 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincom...

Reviews: