18
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a
group from the pull-down menu
q
.
Change the temperature setting of air conditioners.
On the Monitoring screen, operation is allowed
with either Icon or List as the display type.
The temperature setting can be switched by zone
or by group.
Selecting a zone and changing the temperature
setting changes the setting of the air conditioner
groups in Cool, Heat, Auto or Temp operation in
the zone.
Selecting a group and changing the temperature
setting changes the temperature setting of air
conditioners in the group selected.
If all of the air conditioners in the group
selected are in Fan operation, temperature
setting cannot be changed.
2.
Select a zone or a group of which the
temperature setting is to be changed
w
.
3.
Press the Set/Prop button
e
.
Screen 2 Operation appears.
4.
Select Set for the Set Point
r
. Set the
integer part of the setting in
t
and the
decimal part in
y
.
Ex.: For the following zone setting, the
temperature settings available are between
20
°
C and 30
°
C inclusive.
When the temperature setting is 30
°
C, the
actual temperature settings for air
conditioners are as shown below:
Note: Range of temperature settings available is
the range specified in accordance with the
following.
●
Range of temperature setting inherent to
the air conditioner main unit.
●
Range of temperature as a result of the
restriction by the temperature setting limit.
5.
Changing the Temperature Setting
Screen 2 Operation
1
2
3
4
5
6
7
To cancel the setting, press the Cancel
button.
On the menu, temperature settings
available for air conditioners in the zone
are displayed if the setting is to be made
by the zone. See the example below.
Press the OK button
u
.
Zone name
Group name
Range of temperature
settings available
(see Note)
Group name
Temperature setting
Canteen
1F North
25 to 30
°
C
20 to 25
°
C
1F West
1F North
30
°
C
25
°
C
1F West
[Procedure]
See page
44
Oper
ation