BLOWER PERFORMANCE DATA
DCG060-072XXX*HXXXA*
NOTES:
Factory shipped at 2.5 turns open.
Tables represent dry coil without filter. To compensate for filter, add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4%.
***
NOTE:
High static airflow requires installation of high static kit (HSKT*).
BELT DRIVE - 5 & 6 TON
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
2219
0.95
1970
0.75
0.8
2215
1.04
1956
0.82
1697
0.62
1.0
2240
1.15
1957
0.90
1681
0.67
1.2
2260
1.26
1983
1.00
1683
0.74
1.4
2288
1.38
2009
1.10
1711
0.84
1.6
2032
1.21
1741
0.93
1.8
1776
1.04
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
2262
1.16
2051
0.95
1851
0.76
1657
0.60
0.8
2277
1.27
2070
1.05
1852
0.84
1646
0.66
1.0
2304
1.39
2089
1.15
1872
0.93
1647
0.72
1.2
2104
1.26
1893
1.03
1668
0.81
1.4
1912
1.13
1690
0.90
1.6
1720
1.00
ESP (IN
W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
2677
1.29
2486
1.07
0.8
2690
1.42
2529
1.20
2263
0.94
1
2740
1.60
2471
1.27
2246
1.02
1972
0.79
1.2
2748
1.74
2518
1.44
2255
1.13
1970
0.87
1.4
2797
1.87
2562
1.59
2273
1.27
2025
0.99
1.6
2556
1.67
2314
1.40
2035
1.11
1.8
2342
1.50
2037
1.21
2
2137
1.35
ESP (IN
W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
2793
1.64
2575
1.37
2407
1.15
2250
0.96
0.8
2775
1.76
2638
1.53
2407
1.25
2226
1.04
2011
0.84
1
2821
1.89
2660
1.67
2407
1.36
2194
1.12
2012
0.92
1.2
2696
1.79
2497
1.54
2228
1.23
1977
0.98
1.4
2455
1.59
2236
1.35
2013
1.10
1.6
2262
1.44
2032
1.20
1.8
2069
1.30
DCG 072 HIGH STATIC BELT DRIVE DOWNSHOT
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS
DCG 072 HIGH STATIC BELT DRIVE HORIZONTAL FLOW
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS
DCG060 HIGH STATIC BELT DRIVE DOWNSHOT
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS
DCG060 HIGH STATIC BELT DRIVE HORIZONTAL FLOW
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS