PACKAGE GAS SPECIFICATIONS
(1)
Units installed in Canada are certifed only to 4500 feet.
(2)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
IMPORTANT:
While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in
accordance with the National Electrical Code and/or all local codes.
DCG036-072XXX3BXXXA*
DCG0360453BXXX
A*
DCG0360903BXXX
A*
DCG0480903BXXX
A*
DCG0481153BXXX
A*
DCG0601403BXXX
A*
DCG0721403BXXX
A*
COOLING
COOLING CAPACITY, BTUH
34,600
34,600
45,500
45,500
58,000
71,000
CAPACITY
SEER/EER
13/11.0
13/11.0
13/11.3
13/11.3
13/11.1
11.0
HEATING
HIGH HEATING INPUT / OUTPUT BTUH
46,000 / 36,800
92,000 / 74,000
92,000 / 74,000
115,000 / 92,000
138,000 / 110,400
138,000 / 110,400
CAPACITY
LOW HEATING INPUT / OUTPUT BTUH
---
69,000 / 55,000
69,000 / 55,000
86,250 / 69,000
103,000 / 83,000
103,000 / 83,000
STEADY STATE EFFY %
80
80
80
80
80
80
TEMPERATURE RISE (°F) HI/LOW
25 - 55
40 - 70 / 30 - 60
30 - 60 / 15 - 45
40-70 / 25-55
35 - 65 / 25 - 55
35 - 65 / 25 - 55
UNIT
VOLTAGE (NAMEPLATE)
208-230/3/60
208-230/3/60
208-230/3/60
208-230/3/60
208-230/3/60
208-230/3/60
ELECTRICAL
UNIT AMPS (TOTAL)
15.7
15.7
18.3
18.3
21.2
22.4
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
18
18
22
22
25
31
MAXIMUM OVERCURRENT PROTECTION
(2)
25
25
30
30
40
45
HEATING
NUMBER OF BURNERS
2
4
4
5
6
6
SECTION
ORIFICE SIZE NATURAL
43
43
43
43
43
43
ORIFICE SIZE LP
55
55
55
55
55
55
PRESSURE SWITCH SETTING
0.34
0.34
0.34
0.34
0.34
0.34
COMPRESSOR
TYPE
SCROLL
SCROLL
SCROLL
SCROLL
SCROLL
SCROLL
RATED LOAD AMPS
10.4
10.4
13.1
13.1
16
16
LOCKED ROTOR AMPS
73
73
83.1
83.1
110
110
CONDENSER
HORSEPOWER
1/4
1/4
1/4
1/4
1/4
1/4
FAN MOTOR
RPM
1090
1090
1090
1090
1090
1090
RATED LOAD AMPS
1.4
1.4
1.40
1.40
1.4
1.4
LOCKED ROTOR AMPS
2.9
2.9
2.9
2.9
2.9
4.0
BLADE DIAMETER( ") / # OF BLADES
22/4
22/4
22/4
22/4
22/4
22/4
NOMINAL CFM
3,800
3,800
3,800
3,800
3,800
3,800
CONDENSER
FACE AREA - SQ. FT.
17
18
17
17
12.5
19
COIL
NUMBER OF ROWS
1
1
1
1
2
2
FINS PER INCH
24
22
24
24
27
27
EVAPORATOR
HORSEPOWER - TYPE - STANDARD
1.0 - STD STATIC
BELT DRIVE
1.0 - STD STATIC
BELT DRIVE
1.0 - STD STATIC
BELT DRIVE
1.0 - STD STATIC
BELT DRIVE
1.0 - STD STATIC
BELT DRIVE
1.5 - ST D STATIC
BELT DRIVE
BLOWER
NO. OF SPEEDS
1
1
1
1
1
1
MOTOR
RATED LOAD AMPS
3.8
3.8
3.8
3.8
3.8
5
LOCKED ROTOR AMPS
10.9
10.9
10.9
10.9
24
18
MOTOR SPEED TAP - COOLING
---
---
---
---
---
---
RPM
1725
1725
1725
1725
1725
1725
EVAPORATOR
DIAMETER X WIDTH (INCHES)
11 X 10
11 X 10
11 x 10
11 x 10
11 X 10
11 X 10
BLOWER
RATED SCFM COOLING
1200
1200
1600
1600
2000
2400
MAX EXTERNAL STATIC PRESS ("w.c.)
0.7
0.7
1.0
1.0
1.0
1.0
EVAPORATOR
FACE AREA - SQ. FT.
5.4
5.4
7.8
7.8
7.8
7.8
COIL
NUMBER OF ROWS
3
3
4
4
4
4
FINS PER INCH
16
16
16
16
16
16
HEATING
PRIMARY LIMIT SETTING (°F)
140
120
140
140
220
140
LIMITS
AUXILIARY LIMIT SETTING (°F)
120
150
145
150
145
150
ROLLOUT LIMIT SETTING (°F)
350
350
350
350
350
350
GENERAL
FILTER SIZE
(1) 24"X 24" x 2"
(1) 24"X 24" x 2"
(4) 14"X 20" x 2"
(4) 14"X 20" x 2"
(4) 14"X 20" x 2"
(4) 14"X 20" x 2"
INFORMATION
DRAIN SIZE (INCHES)
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
EXPANSION DEVICE
Orifice (0.072)
Orifice (0.068)
Orifice (0.076)
Orifice (0.076)
ORIFICE (0.086)
ORIFICE (0.094)
REFRIGERANT CHARGE R-410A (Oz.)
85
83
105
103
100.8
146
POWER SUPPLY CONDUIT HOLE (")
1.125
1.125
1.125
1.125
1.125
1.125
LOW VOLTAGE CONDUIT HOLE
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
LOW PRESSURE SWITCH (OPEN/CLOSE-PSIG)
22/50
22/50
22/50
22/50
55/95
55/95
HIGH PRESSURE SWITCH (OPENS-PSIG)
660
660
660
660
660
660
SHIPPING WEIGHT LBS.
550
560
600
605
645
700
OPERATING WEIGHT LBS.
525
535
575
580
620
675
CONDENSER FAN