BLOWER PERFORMANCE DATA
NOTES:
Factory shipped at 2.5 turns open.
Tables represent dry coil without filter. To compensate for filter, add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4%.
***
NOTE:
High static airflow requires installation of high static kit (HSKT*).
DCG036-048XXX*BXXXA*
BELT DRIVE - 3 & 4 TON
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
1524
0.32
1340
0.25
0.4
1628
0.41
1396
0.32
1171
0.24
900
0.16
0.6
1541
0.43
1284
0.32
1024
0.23
714
0.14
0.8
1444
0.45
1193
0.33
936
0.24
1.0
1111
0.34
806
0.23
1.2
744
0.22
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
1596
0.36
1368
0.28
1162
0.21
0.4
1468
0.37
1224
0.28
981
0.20
0.6
1610
0.51
1383
0.39
1124
0.28
856
0.19
0.8
1293
0.40
1021
0.29
776
0.20
1.0
948
0.29
614
0.17
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
1800
0.47
1556
0.35
0.4
2002
0.65
1708
0.49
1438
0.36
1167
0.22
0.6
1910
0.67
1612
0.50
1330
0.37
1030
0.23
0.8
1813
0.69
1571
0.54
1222
0.36
989
0.25
1.0
1478
0.56
1142
0.32
1.2
1107
0.41
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
1891
0.56
1632
0.42
1391
0.30
0.4
1796
0.57
1533
0.43
1290
0.31
1055
0.19
0.6
1948
0.74
1744
0.61
1446
0.44
1206
0.32
910
0.19
0.8
1654
0.63
1409
0.48
1096
0.31
1.0
1337
0.50
987
0.28
DCG048 STANDARD BELT DRIVE DOWNSHOT
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS
DCG048 STANDARD BELT DRIVE HORIZONTAL FLOW
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS
DCG036 STANDARD BELT DRIVE DOWNSHOT
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS
DCG036 STANDARD BELT DRIVE HORIZONTAL FLOW
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS